Page 32

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

Burner Observation

Make sure it is clean and free of cracks or holes.

Window

Clean and replace as required.

 

 

 

Combustion Fan Scroll,

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Wheel and Motor

 

 

 

Inshot Burners and

Clear of obstructions (even spider webs will cause problems).

Orifices

Carefully remove any dust and debris from the burner.

 

 

 

Direct-Spark Igniter

Replace if there are cracked ceramics, excessive carbon residue, or erosion

 

of the electrode.

 

The electrode gap should be 1/8" (3.2 mm).

 

 

Thermostat

There should be no exposed wire or damage to the device or wiring.

 

See Page 19, Section 10.

 

 

Suspension Points

Make sure the heater is hanging securely.

 

Look for signs of wear on the suspension materials or ceiling.

 

See Page 6, Figure 2.

 

 

Silicone Tubing

Ensure tight, secure fit on all pressure fittings at pressure switch,

 

burner partition, and blower outlet.

 

 

Gas Valve

Verify that cap covering pressure regulator adjustment screw is secure and

 

has not been tampered with.

 

Verify all wiring connections.

 

 

Condensate Drain

Flush drain and clear any obstructions.

(when installed)

 

 

 

26

Image 32
Contents Combat Page Roberts-Gordon, LLC Page Table of Figures Page Heater Safety Manpower RequirementsInstaller Responsibility Wall TagCorrosive Chemicals National Standards and Applicable CodesMinimum Required Installation Clearances Separated Combustion InstallationCritical Considerations 3.1 Basic Information Clearances to CombustiblesInstallation Clearances and Clearances to Combustibles National Standards and Applicable Codes Major Components 5.1 General SuspensionVent Installation Venting 6.1 VentingUnited States Requirements Canadian RequirementsSeparated Combustion Heaters Models Uhas 150 Unvented OperationHorizontal Venting Vertical VentingVent Material Vent and Roof DetailStandard Vented Heater Common Vertical Vent Termination Concentric Vent Box Horizontal Unvented Installation AIR SupplyBuilding Ventilation Outside Combustion Air SupplyGAS Piping ConnectionsWiring Positioning ThermostatsFan Control Low Voltage Thermostat with One HeaterUhas Series Internal Wiring Diagram TransformerUhas Series Ladder Wiring Diagram Electrical Connection to the Heater Operation and Maintenance LouversElectrical Checks Mechanical ChecksAutomatic Burner Control Sequence Pressure Switch Check Gas RateTurning Off the Heater Complete the Start-UpSimple Troubleshooting Simple Troubleshooting Burner FaultsHeater Operation To Turn the Heater OffUser Instructions Burner Maintenance 12.3 Fan/Motor Assembly MaintenanceHeat Exchanger Maintenance Gas Valve MaintenanceMaintenance Checklist Installation Code and Annual Inspections AllVicinity of the Heater Vehicles and OtherWhen installed Burner ObservationWindow Combustion Fan ScrollTroubleshooting 13.1 General Troubleshooting For Automatic Ignition Burner Systems Result in death or electrical shockTroubleshooting for Flame Supervision System StartConduct start-up procedure as shown on Page 19, Section Troubleshooting for Gas ValvesTroubleshooting for Combustion Fan Replacement Parts Burner ComponentsBurner Compartment Burner InjectorsIgnition Electrode and Flame Probe Description Part Number QtyCombustion Fan Vertical Installation Uhas Axial Fan/Guard/Motor Assembly Limit Switches Removal and ReplacementFan Removal and Replacement To Replace the Fan AssemblySpecifications Standard Models 150 400 Uhas Series Dimension DataGeneral Technical Data Table All Models Technical Data Table All ModelsWarranty is Void if ROBERTS-GORDON will PAY forROBERTS-GORDON will not PAY for Limitations on Authority RepresentativesPage Page Some objects can catch fire or explode when placed
Related manuals
Manual 52 pages 19.42 Kb Manual 62 pages 5.65 Kb

175, 225, 300, 250, 400 specifications

Roberts Gorden is a recognized leader in the field of heating solutions, particularly renowned for the development of its innovative radiant heating systems. The lineup of models including the Roberts Gorden 250, 300, 400, 150, and 225 features a blend of advanced technology, exceptional efficiency, and versatile applications that cater to various industrial and commercial needs.

At the core of Roberts Gorden products is their radiant heating technology. Unlike conventional heating systems that warm the air, radiant heaters emit infrared radiation, which directly heats objects and people within a space. This method not only provides a comfortable environment but also reduces energy consumption and minimizes the loss of heat, making it an environmentally friendly choice.

The Roberts Gorden 250 model is specifically designed for smaller spaces, offering compact efficiency without sacrificing power. It features an adjustable output, allowing for tailored heating based on specific requirements. The advanced burner technology ensures optimum combustion efficiency, translating to cost savings on fuel consumption.

Moving on to the Roberts Gorden 300, this unit is well-suited for medium-sized facilities. With enhanced capabilities, the 300 model offers improved heating distribution, making it ideal for warehouses and production floors. The ease of installation and maintenance further enhances its appeal, allowing businesses to focus on their operations rather than on complicated heating systems.

The Roberts Gorden 400 is a powerhouse in the lineup, engineered for larger spaces that demand high-performance heating. Its robust construction and powerful output provide effective warmth even in challenging environments. The unit is equipped with sophisticated controls that promote energy efficiency while maintaining optimum comfort levels.

In the mid-range spectrum, the Roberts Gorden 150 and 225 models cater to businesses needing versatile heating solutions. Both models are designed with user-friendly interfaces and include safety features that comply with industry standards. Their lightweight design allows for easy installation and mobility, making them suitable for temporary or permanent heating applications.

Overall, Roberts Gorden's commitment to innovation and efficiency is evident across its product range. With a focus on sustainability and advanced heating technologies, the Roberts Gorden 250, 300, 400, 150, and 225 models provide reliable heating solutions that meet the diverse preferences of industrial and commercial users. These products are not just about warmth; they are about creating a comfortable and productive environment while minimizing energy costs and environmental impact.