Omega Vehicle Security DRF-RES Series, DRF-POT Ranges, Galvanic Isolation Levels, Power Supply

Page 9

 

 

 

 

User’s Manual DRF Series

 

TECHNICAL DATA : Models DRF-POT and DRF-RES

INPUT SIGNAL for POTENTIOMETER

 

 

RANGES

0/100 %

StandardDINrailmounting,asspecified

 

0/50 %

on DIN46277 and DIN EN 50022

 

0/25 %

37.5 x 7.5 mm (1.38 x 0.3 ´´)

 

0/12.5%

 

 

 

(minimum 8%)

GALVANIC ISOLATION LEVELS

Potentiometer value min 100Ohms

DCUnits

 

Input - Output

3.5 KV (60 seconds)

 

max 1MOhm

Power-Input

3.5 KV (60 seconds)

3 Wire System, 1 Vdc Excitation

Power- Output

1 KV (60 seconds)

INPUT SIGNAL in RESISTANCE

ACUnits

 

RANGES

0/10 KOhms

Input - Output

3.5 KV (60 seconds)

 

0/5 KOhms

Power- Input

3.5 KV (60 seconds)

 

0/3 KOhms

Power - Output 3.5 KV (60 seconds)

 

0/1.5 KOhms

 

 

(minimum 750 Ohms)

2 Wire System, 0.2 mA Excitation

OUTPUT SIGNAL in VDC

RANGES

0/10 Vdc

 

0/1 Vdc

Max Output

11Vdc approx.

All isolation levels are tested during a time of 60 seconds, with current leaks <1mA

Note : Indicated isolation levels are also

sometimes named as STRENGTHENED ISOLATION levels, for systems with

Polution Level 2

Min Output

-1Vdc approx.

Min Load R

1KOhm

OUTPUT SIGNAL in mA

RANGES

0/20mA (4/20mA)

Max Output

22mA approx.

Min Output

-1.5mA approx.

Max Load R

400 Ohms

POWER SUPPLY

DC Power

24Vdc ±10%

AC Power

230Vac ±10% 50/60 Hz

 

115Vac ±10% 50/60 Hz

Consumption

<3.8VA

GENERALSPECIFICATIONS

Accuracy

<0.2% F.S.

Optimized for

12 bit systems

Linearity

<0.1% F.S.

Thermal Drift

<250 ppm/ºC Tipical

Warm-Up Time

5 minutes

Response Time <70mS (90% of signal)

Plug-In Screw Terminals Maximum Wire Section 2.5 mm2

Protection

IP-30

Temp.Operation from 0 to 60ºC

Temp.Storage

from -20 to +70ºC

MECHANICALDIMENSIONS

MATERIALS

DC Units

22.5 x 93 x 110 mm

Box and Cover in Poliamide PA6 UL94

AC Units

37.0 x 93 x 110 mm

V-2 blue color

Weight DC

120 gr.

Terminals in Poliamide UL94 V-0

Weight AC

200 gr.

 

Page 9

Image 9
Contents User’s Guide Servicing North America Incaseoffire Safetyconsiderations PRESCRIPTION.- Before starting anyDo not use systems with Vaporized liquidsGeneralinformation Quickguide Power Supply ConnectionsSelection Jumpers Output Signal Range Signal AdjustmentSelection Jumpers Input Signal Range AdjustmentExampleformodelDRF-POTSelection Jumpers I Nput Signal Range Dimensions and Connections Generalspecifications Power SupplyMechanicaldimensions Materials RangesRecommended Fuses InstalationWARRANTY/ Disclaimer Shop online at omega.com