York YCJF24 warranty Physical and Electrical Data, Model

Page 2

413437-YTG-C-0908

Physical and Electrical Data

MODEL

 

YCJF24S41S1

YCJF30S41S1

YCJF36S41S1

YCJF42S41S1

YCJF48S41S1

YCJF60S41S1

Unit Supply Voltage

 

 

208-230V,

1φ, 60Hz

 

 

Normal Voltage Range 1

 

 

187 to 252

 

 

Minimum Circuit Ampacity

16.8

18.4

19.1

23.9

27.9

35.9

Max. Overcurrent Device Amps 2

25

30

30

40

45

60

Min. Overcurrent Device Amps 3

20

20

20

25

30

40

Compressor Type

 

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Compressor

Rated Load

12.8

14.1

14.1

17.9

21.1

27.5

Amps

Locked Rotor

58

73

77

112

115

135

Crankcase Heater

 

No

No

No

No

No

No

Fan Motor Amps

Rated Load

.8

.8

1.5

1.5

1.5

1.5

Fan Diameter Inches

22

22

22

24

24

24

 

Rated HP

1/8

1/8

1/4

1/4

1/4

1/4

Fan Motor

Nominal RPM

1075

1075

850

850

850

850

 

Nominal CFM

2750

2800

3200

3600

3600

3700

 

Face Area Sq. Ft.

13.1

17.4

17.4

20.0

21.4

24.0

Coil

Rows Deep

1

1

1

1

1

1

 

Fin / Inches

23

23

23

23

23

23

Liquid Line Set OD

(Field Installed)

3/8

3/8

3/8

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

7/8

7/8

1 1/8

Unit Charge (Lbs. - Oz.) 4

3 - 2

3 - 7

3 - 10

4 - 4

4 - 9

5 - 9

Charge Per Foot, Oz.

0.62

0.62

0.62

0.67

0.67

0.75

Operating Weight Lbs.

128

130

145

172

180

199

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.The Unit Charge is correct for the outdoor unit, smallest matched evaporator coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

C

A

B

All dimensions are in inches. They are subject to change with- out notice. Certified dimensions will be provided upon request.

Unit

 

Dimensions

 

Refrigerant Connection

 

 

(Inches)

 

Service Valve Size

Model

 

 

 

 

 

 

 

A1

 

B

 

C

Liquid

Vapor

 

 

 

24

28

 

29

 

29

 

 

 

 

 

 

 

 

 

3/4”

30

36

 

29

 

29

 

36

36

 

29

 

29

3/8”

 

42

34

 

33.6

 

33.6

7/8”

 

 

 

48

36

 

33.6

 

33.6

 

 

 

 

 

60

40

 

33.6

 

33.6

 

7/8”2

1.Including Fan Guard.

2.Adapter fitting required for 1-1/8” line set.

2

Johnson Controls Unitary Products

Image 2
Contents Technical Guide Physical and Electrical Data ModelJohnson Controls Unitary Products Procedures FootnotesCooling Capacity With Air Handler Coils Seer AC with AHP / SHP / F*FP Seer ACSpeed Total Sens FurnaceCooling Unit Model CFM Range Rated NET MBH SEER1 Seer EER CFM Cooling Capacity YCJF24S41S1 With Variable Speed FurnacesVariable Speed Coil Cooling Furnace Model MODEL1 Rated Seer AC with Variable Speed FURNACES2Variable Speed Cooling Furnace Model MODEL1 RatedCooling Capacity YCJF30S41S1 With Variable Speed Furnaces 1050 29.8 21.8 15.50 13.25 Cooling Capacity YCJF36S41S1 With Variable Speed Furnaces UC60C FC/PC60C Cooling Capacity YCJF42S41S1 With Variable Speed Furnaces UC48C Cooling Capacity YCJF48S41S1 With Variable Speed Furnaces Cooling Capacity YCJF60S41S1 With Variable Speed Furnaces HC60DSound Power Ratings Condensing TemperatureAIR Conditioner Model no YCJF24S41S1 Indoor Coil Model no Entering AIRVariable Speed Coil Furnace AIR Conditioner Model no YCJF30S41S1 Indoor Coil Model no 9V*B12 HC36 9V*C16 HC42 9V*C20 9V*A12 HD36 AIR Conditioner Model no YCJF36S41S1 Indoor Coil Model no PV8*C16 HD48 PV8*C20 PC,V9*C16 PC,V9*C20 PC,V9*D20 AIR Conditioner Model no YCJF42S41S1 Indoor Coil Model no PV8*C16 HD48 PV8*C20 PC,V9*C16 PC,V9*C20 PC,V9*D20 HD60 AIR Conditioner Model no YCJF48S41S1 Indoor Coil Model no 9C*D20 HC60 LC*C16 HD48 LC*C20 9C*C16 9C*C20 HD60 9V*C16 AIR Conditioner Model no YCJF60S41S1 Indoor Coil Model no