Lochinvar CW 645, CW 745 manual Outdoor Installation, Masonry Chimney

Page 11

(FIG. 8) MULTIPLE UNIT BAROMETRIC

DAMPER INSTALLATION

For this type of installation, it is best to use a draft control for each water heater located on the riser between the vent outlet and the breeching - Location “A”. When this riser is too short to permit the installation of a draft control, locate a separate control for each water heater on the main breeching as illustrated in Location “B”. If, because of general crowding or other reasons, neither of these locations are possible, use a single large control in the breeching between the water heater nearest the chimney and the chimney, as shown in Location “C”.

All draft readings are made while unit is in stable operation (approximately 5 minutes running time).

Masonry Chimney

A masonry chimney must be properly sized for the installation of a high efficiency gas fired appliance. Exterior masonry chimneys, with one or more sides exposed to cold outdoor temperatures, are more likely to have venting problems. The temperature of the flue products from a high efficiency appliance may not be able to sufficiently heat the masonry structure of the chimney to generate proper draft. This will result in

condensing of flue products, damage of the masonry flue/tile, insufficient draft and possible spillage of flue products into an occupied living space.

Carefully inspect all chimney systems during the project design phase. If there is any doubt about the sizing or condition of a masonry chimney, it is prudent to reline the chimney with a properly sized and approved chimney liner system. Metallic liner systems (Type “B” doublewall or flexible or rigid metallic liners) are recommended. Consult with local code officials to determine code requirements or the advisability of using or relining a masonry chimney.

OUTDOOR INSTALLATION

(FIG. 9) OUTDOOR VENTING

Units are self venting and can be used outdoors when installed with the optional Outdoor Cap. This cap mounts directly to the top of the water heater and covers the flue outlet and combustion air inlet openings on the jacket. No additional vent piping is required. Maintain a minimum clearance of 3” (76mm) to combustible surfaces and a minimum of 3” (76 mm) clearance to the air inlet.

NOTE: Common venting systems may be too large when an existing unit is removed. Be careful to resize any common venting system when new appliances are installed or existing appliances are replaced.

NOTE:

Flue gases will form a white plume in winter. Plume could obstruct window view. Flue gas condensate can freeze on exterior surfaces or on the vent cap. Flue gas condensate can cause discoloration of exterior building surfaces. Adjacent brick or masonry surfaces should be protected with a rust resistant sheet metal plate.

NOTE: Venting of a high efficiency appliance into a cold or oversized masonry chimney can result in operational and safety problems.

L o c h i n v a r D E S I G N E R S G U I D E C O P P E R - F I N W A T E R H E A T E R 6 1 5 - 8 8 9 - 8 9 0 0

9

 

 

 

 

Image 11
Contents DESIGNER’S Guide COPPER-FINWATER Heater Page Table of Contents Location of Unit CodesTable a Clearances from Combustible Construction Special Location Outdoor USEGAS AIR Connection Inlet HOT Water Outlet Front Flue Products Vent Right SideHOT Water Outlet Left SideCombustion & Ventilation AIR Exhaust Fans VentingContaminants GeneralVent Terminations Barometric Dampers Venting OptionsConventional Venting Masonry Chimney Outdoor InstallationGAS Supply Freeze Protection Outdoor InstallationExample of High Altitude Applications Water ConnectionsHigh Altitude Applications Inlet and Outlet Water ConnectionsBall valves LOW Water Temperature DeliveryWater Velocity Control Pump OperationWater Treatment Water Flow SwitchRelief Valve Electrical RequirementsThermometer System Pump Relief Valve TEE Elbow Union Expansion TankBuilding HOT Water Supply Relief Valve Single Heater TWO TankTWO Temperature Installation Single HEATER-SINGLE Tank Reducing TEE Cold Water Supply Drain OutletTWO HEATERS-TWO Tanks MULTI-STACK Frame W/ Water Heaters and Storage Tank LIT0396Page Lochinvar Corporation Lebanon, TN 615-889-8900 / Fax

CW 645, CW 745 specifications

The Lochinvar CW 645 and CW 745 are advanced water heater models from Lochinvar, a leading manufacturer of water heating solutions. These high-efficiency units are designed to meet the demands of both commercial and residential applications, combining cutting-edge technology with robust performance.

One of the defining features of the CW series is its commitment to energy efficiency. With their stainless steel construction, these water heaters boast a high thermal efficiency rating. The CW 645 and CW 745 utilize modulating technology, allowing them to adjust the heating output based on real-time demand. This results in reduced energy consumption and lower operational costs, making them an ideal choice for environmentally conscious consumers.

These models are equipped with a powerful burner system designed to provide optimal heating performance. The burners are engineered for reliability and longevity, ensuring consistent hot water supply even under heavy usage. Additionally, the CW 645 and CW 745 feature a compact footprint, making them suitable for installation in tight spaces or areas with limited access.

The advanced control system in these units takes user experience to the next level. With intuitive controls and a digital display, users can easily set temperatures and monitor system performance. The integrated diagnostics feature ensures quick troubleshooting, enhancing reliability and reducing maintenance time.

Safety is another paramount consideration in the design of the CW series. Both models come equipped with multiple safety features, including a flame safeguard system and a high-temperature limit switch. These safety mechanisms provide peace of mind while ensuring compliance with local building codes.

Furthermore, the CW 645 and CW 745 models are versatile in their applicability. They can be used for a variety of applications including restaurants, schools, and hospitals. Their ability to provide consistent hot water makes them particularly valuable in high-demand situations.

In summary, the Lochinvar CW 645 and CW 745 are exceptional water heating solutions that epitomize efficiency, safety, and performance. With advanced features, user-friendly controls, and solid construction, these units are well-suited to meet the hot water needs of both commercial and residential users. Investing in a CW series water heater not only secures a reliable source of hot water but also contributes to long-term energy savings and environmental sustainability.