Physical and Electrical Data
MODEL | 
  | 
  | 036H1081A | 048H1081A | 060H1081A | |
  | 
  | 
  | 
  | 
  | 
  | |
Unit Supply Voltage  | 
  | 
  | 
  | 380/415 - 3 - 50  | 
  | |
  | 
  | 
  | 
  | 
  | 
  | |
Normal Voltage Range 1  | 
  | 
  | 
  | 342 - 455  | 
  | |
Minimum Circuit Ampacity  | 12.4  | 14.8  | 16.8  | |||
  | 
  | 
  | 
  | |||
Max. Overcurrent Device Amps 2  | 15  | 20  | 25  | |||
Compressor Type 3  | 
  | 
  | Recip  | Recip  | Recip  | |
Compressor Amps  | 
  | Rated Load  | 6.1  | 8.0  | 9.6  | |
  | 
  | 
  | 
  | 
  | ||
  | Locked Rotor  | 39.0  | 53.0  | 79.0  | ||
  | 
  | 
  | ||||
  | 
  | 
  | 
  | 
  | 
  | |
Crankcase Heater  | 
  | 
  | No  | No  | No  | |
  | 
  | 
  | 
  | 
  | 
  | |
Fan Motor Amps  | 
  | Rated Load  | 1.8  | 1.8  | 1.8  | |
  | 
  | 
  | 
  | 
  | 
  | |
Fan Diameter Inches  | 
  | 
  | 18“  | 20”  | 20”  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Rated HP  | 1/3  | 1/3  | 1/3  | 
Fan Motor  | 
  | 
  | 
  | 
  | 
  | |
  | Nominal RPM  | 1,100  | 1,100  | 1,100  | ||
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Nominal CFM  | 2,300  | 3,000  | 3,000  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Face Area Sq. Ft.  | 9.25  | 11.24  | 11.24  | 
  | 
  | 
  | 
  | 
  | 
  | |
Condenser  | 
  | Rows Deep  | 1  | 2  | 2  | |
Coil Data  | 
  | Fin / Inches  | 18  | 15  | 15  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Tubing Diameter  | 3/8  | 3/8  | 3/8  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Face Area Sq. Ft.  | 3.61  | 4.67  | 4.67  | 
  | 
  | 
  | 
  | 
  | 
  | |
Evaporator  | 
  | Rows Deep  | 3  | 4  | 4  | |
Coil Data  | 
  | Fin / Inches  | 14  | 12  | 12  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Tubing Diameter  | 5/16  | 5/16  | 5/16  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Motor HP / RPM  | 3/4 / 1,000  | 3/4 / 1,050  | 3/4 / 1,100  | |
  | 
  | 
  | 
  | 
  | 
  | |
Blower Data  | 
  | Max. Static Pressure In. Water  | .80  | .80  | .80  | |
  | 
  | 
  | 
  | 
  | 
  | |
  | Dia. x Width (in.) / Rated CFM  | 10 x 7/1,200  | 10 x 7/1,500  | 10 x 7/1,600  | ||
  | 
  | |||||
  | 
  | 
  | 
  | 
  | 
  | |
  | 
  | Motor Full Load AMPS  | 3.0  | 3.0  | 3.0  | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Shipping Weight (lbs.)  | 
  | 
  | 
  | 270  | 354  | 360  | 
  | 
  | 
  | 
  | 
  | 
  | |
Unit Charge (Lbs. - Oz.)  | 
  | 
  | ||||
  | 
  | 
  | 
  | 
  | 
  | |
Minimum Wire Size 4  | 
  | 
  | #14   | #14   | #12   | |
75º C Copper @ 400 Volt  | 
  | 
  | #12   | #12   | #10   | |
  | 
  | 
  | 
  | 
  | 
  | 
  | 
1.Rated in accordance with ARI Standard 110, utilization range “A”.
2.Dual element fuses or HACR circuit breaker.
3.Rated under standard A.R.I. conditions of 80º DB/67º WB indoor, 95º outdoor.
4.Other temperature ratings of wire will have different rated ampacities. Refer to NEC for proper wire sizing recommendations. If using type NM or 
  | A  | B  | 
  | 
  | |
HEATER  | 
  | D  | 
ACCESSORY  | 
  | |
  | C  | |
  | 
  | |
CONTROL  | 
  | 
  | 
WIRING  | 
  | 
  | 
OPENINGS  | 
  | 
  | 
3/4” NPT FEMALE  | G  | 12” DIAMETER  | 
  | ||
DRAIN OPENING  | E  | RETURN  | 
  | 
  | F  | 
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
UNIT DIMENSIONS (INCHES)
UNIT  | A  | B  | C  | D  | E  | F  | G  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
036  | 44  | 30  | 26 5/8  | 24 1/8  | 7 3/4  | 22 1/2  | 12 5/8  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
048  | 46  | 32  | 28 5/8  | 26 1/8  | 7 3/4  | 22 1/8  | 12 5/8  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
060  | 46  | 32  | 28 5/8  | 26 1/8  | 7 3/4  | 22 1/8  | 12 5/8  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
2  | Unitary Products Group  |