York D1EE 048, D1EE 060, D2EE 036 installation instructions Installation

Page 3

035-12046-003-A-0204

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the current edition of the following national and local safety codes:

In USA:

1.National Electrical Code ANSI/NFPA No. 70.

2.Local electric utility requirements.

In Canada:

1.Canadian Electrical Code C22.1.

2.Canadian Installation Codes CAN/CGA-B149.1 and .2. Refer to Table 1 for Unit Application Data.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and / or the customer's expense.

Size of unit for proposed installation should be based on heat loss / heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA).

TABLE 1 - UNIT APPLICATION DATA

Voltage Variation

 

208/230V

187

/ 253

 

460V

414

/ 504

Min. / Max.1

 

 

575V

518

/ 630

 

 

Wet Bulb Temperature (°F) of Air on

57

/ 72

Evaporator Coil,

Min. / Max.

 

 

Dry Bulb Temperature (°F) of Air on

45 / 120

Condenser Coil,

Min.2 / Max.

1Utilization range “A” in accordance with ARI Standard 110.

2A low ambient accessory is available for operation down to 0°F

LOCATION

Use the following guidelines to select a suitable location for these units.

1.Unit is designed for outdoor installation only.

2.Condenser must have an unlimited supply of air. Where a choice of location is possible, position unit on either north or east side of building.

3.For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.

4.Roof structures must be able to support the weight of the unit and its options and / or accessories. Unit must be installed on a solid level roof curb or appropriate angle iron frame.

CAUTION: If a unit is to be installed on a roof curb or special frame other than a YORK roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside.

5.Maintain level tolerance to 1/2" maximum across the entire length or width of the unit.

6.Elevate the unit sufficiently to prevent any blockage of the air entrances by snow in areas where there will be snow ac- cumulation. Check the local weather bureau for the ex- pected snow accumulation in your area.

unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.

BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILL LIFT EVENLY.

Units may also be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.

LENGTH OF FORKS MUST BE A MINIMUM OF 42".

Remove the nesting brackets from the four corners on top of the unit. All screws that are removed when taking these brackets off must be replaced on the unit.

APPROXIMATE

CENTER OF

GRAVITY

FRONT

￿￿￿

 

 

￿￿￿￿

 

30-1/2￿

A

B

Dim.

3-5 Ton

 

 

 

 

 

 

A

19-3/4"

 

 

 

B

40-3/4"

FIG. 1 - CENTER OF GRAVITY

Refer to Table 2 for unit weights and to Figure 1 for approximate center of gravity.

CLEARANCES

All units require certain clearances for proper operation and service. Refer to Figure 5 for the clearances required for combustible construction, servicing, and proper unit operation.

WARNING:Do not permit overhanging structures or shrubs to obstruct outdoor air discharge outlet.

DUCTWORK

Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America (ACCA).

A closed return duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. The supply and return air duct connections at the unit should be made with flexible joints to minimize the transmission of noise.

The supply and return air duct systems should be designed for the CFM and static requirements of the job. They should NOT be sized to match the dimensions of the duct connections on the unit.

CAUTION: When fastening ductwork to the side duct flanges on the unit, insert the screws through the duct flanges only. DO NOT insert the screws through the casing.

Outdoor ductwork must be insulated and water- proofed.

Refer to Figure 5 for information concerning side and bottom supply and return air duct openings.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the

FILTERS

1" filters are supplied with each unit. 2" replacement filters may be used with no modification to the filter racks. Filters must always be installed ahead of the evaporator coil and must be

Unitary Products Group

3

Image 3
Contents Approvals GeneralInspection ReferenceTable of Contents Installation Thermostat Service AccessPower and Control Wiring Condensate DrainOptional Economizer Rain Hood CompressorsCooling / Heating Electronic Thermostat Typical Field WiringUtilities Entry Data KnockoutHole Size Used for MED Electric HeatersUnit Motor Size Speed MBH CFMSize CFM MBH RPM Unit AIR Flow1660 25001560 1077 1630Static Resistances Operation Turns Blower Drive Range RPM Open TON BELT-DRIVE Supply AIR Motor Pulley AdjustmentHeat Anticipator Setpoints Checking Supply AIR CFMNormal Maintenance Maintenance035-12046-003-A-0204 Unitary Products Group

D2EE 036, D1EE 060, D1EE 048 specifications

The York D1EE 048, D2EE 036, and D1EE 060 are advanced air conditioning units designed for superior performance and energy efficiency in commercial and industrial environments. These models are part of York’s reputation for creating reliable HVAC systems that cater to a variety of applications.

The York D1EE 048 is a high-efficiency rooftop unit, renowned for its compact design and robust construction. This model boasts an integrated economizer that enhances energy savings by optimizing the use of outside air for cooling. It features a cutting-edge variable speed compressor, which provides precision cooling and reduces energy consumption under varying load conditions. The advanced microprocessor control system enables quick adjustments to system performance, further enhancing comfort and efficiency.

In contrast, the York D2EE 036 is another exemplary model, distinguished by its dual-stage heating and cooling capabilities. This unit is particularly advantageous for facilities requiring consistent temperature control throughout different seasons. With a SEER rating that meets or exceeds regulatory requirements, the D2EE 036 helps operators minimize downtime and achieve lower operational costs. Its innovative design includes a streamlined airflow system, enabling quiet operation without compromising cooling performance.

Finally, the York D1EE 060 rounds out this trio with its innovative features tailored for large-building applications. This unit is equipped with advanced inverter technology, which allows for seamless adjustments in cooling capacity based on real-time demand. The unit is designed with high-performance heat exchangers that optimize thermal transfer efficiency, ensuring rapid cooling response while maintaining low energy usage. Its smart connectivity features allow for remote monitoring and adjustments, offering facility managers enhanced control over the indoor climate.

In terms of characteristics, all three models prioritize energy efficiency, user-friendly controls, and environmentally responsible refrigerants. They comply with the latest energy standards, making them suitable for organizations aiming for sustainability. With their robust construction and user-centric features, York’s D1EE 048, D2EE 036, and D1EE 060 units represent a commitment to delivering efficient, reliable, and cutting-edge climate control solutions. Whether for small offices or large industrial spaces, these systems provide an optimal balance of performance and cost-effectiveness.