York D1EE 060, D1EE 048, D2EE 036 Heat Anticipator Setpoints, Checking Supply AIR CFM, 1220

Page 13

035-12046-003-A-0204

HEAT ANTICIPATOR SETPOINTS

It is important that the anticipator setpoint be correct. Too high of a setting will result in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the correct setpoint will give shorter “ON” cycles and may result in the lowering of the temperature within the conditioned space. Refer to Table 10 for the required heat anticipator setting.

CHECKING SUPPLY AIR CFM

The speed of the supply air blower will depend on the required CFM, the unit accessories and the static resistances of both the supply and the return air duct systems. With this information,

TABLE 11 - BELT-DRIVE SUPPLY AIR MOTOR PULLEY ADJUSTMENT

TURNS

BLOWER DRIVE RANGE (RPM)

OPEN*

3 TON

4 TON

5 TON

5

780

790

850

4

842

856

924

3

904

922

998

2

966

988

1072

1

1028

1054

1246

0

1090

1120

1220

*Pulley can be adjusted in half-turn increments.

the speed for the supply air blower can be determined from the static resistance and blower performance data on Tables 3 thru 6.

Knowing the required blower RPM and the blower motor HP,

the spe d setting for the d rect-drive supply air motor can be

determin

d.

 

 

CAUTION

 

 

 

 

 

 

 

 

 

 

 

 

 

Procedure

radjustingblttension:

 

 

 

 

 

 

 

 

 

 

1Loosennu(D)fromthemotormount.

 

 

 

 

 

 

 

2Neverlosnnuts(C)fromeachotherwhilelooseningnut(D).

 

3Adjustthete

sionbyturningbolt(B).

 

 

 

 

 

 

 

nsioning

4Donotlosfo

thefournuts(topandbotom)(A);unlesadditional

ditanceisrequired;immediatelyre-tigh

ntheseboltifs

losened.

atthe

5Ueabelt.s

tensionchecker

 

applyaperpendicular

rcetoonebe

midpointofthespanasshwn.to

Thedeflctionforceshouldbeappite l

d

untilaspecificdeflectiondistanceof4mm(5/32")isbtained.fo

Todtetermine

thedeflectiondistanceomnormalposition,useastraightedgefrom

sheave

sheaveasaefefr

renceline.Therecommendeddeflectionforce

isasfollws:to

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GT

 

 

 

 

 

 

 

 

 

 

 

 

 

EN

 

 

 

 

 

 

 

 

 

 

 

 

AN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FO

 

 

 

 

 

 

 

 

 

 

 

 

 

FL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DE

 

 

 

 

 

 

 

 

 

 

Tnsionnewbeltsat

 

(A)

 

 

 

 

 

 

 

(C)*

(D)

(B)

 

 

 

max.deflction

 

rcerecom*NEVERenddforthebeltLOOSEN

sction.Checkthebelthtensionat

easttwtimesfo

duringthefirst24hoursof

opera

.Anyre-tenioningshouldfallbetweenthemin.andmax.

 

dflece tionforcevalue.s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.Afteradjusting,re-tightennut(D)againstthemotormounttakingcarenot toloosennuts(C).

FIG. 7 - BELT ADJUSTMENT

The setting (turns open) for the optional belt-drive supply air motor pulley can be determined from Table 11.

OPTIONAL BELT-DRIVE BLOWER

All units with belt-drive blowers have single-speed motors. The variable pitch pulley on the blower motor can be adjusted to

obtain the desired supply air CFM. Refer to Table 7 for blower motor and drive data. The tension on the belts should be adjusted as shown in Figure 7.

Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other than the equipment installer.

To check the supply air CFM after the initial balancing has been completed:

1.Remove the (two) ￿￿￿ " dot plugs from the holes located on the filter access panel side of the unit.

2.Insert at least 8" of 1/4 inch tubing into each of these holes for sufficient penetration into the air flow on both sides of the evaporator coil.

NOTE: The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pres- sure will not affect the static pressure readings.

3.Using an inclined manometer, determine the pressure drop across a dry indoor coil. Since the moisture on an indoor coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To assure a dry coil, the compressors should be de-energized while the test is being run.

4.Knowing the pressure drop across a dry coil, the actual CFM through the unit can be determined from the curve in Figure 8.

 

0.7

 

 

0.6

060

(IWG)

0.5

036

 

 

048

DROP

0.4

 

PRESSURE

0.3

 

 

 

 

0.2

 

 

0.1

 

0

750 1250 1750 2250 2750 3250 3750

NOMINAL CFM

FIG. 8 - PRESSURE DROP ACROSS A DRY EVAPORATOR COIL VS SUPPLY AIR CFM, WITHOUT AIR FILTERS

WARNING:Failure to properly adjust the total system air quan- tity can result in poor system performance.

NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST MEASUREMENTS TO ASSURE A DRY INDOOR COIL.

Unitary Products Group

13

Image 13
Contents Inspection GeneralReference ApprovalsTable of Contents Installation Power and Control Wiring Service AccessCondensate Drain ThermostatOptional Economizer Rain Hood CompressorsCooling / Heating Electronic Thermostat Typical Field WiringKnockout Utilities Entry DataHole Size Used for Unit Motor Electric HeatersSize Speed MBH CFM MEDSize CFM MBH RPM Unit AIR Flow1560 1077 25001630 1660Static Resistances Operation Heat Anticipator Setpoints BELT-DRIVE Supply AIR Motor Pulley AdjustmentChecking Supply AIR CFM Turns Blower Drive Range RPM Open TONNormal Maintenance Maintenance035-12046-003-A-0204 Unitary Products Group

D2EE 036, D1EE 060, D1EE 048 specifications

The York D1EE 048, D2EE 036, and D1EE 060 are advanced air conditioning units designed for superior performance and energy efficiency in commercial and industrial environments. These models are part of York’s reputation for creating reliable HVAC systems that cater to a variety of applications.

The York D1EE 048 is a high-efficiency rooftop unit, renowned for its compact design and robust construction. This model boasts an integrated economizer that enhances energy savings by optimizing the use of outside air for cooling. It features a cutting-edge variable speed compressor, which provides precision cooling and reduces energy consumption under varying load conditions. The advanced microprocessor control system enables quick adjustments to system performance, further enhancing comfort and efficiency.

In contrast, the York D2EE 036 is another exemplary model, distinguished by its dual-stage heating and cooling capabilities. This unit is particularly advantageous for facilities requiring consistent temperature control throughout different seasons. With a SEER rating that meets or exceeds regulatory requirements, the D2EE 036 helps operators minimize downtime and achieve lower operational costs. Its innovative design includes a streamlined airflow system, enabling quiet operation without compromising cooling performance.

Finally, the York D1EE 060 rounds out this trio with its innovative features tailored for large-building applications. This unit is equipped with advanced inverter technology, which allows for seamless adjustments in cooling capacity based on real-time demand. The unit is designed with high-performance heat exchangers that optimize thermal transfer efficiency, ensuring rapid cooling response while maintaining low energy usage. Its smart connectivity features allow for remote monitoring and adjustments, offering facility managers enhanced control over the indoor climate.

In terms of characteristics, all three models prioritize energy efficiency, user-friendly controls, and environmentally responsible refrigerants. They comply with the latest energy standards, making them suitable for organizations aiming for sustainability. With their robust construction and user-centric features, York’s D1EE 048, D2EE 036, and D1EE 060 units represent a commitment to delivering efficient, reliable, and cutting-edge climate control solutions. Whether for small offices or large industrial spaces, these systems provide an optimal balance of performance and cost-effectiveness.