ACCESSORIES

Refer to Price Manual for specific model numbers.

HARD START KIT - Required when using TXV indoor coil. Also, provides increased starting torque for areas with low voltage.

Model

Source 1 Kit numbers

12

S1-2SA06708606

18

S1-2SA06708606

24

S1-2SA06708706

30

S1-2SA06705906

36

S1-2SA06708106

42

S1-2SA06708106

48

S1-2SA06708806

OFF CYCLE TIMER DELAY - Provides a 5-minute off cycle to prevent rapid recycling of the compressor.

ROOM THERMOSTATS - A wide selection of compatible thermosets are available to provide optimum performance and features for any installation.

1H/1C, manual changeover electronic non-programmable thermostat.

1H/1C, auto/manual changeover, electronic programmable, deluxe 7-day, thermostat.

1H/1C, auto/manual changeover, electronic programmable.

*For the most current accessory information, refer to the price book or consult factory.

SOUND POWER RATINGS*

UNIT MODEL

(dBA)

12

72

18

75

24

76

30

75

36

76

42

75

48

76

60

78

* Rated in accordance with ARI 270-95 Standards.

TYPICAL INSTALLATION

 

MINIMUM 18” SERVICE

 

60” OVERHEAD

ACCESS CLEARANCE

THERMOSTAT

ON ONE SIDE

CLEARANCE

 

 

 

 

WEATHERPROOF

 

 

DISCONNECT

 

 

SWITCH

 

 

 

NEC CLASS 1 WIRING

6” CLEARANCE

 

TO FURNACE OR

AROUND PERIMETER

 

AIR HANDLER

 

 

TERMINAL BLOCK

 

 

NEC CLASS 2 WIRING

 

 

TO INDOOR COIL

NOTE:

 

 

ALL OUTDOOR WIRING

CONTROL

 

MUST BE WEATHERPROOF.

 

ACCESS

SEAL OPENING(S) WITH

 

 

PANEL

PERMAGUM OR EQUIVALENT

TYPICAL FIELD WIRING

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

POWER WIRING

208/230-1-6024 VOLT CONTROL WIRING MINIMUM 18 GA. WIRE

(NEC CLASS 2)

POWER WIRING CONTROL WIRING FACTORY WIRING

CONTACTOR

TERMINALS

GND.

LUGCOIL

CONDENSING UNIT

FURNACE OR AIR HANDLER TERMINAL BLOCK

C Y R G W

* TERMINAL W IS ONLY REQUIRED ON SYSTEMS WITH HEAT.

*

Y R G W

ROOM THERMOSTAT

ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.

10

Johnson Controls Unitary Products

Image 10
Contents Features WarrantyDescription Model TCGD12 TCGD18 TCGD24 TCGD30 TCGD36 TCGD42 TCGD48 TCGD60AV/SV48D2C FC/MC/PC/UC18A3X AHP18B2A AHP24B2A AHP30B2A AHP36C2AAHP42C2C AHP/SHP60D2C AV24B2A AV36C2A FC/MC/PC/UC18B3XProcedures FootnotesSeer AC with MV Variable Speed Unit Model AIR HandlerSeer AC with AV / SV / F*FV Variable Speed Cooling Rated NET MBH Model Condenser only DataUnit AIR Handler Seer EER CFM FC/MC/PC32 FC/MC/PC18 FC/MC/PC24 FC/MC/PC35Seer AC with Variable Speed FURNACES2 FC/MC/PC48C FC/MC/PC48DTypical Installation AccessoriesSound Power Ratings Typical Field WiringCooling Performance Data AHP18 AHP24 FC/MC/PC/UC24MA08B FC/MC18B FC/MC24B MV12B FC/MC/PC32 FC/MC/PC35 FC/MC/PC37 FC/MC/PC43 MA08B FC/MC35B FC/MC36B FC/MC43B MV12BMA12B FC/MC35B FC/MC43B MV12B MV16C FC/MC43C FC/MC35C FC/MC/PC32 FC/MC/PC37 FC/MC/PC43AHP30 AHP36 FC/MC/PC35AIndoor Coil Model no FC/MC/PC43 Condensing FC/MC/PC37A FC/MC/PC/UC48MA16C FC/MC43C MA14D FC/MC48D FC/MC48C MV16C MV20D AHP/SHP60 AV/SV48 Indoor Coil Model no FC/MC/PC48 CondensingMA16C FC/MC48C MA20D FC/MC48D MV16C MV20D MA20D FC/MC62D MV20D