York AIR Conditioner Model no YCJF24S41S1 Indoor Coil Model no, Condensing, Entering AIR

Page 20

413437-YTG-C-0908

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

YCJF24S41S1

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

FC/MC/PC32

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSING

IDCFM

 

 

600

 

 

 

 

800

 

 

 

 

1000

 

 

ENTERING AIR

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

 

T.C.

21.8

23.8

23.8

25.7

27.7

23.9

25.4

25.3

27.6

29.5

26.1

27.1

26.9

29.4

31.4

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

16.3

16.3

16.1

14.4

16.3

16.3

16.3

16.2

15.3

16.3

16.3

16.3

16.3

16.2

 

KW

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

 

T.C.

21.0

23.0

22.9

24.9

26.8

23.1

24.6

24.4

26.6

28.6

25.3

26.1

25.9

28.4

30.4

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

16.3

15.8

15.7

13.9

16.3

16.3

16.0

16.0

14.9

16.3

16.3

16.3

16.3

15.9

 

KW

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

 

T.C.

20.2

22.2

22.0

24.1

25.9

22.4

23.7

23.5

25.7

27.7

24.5

25.2

24.9

27.3

29.5

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

16.3

15.2

15.3

13.4

16.3

16.3

15.8

15.8

14.4

16.3

16.3

16.3

16.3

15.5

 

KW

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

 

T.C.

19.5

21.4

21.2

23.3

25.0

21.6

22.8

22.6

24.8

26.8

23.7

24.2

23.9

26.3

28.5

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

16.3

14.7

15.0

12.9

16.3

16.3

15.5

15.6

14.0

16.3

16.3

16.3

16.3

15.1

 

KW

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

 

T.C.

18.4

20.1

19.9

22.0

23.7

20.4

21.4

21.1

23.4

25.2

22.4

22.6

22.4

24.7

26.8

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

15.9

14.0

14.2

12.2

16.3

16.1

15.2

15.3

13.3

16.3

16.3

16.3

16.3

14.4

 

KW

2.2

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.2

 

T.C.

17.4

18.8

18.6

20.7

22.3

19.3

19.9

19.7

21.9

23.7

21.2

21.0

20.9

23.1

25.1

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

15.4

13.4

13.5

11.6

16.3

15.9

14.8

14.9

12.6

16.3

16.3

16.3

16.3

13.6

 

KW

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

 

T.C.

16.3

17.5

17.3

19.3

20.9

18.1

18.4

18.3

20.4

22.2

19.9

19.4

19.3

21.6

23.4

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

15.0

12.7

12.8

10.9

16.3

15.7

14.5

14.6

11.9

16.3

16.3

16.3

16.3

12.9

 

KW

2.9

2.9

2.9

2.9

2.8

2.9

2.9

2.9

2.8

2.8

2.8

2.8

2.9

2.8

2.8

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed tempera- ture and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Air Handler

Coil

T.C.

S.C.

KW

FC/MC/PC24

1.02

1.04

1.02

FC/MC/PC30

1.02

1.04

1.02

FC/MC/PC35

1.02

1.06

1.02

FC/MC/PC36

1.02

1.06

1.02

FC/MC/PC37

1.04

1.08

1.02

FC/MC/PC43

1.03

1.08

1.02

FC/MC/PC48

1.05

1.10

1.02

HC24

0.99

1.00

1.02

HC30

1.01

1.04

1.02

HC36

1.02

1.06

1.02

HC42

1.04

1.08

1.02

HD24

1.04

1.07

1.02

HD36

1.01

1.02

1.02

HD48

1.05

1.07

1.02

UC24

1.02

1.05

1.02

UC30

1.02

1.05

1.02

AHP24

1.01

1.04

1.01

Air Handler

Coil

T.C.

S.C.

KW

AV24

1.02

1.05

0.93

AV36

1.05

1.09

0.93

F4FP030

1.02

1.04

1.02

MA08B

FC/MC24B

1.02

1.04

1.02

MV12B

FC/MC24B

1.04

1.07

0.94

MA08B

FC/MC30B

1.02

1.04

1.02

MV12B

FC/MC30B

1.04

1.07

0.94

MA08B

FC/MC35B

1.02

1.06

1.02

MV12B

FC/MC35B

1.05

1.08

0.93

MV16C

FC/MC35C

1.05

1.08

0.93

MA08B

FC/MC36B

1.02

1.06

1.02

MV12B

FC/MC36B

1.05

1.08

0.93

MV16C

FC/MC36C

1.05

1.08

0.93

MA08B

FC/MC43B

1.03

1.08

1.02

MV12B

FC/MC43B

1.06

1.10

0.94

MV16C

FC/MC43C

1.06

1.10

0.93

MV16C

FC/MC48C

1.07

1.12

0.93

Continued on Page 21.

20

Johnson Controls Unitary Products

Image 20
Contents Technical Guide Physical and Electrical Data ModelJohnson Controls Unitary Products Procedures FootnotesCooling Capacity With Air Handler Coils Seer AC with AHP / SHP / F*FP Seer ACSpeed Total Sens FurnaceCooling Unit Model CFM Range Rated NET MBH SEER1 Cooling Capacity YCJF24S41S1 With Variable Speed Furnaces Variable Speed Coil Cooling Furnace Model MODEL1 RatedSeer EER CFM Seer AC with Variable Speed FURNACES2Variable Speed Cooling Furnace Model MODEL1 RatedCooling Capacity YCJF30S41S1 With Variable Speed Furnaces 1050 29.8 21.8 15.50 13.25 Cooling Capacity YCJF36S41S1 With Variable Speed Furnaces UC60C FC/PC60C Cooling Capacity YCJF42S41S1 With Variable Speed Furnaces UC48C Cooling Capacity YCJF48S41S1 With Variable Speed Furnaces Cooling Capacity YCJF60S41S1 With Variable Speed Furnaces HC60DSound Power Ratings Temperature AIR Conditioner Model no YCJF24S41S1 Indoor Coil Model noCondensing Entering AIRVariable Speed Coil Furnace AIR Conditioner Model no YCJF30S41S1 Indoor Coil Model no 9V*B12 HC36 9V*C16 HC42 9V*C20 9V*A12 HD36 AIR Conditioner Model no YCJF36S41S1 Indoor Coil Model no PV8*C16 HD48 PV8*C20 PC,V9*C16 PC,V9*C20 PC,V9*D20 AIR Conditioner Model no YCJF42S41S1 Indoor Coil Model no PV8*C16 HD48 PV8*C20 PC,V9*C16 PC,V9*C20 PC,V9*D20 HD60 AIR Conditioner Model no YCJF48S41S1 Indoor Coil Model no 9C*D20 HC60 LC*C16 HD48 LC*C20 9C*C16 9C*C20 HD60 9V*C16 AIR Conditioner Model no YCJF60S41S1 Indoor Coil Model no