Roberts Gorden 400 Check Gas Rate, Pressure Switch, Turning Off the Heater, Complete the Start-Up

Page 27

SECTION 10: OPERATION AND MAINTENANCE

10.2.2Start-Up the Gas Valve (All Gases) 10.2.2.1 Check Burner Gas Pressure

1. Remove the plug in the outlet (burner) pressure test point and connect a pressure tap and a manometer.

2.With the burner firing, measure the pressure on the manometer. To adjust the burner pressure, remove the regulator cover from the valve and turn the regulator adjustment screw to set the required burner pressure as stated in the Technical Data Tables for the correct gas and model on Page 38, Section 15.3.

NOTE: If the correct burner pressure cannot be reached, then check the inlet pressure to the valve with the burner firing. See Technical Data Tables on Page 38, Section 15.3 for inlet pressure requirement.

Do not continue to adjust the regulator if the pressure is not changing.

If the inlet pressure is too low to allow correct burner pressure setting, then the gas inlet pressure must be corrected before completing the commission.

Check Gas Rate

1.After burner pressure adjustment, allow the heater to operate for at least 15 minutes and then re-check settings. Adjust pressure setting if necessary.

2.Check gas flow rate at gas meter.

3.Turn off heater and electrical supply.

4.Remove the manometer and refit all covers to the valve and tighten the screw of the outlet pressure tap.

10.2.3 Pressure Switch

The pressure switch is factory pre-set for each model and is not adjustable.

10.2.4 Turning Off the Heater

Set the thermostat to the "OFF" position or lowest setting and the main burner will stop.

The fan will run until it is stopped automatically by the fan thermostat.

Do not use a disconnect switch for control of heater. Disconnect switch will turn off the fan. Heat exchanger could be damaged. Warranty will not cover damage to the heat exchanger if operated improperly. Only use the disconnect switch for turning off heater for service or during off-season.

10.2.5 External Controls

External controls may include time switch, interlock switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the switches (if fitted) and thermostat(s) to the users’ requirements.

10.3 Complete the Start-Up

Ensure that all covers are fitted correctly and all test points are properly sealed.

10.3.1 Instruction to the User

Explain the controls of the heater to the user including how to turn it on and off, using the controls fitted on site.

Give this manual to the user.

Ensure that the user is shown and understands the importance of maintaining clearances to combustibles and the user instructions on Page 22, Section 11 through Page 22, Section 11.5 and all warnings defined in this manual.

21

Image 27
Contents Combat Page Roberts-Gordon, LLC Page Table of Figures Page Manpower Requirements Heater SafetyNational Standards and Applicable Codes Installer ResponsibilityWall Tag Corrosive ChemicalsClearances to Combustibles Minimum Required Installation ClearancesSeparated Combustion Installation Critical Considerations 3.1 Basic InformationInstallation Clearances and Clearances to Combustibles National Standards and Applicable Codes Suspension Major Components 5.1 GeneralCanadian Requirements Vent InstallationVenting 6.1 Venting United States RequirementsVertical Venting Separated Combustion Heaters Models Uhas 150Unvented Operation Horizontal VentingVent and Roof Detail Vent MaterialStandard Vented Heater Common Vertical Vent Termination Concentric Vent Box Horizontal Outside Combustion Air Supply Unvented InstallationAIR Supply Building VentilationConnections GAS PipingLow Voltage Thermostat with One Heater WiringPositioning Thermostats Fan ControlTransformer Uhas Series Internal Wiring DiagramUhas Series Ladder Wiring Diagram Electrical Connection to the Heater Mechanical Checks Operation and MaintenanceLouvers Electrical ChecksAutomatic Burner Control Sequence Complete the Start-Up Pressure SwitchCheck Gas Rate Turning Off the HeaterTo Turn the Heater Off Simple TroubleshootingSimple Troubleshooting Burner Faults Heater OperationUser Instructions Gas Valve Maintenance Burner Maintenance12.3 Fan/Motor Assembly Maintenance Heat Exchanger MaintenanceVehicles and Other Maintenance ChecklistInstallation Code and Annual Inspections All Vicinity of the HeaterCombustion Fan Scroll When installedBurner Observation WindowTroubleshooting 13.1 General Result in death or electrical shock Troubleshooting For Automatic Ignition Burner SystemsStart Troubleshooting for Flame Supervision SystemTroubleshooting for Gas Valves Troubleshooting for Combustion FanConduct start-up procedure as shown on Page 19, Section Burner Components Replacement PartsBurner Injectors Burner CompartmentDescription Part Number Qty Ignition Electrode and Flame ProbeCombustion Fan Vertical Installation Uhas To Replace the Fan Assembly Axial Fan/Guard/Motor AssemblyLimit Switches Removal and Replacement Fan Removal and ReplacementStandard Models 150 400 Uhas Series Dimension Data SpecificationsTechnical Data Table All Models General Technical Data Table All ModelsLimitations on Authority Representatives Warranty is Void ifROBERTS-GORDON will PAY for ROBERTS-GORDON will not PAY forPage Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 19.42 Kb Manual 62 pages 5.65 Kb

175, 225, 300, 250, 400 specifications

Roberts Gorden is a recognized leader in the field of heating solutions, particularly renowned for the development of its innovative radiant heating systems. The lineup of models including the Roberts Gorden 250, 300, 400, 150, and 225 features a blend of advanced technology, exceptional efficiency, and versatile applications that cater to various industrial and commercial needs.

At the core of Roberts Gorden products is their radiant heating technology. Unlike conventional heating systems that warm the air, radiant heaters emit infrared radiation, which directly heats objects and people within a space. This method not only provides a comfortable environment but also reduces energy consumption and minimizes the loss of heat, making it an environmentally friendly choice.

The Roberts Gorden 250 model is specifically designed for smaller spaces, offering compact efficiency without sacrificing power. It features an adjustable output, allowing for tailored heating based on specific requirements. The advanced burner technology ensures optimum combustion efficiency, translating to cost savings on fuel consumption.

Moving on to the Roberts Gorden 300, this unit is well-suited for medium-sized facilities. With enhanced capabilities, the 300 model offers improved heating distribution, making it ideal for warehouses and production floors. The ease of installation and maintenance further enhances its appeal, allowing businesses to focus on their operations rather than on complicated heating systems.

The Roberts Gorden 400 is a powerhouse in the lineup, engineered for larger spaces that demand high-performance heating. Its robust construction and powerful output provide effective warmth even in challenging environments. The unit is equipped with sophisticated controls that promote energy efficiency while maintaining optimum comfort levels.

In the mid-range spectrum, the Roberts Gorden 150 and 225 models cater to businesses needing versatile heating solutions. Both models are designed with user-friendly interfaces and include safety features that comply with industry standards. Their lightweight design allows for easy installation and mobility, making them suitable for temporary or permanent heating applications.

Overall, Roberts Gorden's commitment to innovation and efficiency is evident across its product range. With a focus on sustainability and advanced heating technologies, the Roberts Gorden 250, 300, 400, 150, and 225 models provide reliable heating solutions that meet the diverse preferences of industrial and commercial users. These products are not just about warmth; they are about creating a comfortable and productive environment while minimizing energy costs and environmental impact.