York 150 Electrical Data DM120 10 TON with Power Convenience Outlet, 380 11.5 75.0

Page 20

035-17311-002-A-0803

TABLE 10: ELECTRICAL DATA - DM120 (10 TON) WITHOUT POWER CONVENIENCE OUTLET

 

 

 

 

Supply

Pwr

Pwr

 

 

 

Min. Circuit

MCA

Max

Max Fuse*

 

 

 

OD Fan

 

 

 

w/Power

Fuse*

Size

 

Compressors

Blower Motor

Exh

Conv

Electric Heater

Actual

Heater

Ampacity

Voltage

 

 

Motors

 

FLA

Motor

Outlet

(Amps)

Exhaust

Size

w/Power

 

 

 

 

 

 

 

 

 

Model No.

KW

Amps

 

 

(Amps)

(Amps)

Exhaust

 

RLA

LRA

FLA

2

 

3

FLA

FLA

 

 

 

2

3

2

3

2

3

2

3

 

ea.

ea.

ea.

HP

 

HP

 

 

 

HP

HP

HP

HP

HP

HP

HP

HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

33.2

34.4

35.4

36.6

40

45

45

45

 

 

 

 

 

 

 

 

 

2TP04521850

11.3

17.2

33.2

34.4

35.4

36.6

40

45

45

45

380

11.5

75.0

1.6

4.1

 

5.3

2.2

0.0

2TP04522450

15

22.8

33.6

35.1

36.4

37.9

40

45

45

45

 

 

 

 

 

 

 

 

 

2TP04523650

21.3

32.4

45.6

47.1

48.3

49.8

50

50

50

50

 

 

 

 

 

 

 

 

 

2TP04525450

33.8

51.4

69.3

70.8

72.1

73.6

70

80

80

80

*Maximum HACR breaker of the same AMP size is applicable.

TABLE 11: ELECTRICAL DATA - DM120 (10 TON) WITH POWER CONVENIENCE OUTLET

 

 

 

 

Supply

Pwr

Pwr

 

 

 

Min. Circuit

MCA

Max

Max Fuse*

 

 

 

OD Fan

 

 

 

w/Power

Fuse*

Size

 

Compressors

Blower Motor

Exh

Conv

Electric Heater

Actual

Heater

Ampacity

Voltage

 

 

Motors

 

FLA

Motor

Outlet

(Amps)

Exhaust

Size

w/Power

 

 

 

 

 

 

 

 

 

Model No.

KW

Amps

 

 

(Amps)

(Amps)

Exhaust

 

RLA

LRA

FLA

2

 

3

FLA

FLA

 

 

 

2

3

2

3

2

3

2

3

 

ea.

ea.

ea.

HP

 

HP

 

 

 

HP

HP

HP

HP

HP

HP

HP

HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

39.5

40.7

41.7

42.9

50

50

50

50

 

 

 

 

 

 

 

 

 

2TP04521850

11.3

17.2

39.5

40.7

41.7

42.9

50

50

50

50

380

11.5

75.0

1.6

4.1

 

5.3

2.2

6.3

2TP04522450

15

22.8

41.5

43

44.2

45.7

50

50

50

50

 

 

 

 

 

 

 

 

 

2TP04523650

21.3

32.4

53.5

55

56.2

57.7

60

60

60

60

 

 

 

 

 

 

 

 

 

2TP04525450

33.8

51.4

77.2

78.7

79.9

81.4

80

80

80

90

*Maximum HACR breaker of the same AMP size is applicable.

TABLE 12: ELECTRICAL DATA - DM150 (12-1/2 TON) WITHOUT POWER CONVENIENCE OUTLET

 

 

 

 

Supply

Pwr

Pwr

 

 

 

Min.

MCA

Max

Max Fuse*

 

 

 

OD Fan

 

 

 

Circuit

w/Power

Fuse*

Size

 

Compressors

Blower

Exh

Conv

Electric Heater

Actual

Heater

Voltage

 

 

Motors

Motor FLA

Motor

Outlet

Ampacity

Exhaust

Size

w/Power

 

 

 

 

 

 

 

 

Model No.

KW

Amps

(Amps)

(Amps)

(Amps)

Exhaust

 

RLA

LRA

FLA

3

5

FLA

FLA

 

 

 

3

5

3

5

3

5

3

5

 

ea.

ea.

ea.

HP

HP

 

 

 

HP

HP

HP

HP

HP

HP

HP

HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

30.1

32.9

32.3

35.1

35

40

40

40

 

 

 

 

 

 

 

 

2TP04521850

11.3

17.2

30.1

32.9

32.3

35.1

35

40

40

40

380

9.6

79.0

1.6

5.3

8.1

2.2

0.0

2TP04522450

15

22.8

35.1

38.6

37.9

41.4

40

40

40

45

 

 

 

 

 

 

 

 

2TP04523650

21.3

32.4

47.1

50.6

49.8

53.3

50

60

50

60

 

 

 

 

 

 

 

 

2TP04525450

33.8

51.4

70.8

74.3

73.6

77.1

80

80

80

80

*Maximum HACR breaker of the same AMP size is applicable.

TABLE 13: ELECTRICAL DATA - DM150 (12-1/2 TON) WITH POWER CONVENIENCE OUTLET

 

 

 

 

Supply

Pwr

Pwr

 

 

 

Min. Circuit

MCA

Max

Max Fuse*

 

 

 

OD Fan

 

 

 

w/Power

Fuse*

Size

 

Compressors

Blower Motor

Exh

Conv

Electric Heater

Actual

Heater

Ampacity

Voltage

 

 

Motors

 

FLA

Motor

Outlet

(Amps)

Exhaust

Size

w/Power

 

 

 

 

 

 

 

 

 

Model No.

KW

Amps

 

 

(Amps)

(Amps)

Exhaust

 

RLA

LRA

FLA

3

 

5

FLA

FLA

 

 

 

3

5

3

5

3

5

3

5

 

ea.

ea.

ea.

HP

 

HP

 

 

 

HP

HP

HP

HP

HP

HP

HP

HP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

36.4

39.2

38.6

41.4

45

45

45

50

 

 

 

 

 

 

 

 

 

2TP04521850

11.3

17.2

36.4

39.5

38.7

42.2

45

45

45

50

380

9.6

79.0

1.6

5.3

 

8.1

2.2

6.3

2TP04522450

15

22.8

43

46.5

45.7

49.2

45

50

50

50

 

 

 

 

 

 

 

 

 

2TP04523650

21.3

32.4

55

58.5

57.7

61.2

60

60

60

70

 

 

 

 

 

 

 

 

 

2TP04525450

33.8

51.4

78.7

82.2

81.4

84.9

80

90

90

90

*Maximum HACR breaker of the same AMP size is applicable.

20

Unitary Products Group

Image 20
Contents Installation Manual Table of Contents List of Figures List of Tables Safety Considerations GeneralInspection Reference½ 12½ Ton Predator Model Number Nomenclature NomenclatureNOMENCLATURE, Additonal Options Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil, Phase Monitor, & Coil Guard Preceding Installation InstallationInstallation Safety Information Rigging and Handling Unit Temperature LimitationsLocation Point Load Weight Length of Forks Must be a Minimum of 60 InchesUnit Dimensions Unit Clearances Detail CBottom Duct Openings from Above Ductwork Duct CoversSide Panels with Hole Plugs Condensate Drain Thermostat Wiring Control Wire SizesPower and Control Wiring Power Wiring DetailElectronic Thermostat Field Wiring RLA LRA FLA Electrical Data DM120 10 TON with Power Convenience Outlet 380 11.5 75.0Minimum Supply AIR CFM OPTIONS/ACCESSORIESPhysical Data Power Exhaust Minimum Position AdjustmentEnthalpy SET Point Adjustment EconomizerEnthalpy SET Point Chart Phasing Blower RotationSupply AIR Limitations Belt Tension1/2 TON Standard Motor Down Shot Blower PERFORMANCE* † 1/2 TON Optional Motor Down Shot Blower PERFORMANCE* †10 TON Standard Motor Down Shot Blower PERFORMANCE* † 10 TON Optional Motor Down Shot Blower PERFORMANCE* †12-1/2 TON Standard Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Down Shot Blower PERFORMANCE* †1/2 TON Standard Motor Side Shot Blower PERFORMANCE* † 1/2 TON Optional Motor Side Shot Blower PERFORMANCE* †4965 12-1/2 TON Standard Motor Side Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Side Shot Blower PERFORMANCE* †Indoor Blower Specifications AIR BalanceChecking AIR Quantity Method ONE Method TWODRY Coil Delta P Supply AIR Drive Adjustment Operation Additional Static ResistanceMotor Sheave Datum Diameters Sequence of Operations OverviewCooling Sequence of Operation Safety Controls Compressor ProtectionElectric Heating Operation Errors Electric Heat Limit SettingElectric Heating Sequence of Operations Electric Heat Antictpator SetpointsSTART-UP Cooling Charging the Unit10 TON Standard Efficiency Superheat Charging 12.5 TON Standard Efficiency Superheat ChargingPredator Flash Codes Normal Maintenance TroubleshootingGeneral Basic Troubleshooting Flowchart Unit Control Board Flash CodesCooling Troubleshooting Guide Unitary Products Group 035-17311-002-A-0803 Unitary 5005 Norman Products York Group Drive 73069