Toshiba RAV-SM2802DT-E Filter sign setting, To secure better effect of heating, Power saving mode

Page 30

Concealed Duct High Static Pressure

Installation Manual

 

Procedure 6

When settings have been completed, push button to determine the settings.

When button is pushed, “SETTING” flashes and then the display content disappears and the air conditioner enters the normal stop mode.

(While “SETTING” is flashing, no operation of the remote controller is accepted.)

!Filter sign setting

According to the installation condition, the filter sign term (Notification of filter cleaning) can be changed.

Follow to the basic operation procedure

(1 2 3 4 5 6).

For the CODE No. in Procedure 3, specify [01].

For the [SET DATA] in Procedure 4, select the SET DATA of filter sign term from the following table.

SET DATA

Filter sign term

 

 

0000

None

 

 

0001

150H

 

 

0002

2500H

(Factory default)

 

 

 

0003

5000H

 

 

0004

10000H

 

 

!To secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling. Follow to the basic operation procedure

(1 2 3 4 5 6).

For the CODE No. in Procedure 3, specify [06].

For the set data in Procedure 4, select the SET DATA of shift value of detection temperature to be set up from the table below.

SET DATA

Detection temperature shift value

 

 

0000

No shift

 

 

0001

+1°C

 

 

0002

+2°C

(Factory default)

 

 

 

0003

+3°C

 

 

0004

+4°C

 

 

0005

+5°C

 

 

0006

+6°C

 

 

!Power saving mode

1.Push button for at least four seconds when the air conditioner is not working.

flashes.

Indicates CODE No. “C2.”

2.Select an indoor unit to be set by pushing (left side of the button).

Each time you push the button, unit numbers change as follows:

UNIT No.

 

UNIT No.

 

UNIT No.

1-1

 

1-2

 

1-3

UNIT No. 1-4

The fan of the selected unit runs.

3.Adjust the power save setting by pushing TIME buttons.

Each push of the button changes the power level by 1% within the range from 100% to 50%.

* The factory default is 75%.

Setting of power level in power saving mode

4.Determine the setting by pushing button.

5.Push button to complete the setting.

29-EN

– 29 –

Image 30
Contents Installation Manual Contents Concealed Duct High Static Pressure Installation Manual Agent Qualifications and knowledge which the agent must haveWork undertaken Protective gear worn Burst Hazard Installation Precautions for SafetySelection of installation location GeneralExplanations given to user Electrical wiringTest run RelocationTo Disconnect the Appliance from Main Power Supply Accessory Parts Part name ’tyUsage Selection of Installation Place Installation under high-humidity atmosphereAvoid installing in the following places Installation example Installation spaceFilter cleaning sign term setting Unit mmInstallation External DimensionsInstallation of hanging bolt Installation of hanging boltInstallation of indoor unit Treatment of ceilingDiagrams for making connecting flanges Air inlet port connecting flangeAir outlet port flange Duct installation example First floor Duct designFAN Characteristics RAV-SM2242 TypeRAV-SM2802 Type Standard Middle static pressure F2 Wire connection change of fan motorLow static pressure F1 High static pressure F3Drain Piping Work Drain up Connecting drain pipePipe material, size and insulator Pipe materialCheck the draining Heat insulating process Pipe size Refrigerant Piping and EvacuatingRefrigerant Piping Liquid side refrigerant pipe connectionTightening connection Gas side refrigerant pipe connectionEvacuation Piping with outdoor unitGas leak check Refrigerant amount to be addedOpen the valve fully Heat insulation processRemote controller wiring Wiring diagramPower and Wiring Specification WiringWire connection Terminal block of electrical control boxRemote Controller Wiring Wiring diagramGroup control Basic procedure for changing settings Changing of setting applicable controlWhen power is turned on for the second or later time Applicable ControlsDetection temperature shift value Filter sign settingPower saving mode To secure better effect of heatingCode No Data name Remote controller switch monitoring functionOutdoor unit data Indoor unit dataGroup control Group control for system of multiple unitsProcedure example Manual address setup procedure33-EN 8C Operation 000010TEST RUN Before test runExecute a test run 11MAINTENANCE Daily maintenance Cleaning of air filterMaintenance List Part Unit Check visual/auditory Maintenance12TROUBLESHOOTING Confirmation of error logConfirmation and check Error codes and parts to be checked Status40-EN
Related manuals
Manual 110 pages 30.72 Kb

RAV-SM2242DT-E, RAV-SM2802DT-E specifications

Toshiba has long been a leader in heating, ventilation, and air conditioning (HVAC) technology, offering innovative solutions that cater to both residential and commercial needs. Among their impressive lineup, the Toshiba RAV-SM2802DT-E and RAV-SM2242DT-E stand out as exceptional models designed for efficiency, performance, and comfort.

The RAV-SM2802DT-E is a powerful unit ideal for larger spaces, boasting a cooling capacity of 28,000 BTU/h and a heating capacity of 31,000 BTU/h. This model features a highly efficient inverter compressor, which adjusts the power consumption based on the cooling or heating demand, ensuring optimal energy use. This inverter technology not only reduces energy consumption but also maintains a stable indoor temperature for enhanced comfort.

On the other hand, the RAV-SM2242DT-E is tailored for mid-sized applications with a cooling capacity of 22,000 BTU/h and a heating capacity of 25,000 BTU/h. This model also embraces inverter technology, promoting lower operational costs while delivering reliable performance. Both units come with a high energy efficiency rating, reducing environmental impact and saving on utility bills.

One of the key characteristics of these Toshiba models is their advanced filtration system. Equipped with a high-performance filtration mechanism, they can effectively reduce dust, allergens, and other pollutants, ensuring a healthier indoor environment. The units also operate quietly, contributing to a peaceful atmosphere, whether in a home, office, or commercial space.

Both the RAV-SM2802DT-E and RAV-SM2242DT-E are designed with user convenience in mind. They come with a user-friendly remote control, allowing for easy adjustments and settings from anywhere in the room. Compatibility with smart home systems further enhances user experience by enabling remote monitoring and control through smartphones or tablets.

Constructed with durability in mind, these units are built to withstand diverse weather conditions, making them suitable for various climatic environments. Additionally, their aesthetic design allows for seamless integration into any setting, ensuring that performance does not compromise on looks.

In summary, Toshiba's RAV-SM2802DT-E and RAV-SM2242DT-E offer a blend of superior technology, energy efficiency, and user-friendly features. With their inverter technology, advanced filtration systems, and durable designs, these models represent Toshiba's commitment to quality and innovation in the HVAC industry. Whether for residential or commercial applications, these units guarantee comfort and reliability all year round.