York H*RD036 THRU 060, H*RD018 THRU 060 warranty Sens, PH 13 Seer AC with AV / SV Variable Speed

Page 10

254892-YTG-C-0606

COOLING CAPACITY - With Air Handler Coils (Continued)

UNIT

 

AIR HANDLER

 

COIL MODEL1

 

 

COOLING

 

 

 

 

ELECTRIC

 

RATED

NET MBH

 

 

MODEL

MODEL

 

W

SEER

EER

 

HEAT KW2

 

CFM

 

 

 

 

 

TOTAL

 

SENS.

 

 

 

 

 

 

 

 

 

 

 

1 PH 13 SEER AC WITH AV / SV - VARIABLE SPEED

 

 

 

 

 

H2RD018S06

AV24

 

2,5,8,10,15

17

600

18.0

 

11.7

14.00

11.50

H2RD024S06

AV24

 

2,5,8,10,15

17

800

23.2

 

16.5

14.00

11.50

H2RD030S06

AV36

 

5,8,10,15,18

21

1000

30.0

 

21.2

14.00

11.50

H2RD036S06

AV36

 

5,8,10,15,18

21

1200

35.2

 

25.0

14.00

11.50

AV/SV48

 

5,8,10,15,18,20,25

24

1200

35.8

 

25.0

13.75

11.00

 

 

 

H2RD042S06

AV/SV48

 

5,8,10,15,18,20,25

24

1400

40.5

 

29.1

14.00

11.50

H2RD048S06

AV/SV48

 

5,8,10,15,18,20,25

24

1600

47.0

 

34.7

13.50

11.00

H2RD060S06

AV/SV60

 

5,8,10,15,18,20,25

24

1800

55.0

 

39.1

13.15

11.00

 

 

 

1 & 3 PH 13

SEER AC WITH AHP / F*FP / F*FV

 

 

 

 

 

H2RD018S06

AHP18

 

2,5,8

17

650

17.7

 

12.3

13.00

11.00

AHP24

 

2,5,8,10

17

655

17.9

 

12.5

13.50

11.00

 

F*FP024

 

5,8,10

17

650

17.5

 

12.2

13.00

11.00

 

AHP24

 

2,5,8,10

17

830

23.0

 

16.8

13.00

11.00

H2RD024S06

AHP30

 

5,8,10

17

795

23.6

 

17.0

13.00

11.00

F*FP024

 

5,8,10

17

800

23.0

 

16.8

13.00

11.00

 

 

 

 

F*FP030

 

5,8,10,15

17

800

23.0

 

16.8

13.00

11.00

H2RD030S06

AHP30

 

5,8,10

17

1015

30.0

 

21.9

13.00

11.00

AHP36

 

5,8,10,15,18

17

1040

30.0

 

22.6

13.50

11.00

 

F*FP036

 

5,8,10,15,19

21

1000

29.6

 

21.3

13.00

11.00

H1RD030S(25,46)

AHP30

 

5,8,10

17

1015

29.7

 

21.7

13.00

11.00

AHP36

 

5,8,10,15,18

17

1040

29.7

 

22.4

13.50

11.00

 

F4FP036

 

5,8,10,15,19

21

1000

29.3

 

21.1

13.00

11.00

 

AHP36

 

5,8,10,15,18

17

1235

35.0

 

27.2

13.50

11.00

H2RD036S06

AHP42

 

5,8,10,15,18

21

1255

35.0

 

27.5

13.50

11.00

AHP/SHP60

 

5,8,10,15,20,25

24

1200

36.0

 

26.7

14.00

11.50

 

 

 

 

F*FP040

 

5,8,10,15

21

1200

34.8

 

25.4

13.00

11.00

 

AHP36

 

5,8,10,15,18

17

1235

34.7

 

27.0

13.50

11.00

H1RD036S(25,46)

AHP42

 

5,8,10,15,18

21

1255

34.7

 

27.3

13.50

11.00

AHP/SHP60

 

5,8,10,15,20,25

24

1200

35.7

 

26.5

14.00

11.50

 

 

 

 

F*FP040

 

5,8,10,15

24

1200

34.5

 

25.2

13.00

11.00

 

AHP42

 

5,8,10,15,18

21

1485

41.0

 

31.0

13.00

11.00

H2RD042S06

AHP/SHP48

 

5,8,10,15,20

24

1400

42.0

 

30.7

13.50

11.00

AHP/SHP60

 

5,8,10,15,20,25

24

1400

40.5

 

33.2

14.00

11.50

 

 

 

 

F*FP048

 

5,8,10,15

24

1400

41.0

 

31.0

13.00

11.00

 

AHP42

 

5,8,10,15,18

21

1485

40.0

 

30.3

13.00

11.00

H1RD042S(25,46)

AHP/SHP48

 

5,8,10,15,20

24

1400

41.0

 

30.0

13.50

11.00

AHP/SHP60

 

5,8,10,15,20,25

24

1400

39.5

 

32.5

14.00

11.50

 

 

 

 

F4FP048

 

5,8,10,15

24

1400

40.0

 

30.3

13.00

11.00

H2RD048S06

F*FV060

 

5,8,10,15,20,25

24

1600

47.5

 

36.9

13.50

11.00

AHP/SHP48

 

5,8,10,15,20

24

1675

47.0

 

36.8

13.00

11.00

 

AHP/SHP60

 

5,8,10,15,20,25

24

1600

47.0

 

36.2

13.75

11.00

H1RD048S(25,46)

AHP/SHP48

 

5,8,10,15,20

24

1675

46.0

 

36.1

13.00

11.00

AHP/SHP60

 

5,8,10,15,20,25

24

1600

46.0

 

35.5

13.75

11.00

 

 

 

H2RD060S06

F*FV060

 

5,8,10,15,20,25

24

1850

55.0

 

40.3

13.20

11.00

AHP/SHP60

 

5,8,10,15,20,25

24

1850

55.0

 

40.3

13.00

11.00

 

 

 

H1RD060S(25,46)

AHP/SHP60

 

5,8,10,15,20,25

24

1850

54.0

 

39.6

13.00

11.00

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210. Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions. SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

1.G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.

2.Single phase units require single phase 2HK heaters.

= Not applicable.

10

Unitary Products Group

Image 10
Contents Features WarrantyDescription Model Physical and Electrical Data 1 PhaseDimensions UnitIndoor Coil1,2 TXV KIT3 Additional Charge, Oz HC36B3X HC42C3X HC60C3X HD24A3X HC18A3XHC30A3X HD36B3X HD48C3X HD60D3X AHP18B3X AHP24B3XProcedures FootnotesPhysical and Electrical Data 3 Phase H1RDIndoor Coil1 Additional Charge, Oz Footnotes PH 13 Seer AC with MV Variable Speed PH 13 Seer AC with AV / SV Variable Speed SensSeer AC with AHP / F*FP / F*FV Cooling Unit Model CFM Range Rated NET MBH SEER1 FurnaceTotal Sens FC/MC/PC/UC48 FC/MC/PC/UC42FC/MC/PC/UC60 FC/MC/PC24A FC/MC/PC18AFC/MC/PC18B FC/MC/PC24BFC/MC/PC48C FC/MC/PC42BFC/MC/PC42C FC/MC/PC48DFC/PC60C Sens PH 13 Seer AC with Variable Speed FURNACES2FC/MC/PC60D Sound Power Ratings AccessoriesTypical Installation AIR Conditioner Model no TemperatureCooling Performance Data Indoor Coil Model no FC/MC/PC/UC18 CondensingH2RD024S06 Indoor Coil Model no FC/MC/PC/UC24 CondensingMA12B MC30B MC36B H2RD030S06 , H1RD030S25,46Indoor Coil Model no FC/MC/PC/UC30 Condensing AHP30 AHP36Indoor Coil Model no FC/MC/PC/UC36 Condensing H2RD036S06 , H1RD036S25,46AHP36 AHP42 AHP/SHP60 MA12C MC42C MA14D MC42D MC48C MC48D H2RD042S06 , H1RD042S25,46Indoor Coil Model no FC/MC/PC/UC42 Condensing MA12CIndoor Coil Model no FC/MC/PC/UC48 Condensing H2RD048S06, H1RD048S25,46MA12C MC48C MA20D MC48D MA20D MC60D MC61D H2RD060S06, H1RD060S25,46Indoor Coil Model no FC/MC/PC/UC60 Condensing MA20D MC60DUnitary 5005 Norman Products York Group Drive 73069