Toshiba RAV-SM2802DT-E Gas side refrigerant pipe connection, Evacuation, Tightening connection

Page 24

Concealed Duct High Static Pressure

Tightening connection

CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit: N•m)

 

 

Outer dia. of copper pipe

Tightening torque

 

 

12.7 mm (dia.)

50 to 62 (5.0 to 6.2 kgf•m)

 

 

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.

(Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque.

Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union Flare nut

Externally

 

 

Internally

 

threaded side

 

 

threaded side

 

 

 

 

 

 

Use a wrench to secure.

Use a torque wrench to tighten.

REQUIREMENT

Tightening with an excessive torque may crack the nut depending on installation conditions.

Tighten the nut within the specified tightening torque.

Installation Manual

Remove the cup on the gas side piping by using a brazing machine.

CAUTION

Do not burn the pipe heat insulator.

Remove the cap.

Attached joint part

Connection pipe Locally procured Ø28.6 mm

Braze the attached joint part to the gas side piping and braze the connection piping to the joint part.

brazing

Braze all around

brazing

Turn back the pipe heat insulator and tie up with a banding band.

Tie up with a banding

band.

!Gas side refrigerant pipe connection

Turn up the pipe heat insulator to the unit side.

Wrap the pipe with wet cloth.

Piping with outdoor unit

For details of installation, refer to the Installation Manual of the outdoor unit.

!Evacuation

Wet cloth

Turn up pipe heat insulator

Remove the all brazed part.

Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.

For details, follow to the Installation Manual attached to the outdoor unit.

Never use the refrigerant sealed in the outdoor unit for evacuation.

REQUIREMENT

For the tools such as charge hose, etc., use those manufactured exclusively for R410A.

23-EN

– 23 –

Image 24
Contents Installation Manual Contents Concealed Duct High Static Pressure Installation Manual Agent Qualifications and knowledge which the agent must haveWork undertaken Protective gear worn Burst Hazard Precautions for Safety Selection of installation locationInstallation GeneralElectrical wiring Test runExplanations given to user RelocationTo Disconnect the Appliance from Main Power Supply Accessory Parts Part name ’tyUsage Selection of Installation Place Installation under high-humidity atmosphereAvoid installing in the following places Installation space Filter cleaning sign term settingInstallation example Unit mmInstallation External DimensionsInstallation of hanging bolt Installation of indoor unitInstallation of hanging bolt Treatment of ceilingDiagrams for making connecting flanges Air inlet port connecting flangeAir outlet port flange Duct installation example First floor Duct designFAN Characteristics RAV-SM2242 TypeRAV-SM2802 Type Wire connection change of fan motor Low static pressure F1Standard Middle static pressure F2 High static pressure F3Drain Piping Work Connecting drain pipe Pipe material, size and insulatorDrain up Pipe materialCheck the draining Heat insulating process Refrigerant Piping and Evacuating Refrigerant PipingPipe size Liquid side refrigerant pipe connectionGas side refrigerant pipe connection EvacuationTightening connection Piping with outdoor unitRefrigerant amount to be added Open the valve fullyGas leak check Heat insulation processWiring diagram Power and Wiring SpecificationRemote controller wiring WiringWire connection Terminal block of electrical control boxRemote Controller Wiring Wiring diagramGroup control Changing of setting applicable control When power is turned on for the second or later timeBasic procedure for changing settings Applicable ControlsFilter sign setting Power saving modeDetection temperature shift value To secure better effect of heatingRemote controller switch monitoring function Outdoor unit dataCode No Data name Indoor unit dataGroup control Group control for system of multiple unitsProcedure example Manual address setup procedure33-EN 8C Operation 000010TEST RUN Before test runExecute a test run 11MAINTENANCE Daily maintenance Cleaning of air filterMaintenance List Part Unit Check visual/auditory Maintenance12TROUBLESHOOTING Confirmation of error logConfirmation and check Error codes and parts to be checked Status40-EN
Related manuals
Manual 110 pages 30.72 Kb

RAV-SM2242DT-E, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.