Toshiba 300kVA UPS dimensions Toshiba G8000 Series UPS, General Mechanical Information

Models: 300kVA UPS

1 1
Download 1 pages 31.79 Kb
Page 1
Image 1
Toshiba G8000 Series UPS

Toshiba G8000 Series UPS

Installation Planning Guide for 300kVA UPS

Standard System: 480V Input, 480Y/277V Output

General Mechanical Information

 

Dimensions

 

 

Weight

 

 

(W x D x H)

 

 

 

 

 

 

 

 

 

Inches

 

 

Lbs.

 

 

82.7 x 35.4 x 78.75

4,630

 

Approximate Full-

Load Heat Loss

Btu/Hr

76,184

Primary AC Input (480V 3-Phase / 3-Wire)

Maximum Input Power

External Overcurrent

Suggested Minimum Feeder

Suggested Maximum Feeder Length

 

Demand

 

Protection

Wire Size – Per Phase

For Min. Wire Size in Steel Conduit

kVA

PF

 

Amps

Amps

AWG or kcmil at 75º C Temp. Rating

Feet

300

>0.98

 

361

500 AT

(2) x 4/0

380

Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)

Maximum Input Power

External Overcurrent

Suggested Minimum Feeder

Suggested Maximum Feeder Length

 

Demand

 

Protection

Wire Size – Per Phase / Neutral

For Min. Wire Size in Steel Conduit

kVA

PF

 

Amps

Amps

AWG or kcmil at 75º C Temp. Rating

Feet

300

0.8

 

361

500 AT

(2) x 2/0 / (2) x 350

380

Battery Input (360VDC Nominal)

 

Battery Capacity Required

 

Maximum Discharge

 

External Overcurrent

 

Suggested Minimum Feeder

 

 

for Full Load Output

 

at Full Load Output

 

Protection

 

Wire Size – Per Phase

 

 

kWB

 

Amps DC

 

Amps

 

 

g

 

 

 

 

AWG or kcmil at 75º C Temp. Ratin

255.3

887

 

1000 AT

(2) x 4/0 per battery cabinet

Suggested Maximum Feeder Length For Min. Wire Size in Steel Conduit

Feet

70

AC Output (480/277V 3-Phase / 4-Wire)

 

Rated Output Power

 

 

External Overcurrent

 

 

Suggested Minimum Feeder

 

 

Suggested Maximum Feeder Length

 

 

 

 

Protection

 

 

Wire Size – Per Phase / Neutral

 

 

For Min. Wire Size in Steel Conduit

 

 

 

 

 

 

 

 

 

 

 

 

 

kVA

PF

Amps

 

 

Amps

 

 

AWG or kcmil at 75º C Temp. Rating

 

 

Feet

 

300

0.8

361

 

 

500 AT

 

(2) x 4/0 / (2) x 350

380

 

Important Notes:

1.Maximum Current required at Primary AC Input based on full load output and maximum battery charging current.

2.Output load conductors are to be installed in separate conduit from input conductors.

3.Control wires and power wires are to be installed in separate conduits.

4.Recommended AC input and output overcurrent protection based on continuous full load current per NEC.

5.Wiring shall comply with all applicable national and local electrical codes.

6.Grounding conductors to be sized per NEC Article 250-122. Neutral conductors to be sized per NEC Article 310.15.

-Primary AC Input: 3φ, 4-wire + ground.

-Alternate AC Input: 3φ, 4-wire + ground.

-AC Output: 3φ, 4-wire + ground.

-DC Input: 2-wire (Positive/Negative) + ground.

7.Nominal battery voltage based on the use of VRLA type batteries (2.0 volts/cell nominal).

8.Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC.

9.DC wires should be sized to allow not more than a 2-volt drop at maximum discharge current.

10.Weights do not include batteries or other auxiliary equipment external to the UPS.

11.Sizing calculations based on the following assumptions:

-Not more than 3 current-carrying conductors installed in steel conduit in ambient temperature of 30 degrees C.

-Temperature rating of conductors and terminals: 90 deg. C.

-Feeder distance calculations based on NEC Tables 8 and 9 data, allowing for 2% AC voltage drop.

-Reference: 2002 NEC Handbook. Consult latest edition of applicable national and local codes for possible variations.

12.Ratings of wires and overcurrent devices are suggested minimums. Consult with a registered Professional Engineer within your local area for proper size selections.

13.More than one Battery Cabinet will require a DC Junction box for all battery cabinet connections.

TOSHIBA INTERNATIONAL CORPORATION

13131 West Little York Road

Houston, TX 77041

Telephone: (800) 231-1412

Fax: (713) 896-5212

Corporate Web Site: www.tic.toshiba.com

Group Web Site: www.toshibaups.com

Rev. 1.03

Page 1 of 1

G8000-IPG-300kVA

Page 1
Image 1
Toshiba dimensions Toshiba G8000 Series UPS, Installation Planning Guide for 300kVA UPS, General Mechanical Information