TOWER PERFORMANCE–Keep the cooling tower clean and water dis- tribution uniform to obtain continued maximum cooling capacity.

The capacity of a cooling tower to cool water to a given cold water tem- perature varies with the wet-bulb temperature and the heat load applied to the cooling tower.

As the wet-bulb temperature drops, the cold water temperature also drops. However, the cold water temperature does not drop linearly with the wet-bulb temperature.

A cooling tower will not control heat load. The flow rate of water circulated through the cooling tower will determine the temperature range of cool- ing in conjunction with a given heat load. The hot water and cold water temperatures will increase with higher heat loads.

HOT WATER DISTRIBUTION SYSTEM–Maintain uniform water distribu- tion at the nozzles (uniform spray cone). The amount of water circulated should approximate the contract requirements and the nozzle pressure should be kept constant. Lower pressures may indicate excessive losses in the piping system and/or insufficient pump capacity; greater pressures might indicate clogged nozzles and/or overpumping. If a greatly reduced water flow rate is desired, it may be advisable to change nozzle sizes to obtain the desired pressure and maintain proper water distribution. An SPX Cooling Technologies engineer can advise minimum and maximum flow rates for even distribution.

COLD WATER COLLECTION BASIN–A suitable depth must be maintained to keep the pumps from pulling air into the line. The amount of “make-up” water required to keep the water in the collection basin at the required depth depends upon the “evaporation loss” and “blowdown” .

FAN DRIVE–When using two-speed motors, allow a time delay of 20 seconds minimum after de-energizing the high-speed winding and before energizing the low-speed winding. Tremendous stresses are placed on driven machinery and motors unless the motors are allowed to slow to low-speed RPM or less before the low-speed winding is energized.

COLD WEATHER OPERATION–During periods of low temperature op- eration, 35°F to 40°F or below, ice will form on the relatively dry parts of the cooling tower that are in contact with the incoming air. Primarily, this includes the air inlet and adjacent structural framing. Your understanding of

5

Image 5
Contents Marley Class F400 Cooling Tower Contents Before Start-up Operation Starting ProcedurePage Tower Maintenance Drift ELIMINATORS-Eliminators should be kept clean BLOWDOWN-% of Circulating Rate Water TreatmentMaintenance of Fill Performance Page ClassF400 Seasonal Shutdown Instructions Spare PartsGeareducer shutdown for 3 months or more Cooling Tower CleaningTrouble Cause Remedy TroubleshootingDavits, Derricks, and Hoists General Recommendations Inspection and Maintenance ScheduleInspection and Maintenance Notes Heat Transfer System StructureWater Distribution System RPM Mechanical EquipmentManual 93-1288A
Related manuals
Manual 8 pages 51.97 Kb

F400 specifications

The SPX Cooling Technologies F400 is an advanced cooling tower renowned for its robust design, efficiency, and versatility in industrial applications. Engineered with cutting-edge technologies, the F400 addresses the demanding thermal management needs of various sectors, including power generation, oil and gas, and manufacturing.

One of the standout features of the F400 is its modular design, allowing for seamless scalability. This design enables businesses to adapt their cooling solutions to fluctuating demand without compromising on performance. The ability to integrate multiple units into a singular system provides flexibility in addressing specific cooling needs while maintaining operational efficiency.

The F400 employs patented air and water flow technologies that enhance its heat transfer capabilities. The combination of optimized fan design and advanced drift eliminators maximizes air circulation while minimizing water loss, making it an environmentally friendly choice. The use of high-efficiency fans contributes to lower energy consumption, thus reducing operational costs and supporting sustainability initiatives.

Another key characteristic of the F400 is its durable construction. Built with corrosion-resistant materials and components, it is designed to withstand harsh environmental conditions, ensuring longevity and reliability. The tower's modular fill design enhances thermal performance while simplifying maintenance, as individual components can be accessed easily for inspection and cleaning.

The F400 is equipped with advanced monitoring and control systems that enable real-time performance assessments. These systems provide operators with valuable insights into operational efficiency, enabling proactive maintenance and troubleshooting, further enhancing productivity while reducing downtime.

Additionally, the F400’s quiet operation is a significant benefit for installations in urban or noise-sensitive areas. The sound suppression features ensure that the cooling tower blends seamlessly into its surroundings without causing disturbances.

Overall, the SPX Cooling Technologies F400 represents a significant leap forward in cooling tower technology, combining efficiency, adaptability, and durability. Its features make it a leading choice for industries that require dependable cooling solutions, underscoring SPX Cooling Technologies' commitment to innovation and excellence in thermal management.