Lochinvar 51 - 211 manual Maintenance schedule, Fill condensate trap with water

Page 6

2 Maintenance schedule

Maintenance procedures

Boiler must be serviced and maintained

User’s Information Manual

Read the list of potential materials listed in Table 1A on page 4 of this manual. If any of these products are in the room from which the boiler takes its combustion air, they must be removed immediately or the boiler combustion air (and vent termination) must be relocated to another

￿WARNING

NOTICE

The boiler must be inspected and started annually at the beginning of the heating season by a qualified service technician. In addition, the maintenance and care of the boiler designated on page 5 of this manual and explained on pages 6 through 8 must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure, causing possible severe personal injury, death, or substantial property damage.

The following information provides detailed instructions for completing the maintenance items listed in the maintenance schedule on page 5. In addition to this maintenance, the boiler must be serviced and started up at the beginning of each heating season by a qualified service technician.

area.

Check pressure/temperature gauge

1.Make sure the pressure reading on the boiler pressure/ temperature gauge does not exceed 24 psi. Higher pressure may indicate a problem with the expansion tank.

2.Contact a qualified service technician if problem persists.

Check vent piping

1.Visually inspect the flue gas vent piping for any signs of blockage, leakage, or deterioration of the piping. Notify your qualified service technician at once if you find any problems.

￿WARNING Failure to inspect the vent system as noted above and have it repaired by a qualified

service technician can result in vent system failure, causing severe personal injury or

Check boiler area

death.

￿WARNING

To prevent potential of severe personal injury, death, or substantial property damage, eliminate all materials discussed below from the boiler vicinity and the vicinity of the boiler combustion air inlet. If contaminants are found:

Remove products immediately from the area. If they have been there for an extended period, call a qualified service technician to inspect the boiler for possible damage from acid corrosion.

If products cannot be removed, immediately call a qualified service technician to re-pipe vent and air piping and locate vent termination/air intake away from contaminated areas.

Check air piping

1.Visually inspect the air inlet termination to be sure it is unobstructed. Inspect the entire length of air piping to ensure piping is intact and all joints are properly sealed.

2.Call your qualified service technician if you notice any problems.

Check relief valve

1.Inspect the boiler relief valve and the relief valve discharge pipe for signs of weeping or leakage.

2.If the relief valve often weeps, the expansion tank may not be working properly. Immediately contact your qualified service technician to inspect the boiler and system.

Check condensate drain system

1.Combustible/flammable materials -- Do not store combustible materials, gasoline or any other flammable vapors or liquids near the boiler. Remove immediately if found.

2.Air contaminants -- Products containing chlorine or fluorine, if allowed to contaminate the boiler intake air, will cause acidic condensate in the boiler. This will cause significant damage to the boiler if allowed to continue.

6

1.Inspect the condensate drain line, condensate PVC fittings and condensate trap.

Fill condensate trap with water

1.Remove the bezel on the front of the unit.

2.Remove the PVC cap retaining screw from the PVC cap (FIG. 2-1).

3.Remove the 2" PVC cap with the switch located at the top of the trap (FIG. 2-1).

Image 6
Contents User’s Information Manual Models 51 Contents Boiler service and maintenance Please read before proceedingPrevent combustion air contamination Products to avoidAreas likely to have contaminants Maintenance schedule Service technician Owner maintenanceSee pages 6 8 for detailed instructions Maintenance schedule Fill condensate trap with water1Condensate Trap Condensate disposalCheck air vents Operating instructions Installer Smart System control moduleUser Temperature Units Night Setback OverrideSpace heating SH1, SH2, SH3 and tank set points Call for Heat Smart System control module Dial Function User’s Information Manual

51 - 211 specifications

Lochinvar 51-211 is a notable model in the realm of high-performance heating solutions, designed to efficiently meet commercial and residential hot water demands. This innovative water heater stands out due to its capacity, advanced technologies, and energy efficiency, making it a preferred choice for many.

One of the primary features of the Lochinvar 51-211 is its impressive output. With a 211,000 BTU input and a robust design, it is capable of delivering a substantial amount of hot water quickly, which is essential in applications where hot water demand fluctuates significantly. This unit is particularly suitable for large residential homes, restaurants, and other commercial settings where high-volume hot water is critical.

The Lochinvar 51-211 incorporates cutting-edge technology to optimize its performance. It features a stainless steel heat exchanger that not only enhances durability but also improves heat transfer efficiency. This construction provides not only longevity but also minimizes maintenance needs over the lifespan of the unit. Additionally, its smart control system allows for precise temperature control and monitoring, ensuring that users can easily customize settings according to their needs.

Energy efficiency is a cornerstone of the Lochinvar brand, and the 51-211 model is no exception. It achieves a high Energy Factor (EF), which translates to lower energy costs and reduced environmental impact. This unit is also designed to meet stringent efficiency standards, making it an ideal option for environmentally conscious consumers.

Another characteristic of the Lochinvar 51-211 is its versatility in installation. It can be installed in various configurations, allowing for flexible integration into existing systems. Furthermore, its compact design means it can fit into tight spaces without compromising functionality, making it perfect for urban settings where space is often a premium.

Safety features are also a priority in the design of the Lochinvar 51-211. The unit incorporates built-in safeguards, including flue gas monitoring and a vent system designed to prevent backdrafts, ensuring reliable and safe operation for users.

In summary, the Lochinvar 51-211 water heater combines high BTU output, advanced stainless steel technology, excellent energy efficiency, versatile installation options, and safety features. These attributes make it a top choice for anyone in need of a dependable and efficient hot water solution. With Lochinvar’s commitment to quality, users can feel confident that this unit will provide consistent performance for years to come.