York H*RD018 THRU 060, H*RD036 THRU 060 warranty Footnotes, Procedures

Page 5

254892-YTG-C-0606

Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 Phase (Continued)

Outdoor Unit

H2RD018S06

H2RD024S06

H2RD030S06

H2RD036S06

H2RD042S06

H2RD048S06

H2RD060S06

Required TXV

1TVM2A1

1TVM2(A,B)1

1TVM2A1

1TVM2A1

1TVM2C1

1TVM2C1

1TVM2C1

Factory R-22 Charge, lbs-oz

4 - 9

6 - 3

5 - 13

6 - 0

8 - 13

8 - 6

10 - 2

 

 

 

 

 

 

 

 

Indoor Coil1,2

 

 

TXV KIT3 - Additional Charge, Oz

 

 

F2RP/F2FP040

0

F2FP048

0

F2FP060

0*

F2FV060

0

0

G4FA030S14T2A

0

G4FA030S14T2B

1

G4FA036S14T2A

0

0

0

G4FA036S17T2A

0

G4FA036S21T2A

0

G4FA036S21T2B

1

G4FA048S17T2A

0

G4FA048S17T2C

 

0

G4FA048S21T2A

0

G4FA048S21T2C

0

G4FA060S21T2C

0

G4FA060S24T2C

0

G4FD024H14T2A

0

G4FD024H14T2B

1

G4FD024H17T2A

0

G4FD024H17T2B

 

1

G4FD030H17T2A

0

G4FD035H14T2A

0

G4FD036H17T2A

0

0

0

G4FD036H21T2A

0

G4FD042H21T2A

0

G4FD042H21T2C

0

G4FD046H17T2A

0

G4FD046H17T2C

0

G4FD048H21T2A

G4FD048H21T2C

0

0

G4FD048H24T2A

G4FD048H24T2C

0

0

G4FD060H24T2C

0

G4FD061H24T2C

0

F4FP024H06T2A

0

F4FP024H06T2B

1

F4FP030H06T2A

0

F4FP036H06T2A

F4FP040H06T2A

0

F4FP042H06T2A

0

F2FP048H06T2C

0

F2FP060H06T2C

0*

F2FV060H06T2C

0

0

FOOTNOTES:

 

 

 

 

 

 

 

1.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

2.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

3.A TXV kit must be used with these coils to obtain system performance (2A, 2B, and 2C indicate 1TVM series).

*This loose coil match does not achieve 13 SEER.

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and for 15 feet of inter- connecting

line tubing.

2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.

4. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.

Unitary Products Group

5

Image 5
Contents Description WarrantyFeatures Dimensions Physical and Electrical Data 1 PhaseModel UnitIndoor Coil1,2 TXV KIT3 Additional Charge, Oz HC30A3X HC18A3XHC36B3X HC42C3X HC60C3X HD24A3X HD36B3X HD48C3X HD60D3X AHP18B3X AHP24B3XFootnotes ProceduresH1RD Physical and Electrical Data 3 PhaseIndoor Coil1 Additional Charge, Oz Footnotes PH 13 Seer AC with MV Variable Speed Seer AC with AHP / F*FP / F*FV SensPH 13 Seer AC with AV / SV Variable Speed Total Sens FurnaceCooling Unit Model CFM Range Rated NET MBH SEER1 FC/MC/PC/UC60 FC/MC/PC/UC42FC/MC/PC/UC48 FC/MC/PC18B FC/MC/PC18AFC/MC/PC24A FC/MC/PC24BFC/MC/PC42C FC/MC/PC42BFC/MC/PC48C FC/MC/PC48DFC/MC/PC60D Sens PH 13 Seer AC with Variable Speed FURNACES2FC/PC60C Typical Installation AccessoriesSound Power Ratings Cooling Performance Data TemperatureAIR Conditioner Model no Indoor Coil Model no FC/MC/PC/UC18 CondensingIndoor Coil Model no FC/MC/PC/UC24 Condensing H2RD024S06Indoor Coil Model no FC/MC/PC/UC30 Condensing H2RD030S06 , H1RD030S25,46MA12B MC30B MC36B AHP30 AHP36AHP36 AHP42 AHP/SHP60 H2RD036S06 , H1RD036S25,46Indoor Coil Model no FC/MC/PC/UC36 Condensing Indoor Coil Model no FC/MC/PC/UC42 Condensing H2RD042S06 , H1RD042S25,46MA12C MC42C MA14D MC42D MC48C MC48D MA12CMA12C MC48C MA20D MC48D H2RD048S06, H1RD048S25,46Indoor Coil Model no FC/MC/PC/UC48 Condensing Indoor Coil Model no FC/MC/PC/UC60 Condensing H2RD060S06, H1RD060S25,46MA20D MC60D MC61D MA20D MC60DUnitary 5005 Norman Products York Group Drive 73069