York H*RC036S Physical and Electrical Data 1 Phase, Physical and Electrical Data 3 Phase, Model

Page 2

036-21137-004 Rev. C (0505)

Physical and Electrical Data - 1 Phase

MODEL

 

 

H2RC018S06

H2RC024S06

H2RC030S06

H2RC036S06

 

H2RC042S06

H2RC048S06

H4RC060S06

 

 

 

 

 

 

 

 

 

Unit Supply Voltage

 

 

 

 

208/230 – 1 – 60

 

 

 

Normal Voltage Range

 

 

 

 

187 to 252

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Circuit Ampacity1

10.1

14.1

16.5

 

19.7

 

26.2

28.5

37.5

Max. Overcurrent Device Amps 2

15

25

25

 

30

 

45

50

60

Compressor Type3

 

Recip

Inertia

Recip

 

Recip

 

ScrollB

Recip

ScrollB

Compressor Amps

Rated Load

7.7

10.9

12.8

 

14.7

 

19.9

21.8

28.8

Locked Rotor

48

60

68

 

82

 

115

105

145

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No

No

No

 

Yes

 

No

No

No

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

0.5

0.5

0.5

 

1.3

 

1.3

1.3

1.5

 

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

18

18

22

 

22

 

22

22

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/12

1/12

1/15

 

1/4

 

1/4

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

 

 

 

 

 

Nominal RPM

1,100

1,100

850

 

850

 

850

850

850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal CFM

2,000

2,000

2,300

 

3,300

 

3,300

3,300

3,450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

12.58

12.58

15.72

 

15.72

 

17.03

19.65

23.58

Coil

 

 

 

 

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

 

1

 

1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

18

18

18

 

18

 

18

18

22

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Line OD

 

3/8

3/8

3/8

 

3/8

 

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

 

Vapor Line OD

 

3/4

3/4

3/4

 

3/4

 

7/8

7/8

1-1/8

 

 

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 4

4 - 9

4 - 7

5 - 8

 

5 - 3

 

6 - 13

7 - 7

8 - 15

Charge Per Foot, Oz.

0.68

0.68

0.68

 

0.68

 

0.70

0.70

0.76

 

 

 

 

 

 

 

 

 

 

Operating Weight Lbs.

144

146

156

 

161

 

157

190

198

 

 

 

 

 

 

 

 

 

 

 

 

 

PHYSICAL AND ELECTRICAL DATA - 3 Phase

MODEL

 

 

H1RC036S25

H1RC048S25

H1RC060S25

 

H1RC036S46

H1RC048S46

H1RC060S46

Unit Supply Voltage

 

 

 

208/230 – 3 – 60

 

 

 

460 - 3 - 60

 

Normal Voltage Range 1

 

 

187 to 252

 

 

 

432 to 504

 

Minimum Circuit Ampacity

13.3

 

18.9

 

22.9

 

7.6

9.6

12.0

Max. Overcurrent Device Amps 2

20

 

30

 

40

 

15

15

20

Compressor Type

 

Inertia

 

Inertia

 

Scroll

 

Inertia

Inertia

Scroll

Compressor Amps

Rated Load

9.6

 

14.1

 

17.3

 

5.4

7.0

9.0

Locked Rotor

78.0

 

130.0

 

123.0

 

40.0

64.0

62.0

 

 

 

 

 

 

Crankcase Heater

 

No

 

No

 

No

 

No

No

No

Fan Motor Amps

Rated Load

1.3

 

1.3

 

1.3

 

0.8

0.8

0.8

Fan Diameter Inches

22

 

22

 

22

 

22

22

22

 

 

 

Rated HP

1/4

 

1/4

 

1/4

 

1/4

1/4

1/4

Fan Motor

 

Nominal RPM

850

 

850

 

850

 

850

850

850

 

 

 

Nominal CFM

3,300

 

3,300

 

3,400

 

3,300

3,300

3,400

 

 

Face Area Sq. Ft.

15.72

 

17.03

 

23.58

 

15.72

17.03

23.58

Coil

 

Rows Deep

1

 

1

 

1

 

1

1

1

 

 

Fin / Inches

18

 

18

 

18

 

18

18

18

Liquid Line OD

 

3/8

 

3/8

 

3/8

 

3/8

3/8

3/8

Vapor Line OD

 

3/4

 

7/8

 

1-1/8

 

3/4

7/8

1-1/8

Unit Charge (Lbs. - Oz.) 4

6 - 2

 

7 - 10

 

9 - 3

 

6 - 2

7 - 10

9 - 3

Charge Per Foot, Oz.

0.68

 

0.70

 

0.76

 

0.68

0.70

0.76

Operating Weight Lbs.

157

 

184

 

198

 

157

184

198

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker.

3.All scrolls listed with a superscript “B” are Bristol scrolls. All scrolls listed with a superscript “C” are Copeland scrolls.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub- tract the amount of refrigerant, using the difference in length multiplied by the per foot value.

2

Unitary Products Group

Image 2
Contents Description WarrantyFeatures Model Physical and Electrical Data 1 PhasePhysical and Electrical Data 3 Phase ModelIndoor Coil5 G1NF048SOF ProceduresG1NF024SOF G1NF036SOF G1NF060SOFOutdoor Unit Unit Orifice s Factory R-22 Charge, lbs-ozSens Cooling Capacity With Air Handler CoilsWith TXV3 Seer AC with N1AH / G2FDFurnace Total Sens1200 33.6 23.4 1575 45.5 34.1 12.00 + TXV2 Cooling Capacity With Variable Speed FurnacesTotal Sens TXV SPEED3DUC20V P1XDC20VAccessories Dimensions 1 PhaseDimensions 3 Phase Sound Power RatingsTypical Field Wiring 3 Phase Application Typical InstallationTypical Field Wiring 1 Phase Application G1FA024S14,17 Cooling Performance DataH2RC018S06 H2RC024S06 G1FA036S17,21H2RC030S06 N1VSC16 H2RC036S06G1FA048S21 P1DUC20VH1RC036S25,46 H2RC042S06 H2RC048S06 N1VSD20H1RC048S25,46 N1AHD20 H4RC060S06G1FA060S21,24 H1RC060S25,46 Matching Indoor Components Unitary 5005 Norman Products York Group Drive 73069

H*RC018 THRU 060, H*RC036S specifications

The York H*RC036S and H*RC018 through H*RC060 are high-performance, energy-efficient rooftop units designed for commercial and industrial applications. These units are engineered to deliver exceptional heating and cooling performance while maintaining a low environmental impact. Both models leverage advanced technologies to ensure optimal indoor climate control and enhanced user comfort.

One of the standout features of the York H*RC series is its cutting-edge inverter technology. This innovation allows the units to adjust their cooling and heating capacity based on real-time demand, enabling significant energy savings. By operating at varying speeds, these rooftop units minimize energy consumption during off-peak times, contributing to a reduced overall carbon footprint.

The H*RC series is equipped with advanced microprocessor controls, which streamline operational management and provide users with precise control over their HVAC systems. The intuitive interface allows for easy programming and monitoring of performance, ensuring that users can maintain an ideal indoor environment with minimal effort.

In terms of construction, the H*RC units boast a robust build, designed to withstand harsh weather conditions while ensuring long-term durability. The units are equipped with high-efficiency fans and heat exchangers that optimize airflow and thermal exchange, enhancing overall performance and reliability.

Noise reduction is another key characteristic of the York H*RC series. These rooftop units are designed with sound-dampening features that minimize operational noise, making them suitable for noise-sensitive environments such as hospitals, schools, and office buildings.

The H*RC series also incorporates advanced filtration systems to improve indoor air quality. These systems effectively remove pollutants and allergens from the air, contributing to a healthier and more comfortable living and working environment.

Additionally, the York H*RC036S and H*RC018 through H*RC060 models are compliant with the latest regulations and standards, ensuring that they deliver efficient performance while adhering to environmental guidelines.

With a wide range of capacities and configurations available, the York H*RC series is versatile and can be tailored to meet specific application needs. Overall, these rooftop units represent a perfect blend of technology, energy efficiency, and reliability, making them an excellent choice for commercial and industrial HVAC applications.