York ND600, ND360, ND480 manual 115F 125F

Page 14

628767-YTG-C-0910

YD600/ND600 Air Handler with M1CZ600A Evaporator Section (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

586.4

62.8

340.6

284.5

228.3

-

-

-

529.2

68.8

313.5

257.5

201.5

-

-

-

 

 

72

558.8

62.8

414.2

358.1

301.9

245.8

-

-

514.2

68.8

394.0

338.0

282.0

226.0

-

-

15000

 

67

531.1

62.7

487.8

431.7

375.5

319.4

263.2

-

499.2

68.9

474.4

418.4

362.5

306.5

250.5

-

 

 

62

505.9

62.3

505.9

475.0

418.8

362.7

306.5

250.4

468.9

68.7

468.9

441.8

385.8

329.8

273.8

217.9

 

 

57

525.3

63.4

525.3

471.3

415.2

359.0

302.9

246.7

486.2

70.9

486.2

432.4

376.4

320.4

264.4

208.5

 

 

77

608.8

62.6

402.0

318.1

251.3

-

-

-

554.3

68.3

387.9

293.8

225.3

-

-

-

 

 

72

580.2

62.5

465.9

399.1

332.3

265.5

-

-

538.4

68.3

451.6

383.1

314.7

246.2

-

-

17500

 

67

551.5

62.5

529.8

480.1

413.3

346.5

279.7

-

522.4

68.3

515.2

472.4

404.0

335.5

267.1

-

 

 

62

525.2

62.1

525.2

509.8

461.0

394.2

327.4

260.6

490.9

68.2

490.9

477.3

430.7

363.5

293.8

225.4

 

 

57

545.4

63.2

545.4

518.4

457.0

390.2

323.4

256.6

509.0

70.4

509.0

482.1

420.5

353.3

283.6

215.1

 

 

77

631.3

62.4

463.4

351.8

274.3

-

-

-

579.4

67.8

462.4

330.1

249.2

-

-

-

 

 

72

601.5

62.3

517.6

440.2

362.7

285.3

-

-

562.6

67.8

509.2

428.3

347.3

266.4

-

-

20000

 

67

571.8

62.3

571.8

528.6

451.2

373.7

296.3

-

545.7

67.8

545.7

526.4

445.5

364.6

283.7

-

 

 

62

544.6

61.9

544.6

544.6

503.2

425.8

348.3

270.9

512.8

67.7

512.8

512.8

475.7

397.1

313.8

232.9

 

 

57

565.5

63.0

565.5

565.5

498.8

421.4

343.9

266.5

531.8

69.9

531.8

531.8

464.6

386.2

302.7

221.8

 

 

72

606.1

62.2

533.5

455.3

377.2

299.0

-

-

563.8

67.7

520.2

440.2

360.1

280.0

-

-

21750

 

67

576.2

62.1

576.2

547.3

469.1

390.9

312.8

-

547.0

67.7

547.0

542.0

462.0

381.9

301.8

-

 

62

548.7

61.7

548.7

548.7

523.2

445.1

366.9

288.8

514.0

67.6

514.0

514.0

493.1

414.2

332.9

252.9

 

 

 

 

57

569.8

62.8

569.8

569.8

518.7

440.5

362.3

284.2

532.9

69.8

532.9

532.9

481.5

402.7

321.4

241.3

 

 

72

610.7

62.0

549.4

470.5

391.6

312.7

-

-

565.0

67.6

531.3

452.0

372.8

293.6

-

-

23500

 

67

580.5

61.9

580.5

565.9

487.1

408.2

329.3

-

548.3

67.6

548.3

548.3

478.4

399.2

320.0

-

 

62

552.9

61.5

552.9

552.9

543.3

464.4

385.5

306.6

515.1

67.5

515.1

515.1

510.5

431.2

352.0

272.8

 

 

 

 

57

574.2

62.6

574.2

574.2

538.5

459.6

380.8

301.9

534.1

69.7

534.1

534.1

498.4

419.2

340.0

260.8

1These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 ÷ nameplate rated motor efficiency.

2These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.

14

Johnson Controls Unitary Products

Image 14
Contents 410A DescriptionND360, 480 30 50 Ton HertzTable of Contents Installation Options NomenclatureBenefits Air Handling Unit Features and BenefitsFeatures Guide Specifications Each Unit Shall Include The Following Accessories Installer ShallUnit Operating Characteristics Electrical RequirementsPhysical Data ND360, 480 & 600 Physical DataAir Handling Unit Limitations Unit LimitationsCooling and Heating Ratings Cooling RatingsCapacity Performance Condenser and Air Handling Cooling Capacities YD360/ND360Capacity1 Input YD480/ND480 YD480/ND480 YD600/ND600 Air Handler with M1CZ600A Evaporator Section 75F 85F115F 125F Hot Water Coil Capacity Correction And Pressure Drop Vs GPM1 ND360 1NF0454 Steam Pressure Psig Capacity Correction FactorND600 Fan Performance Data 50 Ton Fan PerformanceND480 Fan Performance Data 40 Ton CFM RPMND360, 480 & 600 Motor Overload Elements1 ND360, 480 & 600 Drive Kit DataND360, 480 & 600 Motor Kit Data Motor HP Voltage Model NumberSound Performance Indoor Sound Power LevelsStatic Resistance Static ResistanceMIN MAX Unit Voltage Fuse FLA Circuit Model Electrical DataElectrical Data SizeAir Handling Units Typical Wiring DiagramsTypical ND360, 480 & 600 Wiring Diagram Vertical Airflow Weights And DimensionsCorner Weights & Center of Gravity ND360, 480 & 600 Unit CG YUnit Dimensions ND360 TOPHorizontal Configuration Unit Dimensions ND480 88.8 Unit Dimensions ND600 Unit Dimensions M1CZ600 Evaporator Section Horizontal Configuration Unit Dimensions ND600 Airhandler & M1CZ600 Evaporator CoilCoil Unit Dimensions Model Dimensions Hot Water CoilDimensions Hot Water Coil Unit Connection SizesDimensions Steam Coil Dimensions Steam Coil1Dimensions Base Sections1 Dimensions Base SectionND360, 480 ND480/ND360 Weight Distribution With Suspension ApplicationUnit Mounting ND360 & 480 Mounting DetailHanger Rods Suspension Channel ND600 Mounting Detail ND600 & M1CZ600 Details For Securing Suspension ChannelsND480 Unit Mounting DimensionsND360 ND600Typical Field Wiring Diagrams Typical Liquid Line Solenoid Wiring Johnson Controls Unitary Products York Drive Norman, OK