Additional
Outdoor Unit | H1RD030S(25,46) | H1RD036S(25,46) |
| H1RD042S(25,46) |
| H1RD048S(25,46) | H1RD060S(25,46) |
Required TXV | 1TVM2A1 | 1TVM2A1 |
| 1TVM2C1 |
| 1TVM2C1 | 1TVM2C1 |
Factory | 5 - 13 | 6 - 0 |
| 8 - 13 |
| 8 - 6 | 10 - 2 |
|
|
|
|
|
|
|
|
Indoor Coil1 |
|
| Additional Charge, Oz |
|
| ||
G4FA036S14T2A | 0 | – |
| – |
| – | – |
G4FA048S17T2A | – | 0 |
| – |
| – | – |
G4FA048S17T2C | – | – |
| 0 |
| – | – |
G4FA048S21T2A | – | 0 |
| – |
| – | – |
G4FA048S21T2C | – | – |
| 0 |
| – | – |
G4FA060S21T2C | – | – |
| – |
| – | 0 |
G4FA060S24T2C | – | – |
| – |
| – | 0 |
G4FD036H17T2A | 0 | 0 |
| – |
| – | – |
G4FD036H21T2A | – | 0 |
| – |
| – | – |
G4FD042H21T2A | – | 0 |
| – |
| – | – |
G4FD042H21T2C | – | – |
| 0 |
| – | – |
G4FD046H17T2A | – | 0 |
| – |
| – | – |
G4FD046H17T2C | – | – |
| 0 |
| – | – |
G4FD048H21T2C | – | – |
| 0 |
| 0 | – |
G4FD048H24T2C | – | – |
| 0 |
| 0 | – |
G4FD060H24T2C | – | – |
| – |
| – | 0 |
G4FD061H24T2C | – | – |
| – |
| – | 0 |
F4FP040H06T2A | 0 | – |
| – |
| – | – |
F4FP042H06T2A | – | 0 |
| – |
| – | – |
F2FP048H06T2C | – | – |
| 0 |
| – | – |
FOOTNOTES: |
|
|
|
|
|
|
|
1.Systems matched with furnace or air handlers not equipped with
PROCEDURES:
1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of inter- connecting
line tubing.
2.Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.
3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.
8 | Unitary Products Group |