DESIGN GUIDELINES FOR OUTSIDE COMBUSTION AIR CONNECTION

1)For installations with horizontal through-the-wall exhaust, it is strongly recommended that the stove combustion air be connected to the outside. If the home is newer or has been tightly insulated, it is required to install outside combustion air.

2)Connection to outside the house is REQUIRED for mobile home installations. We strongly urge use of the 69FAK Fresh Air Kit.

90 DEGREE BEND TERMINATION

WIND HOOD TERMINATION

Wind Hood

2” Min. Diameter

3”

NOTE:

A wire mesh screen with a maximum opening size of 3/8” must be installed in the pipe or elbow for rodent exclusion..

2”

6”

3)Only noncombustible pipe 2 inches (or greater) in diameter is approved to use for outside air connections (straight or flexible). PVC pipe is NOT approved and should NEVER be used.

4)If the air inlet is connected to the outside, it MUST be terminated with a vertical 90-degree bend (down) or with a wind hood. Failure to do so could result in a burn back during high winds blowing directly up the air inlet during a simulta- neous power failure (see diagram above).

5)Blockage, excessive length, or extra bends in the air intake pipe will starve the stove of combustion air. A 90-degree bend is equivalent in restriction to approximately 30 inches of straight inlet pipe.

CAUTION: The operation of exhaust fans such as bath room fans, attic fans, etc. might starve the heater of combustible air creating a negative pressure in the room. Provide adequate ventilation in the room accompanying the heater. If not, the pressure switch may shut off operation of the heater. (Due to negative pressure)

USSC

11

Image 11
Contents 6039, 6039I, 6039T Congratulations Specifications6039T Assembly AssemblyPedestal Trim Assembly Disconnect the Power Cord Before Servicing this Stove 6039I AssemblyComponent Location Burning Solid Fuels Safety StepsContent Installation RequirementsHearth Protection Clearances to Combustibles 6039TClearances to Combustibles Vent Termination Clearances Guidelines for Exhaust Venting Systems DesignDesign Guidelines for Outside Combustion AIR Connection Mobile Home Installation Requirements Installation ConfigurationsDimensional tolerance ±1/4 Ussc Installation AS ABUILT-INFIREPLACE Design Guidelines for 6039I Insert InstallationINSTALLATIONINTOAFACTORY-BUILT Metal Fireplace Installation Into a Masonry FireplaceRemoval of Broken or Damaged Ceramic Glass Glass MAINTENANCE, Removal and ReplacementControl Panel Understanding the Control BoardTo Start Lighting InstructionsDisposal of Ashes Maintenance InstructionsSPECIALCLEANING/OPERATIONAL Instructions Fuel Additive Automatic Safety FeaturesSTART-UP Sequence of Events Circuit Board FunctionsError Codes and Display Indicators Problem Trouble ShootingWiring Diagram Repair Parts DIAGRAM-6039 Repair Parts LIST-6039 Repair PARTS-6039I Repair Parts LIST-6039I 6039T Parts Diagram & List Ussc HOW to Order Repair Parts