Guide Specifications

MILLENNIUM™

Split System Air-Cooled Air Handler Models: NC300 and ND360, 480 and 600

General

Units shall be manufactured by Johnson Controls, Unitary Products Group in an ISO 9001 certified facility. These factory-assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes and aluminum fins, expansion valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower motor, an adjustable belt drive, a blower motor contactor and a small holding charge of nitrogen. The units are shipped in the vertical position ready for field installation. The air handler units can be installed for horizontal operation by reversing the position of the solid bottom panel with the return air duct flange on the front of the unit. The products must be tested per ARI 340/360 and Underwriter Laboratories U.L. 1995 and carry both CSA and ARI certification.

Description

The NC/ND indoor units are completely piped and wired at the factory and are shipped ready for immediate installation. Only the interconnecting liquid and suction lines, control wiring, and the main power wiring are required to complete the installation. Every coil is dehydrated, evacuated, leak tested and pressure tested at 450 psig before being pressurized with a holding charge of nitrogen for shipment and/or storage.

To eliminate the costly cabinet deterioration problems usually associated with outdoor equipment, all sheet metal parts are constructed of commercial grade (G90) galvanized steel.

After fabrication, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The parts that will be exposed to the weather are then coated with a powder paint to assure a quality finish for many years. This coating system has passed the 1000-hour, salt spray test per ASTM Standard B117.

Unit Cabinet

Cabinet shall be constructed of 18 gauge, zinc coated steel, finished with a powder paint process capable of withstanding a minimum of 1000 salt spray hours according to ASTM B117. Cabinet screws shall comply with the ASTM B117 salt spray test for a minimum of 1000 hours. Panels shall be removable for easy access to all internal components during maintenance and service. A filter rack shall be included to accommodate 1" or 2" filters. Cabinet shall feature a separate access panel for the controls so that unit airflow need not be disturbed during servicing. The NC300, ND360- 480 units are shipped in the vertical position ready for field

installation. The blower module can be repositioned in the field for maximum flexibility. The ND600 product ships with a separate M1CZ600A evaporator coil and can be assembled in the vertical or horizontal position in the field.

Each unit shall have:

a. A steel angle frame to provide the rigid support required for shipping, rigging and years of dependable operation.

b. Exterior panels of 18 gauge steel, finished with baked enamel to provide a long-lasting quality appearance.

c. Removable panels to provide easy access to the internal components for maintenance and service.

d. A filter rack with 1" or 2" filters.

Indoor (Evaporator) Fan Assembly

Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Blower motors and drive kits are ordered separately. Power wiring for blower motor is field supplied.

Refrigerant Components

Coils:

a. Evaporator coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed.

b. Evaporator coil shall be of the direct expansion, draw through design.

Refrigerant Circuit and Refrigerant Safety Components:

a. Include factory-mounted distributors, adjustable thermal expansion valves and solenoid valves for both capacity reduction and refrigerant pump out on start- up.

b. Include factory installed auxiliary side connectors for the addition of field installed hot gas bypass.

c. Shall include filter/strainer to eliminate any foreign matter.

Controls

Unit controls shall include 208/230/460 or 575 volt transformer, blower motor contactor and relay, as well as a low voltage terminal block. Unit wiring shall be color-coded for easy service and trouble shooting.

Johnson Controls Unitary Products

5

Image 5
Contents ND360, 480 Description410A 30 50 Ton HertzTable of Contents Nomenclature Installation OptionsBenefits Air Handling Unit Features and BenefitsFeatures Guide Specifications Unit Operating Characteristics Installer ShallEach Unit Shall Include The Following Accessories Electrical RequirementsND360, 480 & 600 Physical Data Physical DataCooling and Heating Ratings Unit LimitationsAir Handling Unit Limitations Cooling RatingsCondenser and Air Handling Cooling Capacities YD360/ND360 Capacity PerformanceCapacity1 Input YD480/ND480 YD480/ND480 75F 85F YD600/ND600 Air Handler with M1CZ600A Evaporator Section115F 125F Hot Water Coil Capacity Correction And Pressure Drop Vs GPM1 Steam Pressure Psig Capacity Correction Factor ND360 1NF0454ND480 Fan Performance Data 40 Ton Fan PerformanceND600 Fan Performance Data 50 Ton CFM RPMND360, 480 & 600 Motor Kit Data ND360, 480 & 600 Drive Kit DataND360, 480 & 600 Motor Overload Elements1 Motor HP Voltage Model NumberStatic Resistance Indoor Sound Power LevelsSound Performance Static ResistanceElectrical Data Electrical DataMIN MAX Unit Voltage Fuse FLA Circuit Model SizeAir Handling Units Typical Wiring DiagramsTypical ND360, 480 & 600 Wiring Diagram Corner Weights & Center of Gravity ND360, 480 & 600 Unit Weights And DimensionsVertical Airflow CG YTOP Unit Dimensions ND360Horizontal Configuration Unit Dimensions ND480 88.8 Unit Dimensions ND600 Unit Dimensions M1CZ600 Evaporator Section Unit Dimensions ND600 Airhandler & M1CZ600 Evaporator Coil Horizontal ConfigurationDimensions Hot Water Coil Dimensions Hot Water CoilCoil Unit Dimensions Model Unit Connection SizesDimensions Base Sections1 Dimensions Steam Coil1Dimensions Steam Coil Dimensions Base SectionUnit Mounting ND480/ND360 Weight Distribution With Suspension ApplicationND360, 480 ND360 & 480 Mounting DetailHanger Rods Suspension Channel ND600 & M1CZ600 Details For Securing Suspension Channels ND600 Mounting DetailND360 Unit Mounting DimensionsND480 ND600Typical Field Wiring Diagrams Typical Liquid Line Solenoid Wiring Johnson Controls Unitary Products York Drive Norman, OK