York Unitary Products Group: Air Conditioner Models and Performance Data

Page 9

 

 

 

 

 

 

 

 

036-21103-003 Rev. A (0403)

 

 

 

 

 

 

 

 

 

 

 

COOLING PERFORMANCE DATA

 

 

 

 

 

 

 

 

 

 

AIR CONDITIONER MODEL NO.

H1RA030S78A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

 

G2FD030S17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSER

IDCFM

 

650

 

 

850

 

 

 

1050

 

 

 

 

 

 

 

 

 

 

 

 

ENTERING AIR

ID DB (°F)

85

80

70

85

80

70

 

85

80

70

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

72

67

57

72

67

57

 

72

67

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

26.4

25.3

24.0

26.6

25.7

24.6

 

26.7

26.1

25.2

75

 

 

 

 

 

 

 

 

 

 

 

S.C.

15.4

15.6

15.4

16.2

16.7

16.8

 

16.9

17.8

18.2

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

2.39

2.35

2.32

2.53

2.49

2.46

 

2.56

2.53

2.50

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

25.4

23.9

21.8

25.7

24.6

22.8

 

26.1

25.2

23.7

85

 

 

 

 

 

 

 

 

 

 

 

S.C.

15.3

15.1

14.4

16.4

16.6

16.2

 

17.4

18.2

18.1

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

2.67

2.62

1.40

2.82

2.76

2.71

 

2.93

2.88

2.83

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

24.4

22.5

19.6

24.9

23.4

20.9

 

25.4

24.3

22.2

95

 

 

 

 

 

 

 

 

 

 

 

S.C.

15.3

14.6

13.4

16.6

16.6

15.7

 

17.9

18.5

17.9

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

2.71

2.64

2.55

2.86

2.80

2.71

 

2.91

2.85

2.77

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

22.5

20.1

17.6

23.2

21.1

18.6

 

23.9

22.1

19.6

105

 

 

 

 

 

 

 

 

 

 

 

S.C.

14.7

13.8

12.7

16.4

15.9

14.7

 

18.1

17.9

16.8

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

2.98

2.89

2.80

3.14

3.05

2.95

 

3.27

3.18

3.08

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

20.6

17.7

15.6

21.5

18.8

16.3

 

22.4

19.8

16.9

115

 

 

 

 

 

 

 

 

 

 

 

S.C.

14.2

13.0

11.9

16.3

15.2

13.8

 

18.3

17.3

15.6

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

3.00

2.88

2.80

3.17

3.05

2.95

 

3.24

3.12

3.00

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

17.8

15.2

13.3

18.7

15.9

14.0

 

19.5

16.7

14.7

125

 

 

 

 

 

 

 

 

 

 

 

S.C.

13.3

12.4

11.4

15.4

14.3

13.1

 

17.4

16.1

14.7

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W

3.13

3.02

2.93

3.30

3.18

3.08

 

3.37

3.23

3.13

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.

Air Handler

Coil

T.C.

S.C.

KW

 

 

 

 

 

N1AHB1293

G2FD030S17

1.00

1.00

1.00

 

 

 

 

 

N1AHB1293

G2FD036S17

1.02

1.03

1.03

 

 

 

 

 

F2RP036N93

 

1.02

1.03

1.03

 

 

 

 

 

Unitary Products Group

9

Image 9
Contents Description FeaturesPhysical and Electrical Data 1 & 3 Phase Cooling Capacity With Air Handler Coils SUCT. T/P AIR Temp on Condenser Model Cooling PerformanceSound Ratings AccessoriesTypical Field Wiring 3 PH Application 036S50 060S50 Typical Field Wiring 1 PH Application 018S78 036S78Cooling Performance Data H1RA018S78AG2FD024S17 G2FD030S17 H1RA024S78AH1RA030S78A G2FD036S17 H1RA036S50AH1RA036S78A G2FD048S21 H1RA048S50AFD060S24A H1RA060S50AAIR Handlers Matching Indoor CompnentsUnitary Products Group Unitary 5005 Norman Product York Group Drive 73069