Troubleshooting

Trouble

Cause

Remedy

Wrong Rotation (Motor)

Wrong sequence of phases

Change any two of the three motor leads.

 

 

 

Geareducer Noise

Geareducer bearings

If new, see if noise disappears after one week of operation.

 

 

Drain, flush and refill Geareducer. See Geareducer User Manual.

 

 

If still noisy, replace.

 

Gears

Correct tooth engagement. Replace badly worn gears. Replace

 

 

gears with imperfect tooth spacing or form.

 

 

 

Unusual Fan Drive

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment

Vibration

 

and supports.

 

 

 

 

Unbalanced drive shaft or worn

Make sure motor and Geareducer shafts are in proper alignment

 

couplings

and “match marks” properly matched. Repair or replace worn

 

 

couplings. Rebalance drive shaft by adding or removing weights

 

 

from balancing cap screws. See Drive Shaft User Manual.

 

 

 

 

Fan

Make certain all blades are as far from center of fan as safety

 

 

devices permit. All blades must be pitched the same. See Fan

 

 

User Manual. Clean off deposit build-up on blades.

 

Worn Geareducer bearings

Check fan and pinion shaft endplay. Replace bearings as

 

 

necessary.

 

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates, rebal-

 

 

ance rotor.

 

Bent Geareducer shaft

Check fan and pinion shaft with dial indicator. Replace if neces-

 

 

sary.

 

 

 

Fan Noise

Loose fan hub cover

Tighten hub cover fasteners.

 

Blade rubbing inside of fan cylinder

Adjust cylinder to provide blade tip clearance.

 

 

 

 

Loose bolts in blade clamps

Check and tighten if necessary.

 

 

 

SAFETY FIRST–The tower has been designed to provide a safe working environment while either operating or shut down. The ultimate responsibility for safety rests with the Operator and Owner. When flow to the tower is shut off or when portions of the tower require maintenance, temporary safety barricades may be required around openings, and other safety precautions such as safety harnesses should be utilized where appropriate for compliance with OSHA regulations and standards and good safety practices.

Routine periodic maintenance must

 

 

Ladders, Stairways,￿

 

be performed on all personnel access

 

Walkways, Handrails, Covers,￿

Davits, Derricks, and Hoists

and material handling accessories in

Decks and￿

accordance with the following schedule:

 

Access Doors

 

 

 

 

Inspect for General Condition

Semi-annually

Semi-annually

 

 

 

Inspect and Repair for Safe Use

Yearly

 

 

 

 

Inspect and Repair Before Each Use

 

As Required

 

 

 

15

Image 15
Contents Marley Class F400 Cooling Tower Contents Before Start-up Operation Starting ProcedurePage Tower Maintenance Drift ELIMINATORS-Eliminators should be kept clean BLOWDOWN-% of Circulating Rate Water TreatmentMaintenance of Fill Performance Page ClassF400 Seasonal Shutdown Instructions Spare PartsGeareducer shutdown for 3 months or more Cooling Tower CleaningTrouble Cause Remedy TroubleshootingDavits, Derricks, and Hoists General Recommendations Inspection and Maintenance ScheduleInspection and Maintenance Notes Structure Water Distribution SystemHeat Transfer System RPM Mechanical EquipmentManual 93-1288A
Related manuals
Manual 8 pages 51.97 Kb

F400 specifications

The SPX Cooling Technologies F400 is an advanced cooling tower renowned for its robust design, efficiency, and versatility in industrial applications. Engineered with cutting-edge technologies, the F400 addresses the demanding thermal management needs of various sectors, including power generation, oil and gas, and manufacturing.

One of the standout features of the F400 is its modular design, allowing for seamless scalability. This design enables businesses to adapt their cooling solutions to fluctuating demand without compromising on performance. The ability to integrate multiple units into a singular system provides flexibility in addressing specific cooling needs while maintaining operational efficiency.

The F400 employs patented air and water flow technologies that enhance its heat transfer capabilities. The combination of optimized fan design and advanced drift eliminators maximizes air circulation while minimizing water loss, making it an environmentally friendly choice. The use of high-efficiency fans contributes to lower energy consumption, thus reducing operational costs and supporting sustainability initiatives.

Another key characteristic of the F400 is its durable construction. Built with corrosion-resistant materials and components, it is designed to withstand harsh environmental conditions, ensuring longevity and reliability. The tower's modular fill design enhances thermal performance while simplifying maintenance, as individual components can be accessed easily for inspection and cleaning.

The F400 is equipped with advanced monitoring and control systems that enable real-time performance assessments. These systems provide operators with valuable insights into operational efficiency, enabling proactive maintenance and troubleshooting, further enhancing productivity while reducing downtime.

Additionally, the F400’s quiet operation is a significant benefit for installations in urban or noise-sensitive areas. The sound suppression features ensure that the cooling tower blends seamlessly into its surroundings without causing disturbances.

Overall, the SPX Cooling Technologies F400 represents a significant leap forward in cooling tower technology, combining efficiency, adaptability, and durability. Its features make it a leading choice for industries that require dependable cooling solutions, underscoring SPX Cooling Technologies' commitment to innovation and excellence in thermal management.