Lennox International Inc 51M37 operation manual FAN Auto

Page 40

COOL − Using the Cool Mode

Enabling and Disabling Cool Mode

Use the COOL button to enable or disable cool mode as desired. If the thermostat is in heat or off mode, cool mode is enabled when the COOL button is pressed. This is indi- cated by COOL on the right side of the display (see figure 9).

 

 

Turn Cool ON/OFF

 

 

 

Heat

Cool

 

 

 

Prog

Auto

 

 

i0:30

 

 

 

70

Copy Day/Time

 

 

 

 

 

75

66

Fan

Hold

(DOOR

 

 

 

 

 

 

OPEN)

 

 

Settings Enter

 

 

 

 

(Outside)

 

Figure 9

If the thermostat is in cool mode, pressing the COOL but- ton disables cool mode (indicated by OFF on the right side of the display).

Cooling Demand

Set the thermostat to cool mode to control the cooling equipment. Then, if the room temperature is higher than the temperature setpoint, as shown in figure 10, the ther- mostat detects a cooling demand and will activate the cool- ing equipment to satisfy the demand.

Cooling Demand

 

COOL SETPOINT

 

FAN

76°

 

AUTO

COOL

ROOM

 

 

 

° HEAT SETPOINT

Lo

80

68

°

 

 

 

Hi

Figure 10

Cooling operation is indicated by flashing nowflake" icons. When the actual temperature drops below the tem- perature setpoint, the snowflake icons will disappear. This indicates that the cooling demand has been satisfied and that the cooling equipment has been turned off.

If your system supports 2−stage cooling (as does the 51M42 thermostat), you may notice various cooling levels being delivered during a demand. Also, if a small cooling demand is present, "Lo" will be displayed in the SYSTEM box. However, if a large cooling demand is present, "Hi" will be displayed in the lower right side of the display (shown in figure 10).

NOTE − If no buttons are pressed during a demand for cooling, the equipment must operate for at least 4 minutes. After a demand has been satisfied, cooling equipment op- eration is locked out for 5 minutes. If another cooling de- mand occurs during this 5−minute interval,

snowflakes will flash; however, the cooling equipment will not operate until the 5−minute delay has elapsed.

AUTO − Using the Autochangeover Mode

When in either heat mode or cool mode, autochangeover can be enabled or disabled by pressing the AUTO button. If enabled, AUTO appears at the lower right corner of the dis- play. The thermostat will then automatically change over from heating to cooling and vice versa, to keep the room temperature in between the heating and cooling setpoints. Autochangeover can be used in either of the thermostat hold modes, or when the thermostat program is running. These modes are described later.

HOLD − Using Temperature Hold Modes

When the HOLD button is displayed at the HOME screen, the thermostat is in a temperature hold condition. This means that the temperature program data is ignored and the thermostat functions much like a non−programmable thermostat.

Adjusting Temperature Setpoint in Hold Mode

The temperature setpoint represents the desired tempera- ture of the space around the thermostat. The default heat setpoint in hold mode is 70°F; the default cool setpoint in hold mode is 78°F.

To adjust the setpoint, press the UP or DOWN (YB) arrow buttons (see figure 11); the existing setpoint is displayed to the right of the actual room temperature. Each button press adjusts the setpoint up or down by 1 degree.

 

Hold Temperature Mode

 

 

 

Heat

Cool

 

 

i0:30

Prog

Auto

 

 

 

 

 

 

78

Copy Day/Time

 

 

 

 

 

80

70

Fan

Hold

(DOOR

 

 

 

 

 

 

OPEN)

 

 

Settings Enter

 

 

 

 

(Outside)

 

Figure 11

After the desired setpoint is reached, the HOME screen will reappear after about 15 seconds.

Permanent Hold Mode

At any time the program is running, from the HOME screen, set a permanent hold (program override) by press- ing the HOLD button (see figure 11). The thermostat now functions much like a non−programmable thermostat. Use the Up/Down arrow buttons to adjust the hold setpoint. To return to the program, press the HOLD button again.

Page 4

505069M 07/05

Image 40
Contents 51M37 Merit Series Buttons, Backlight, Timers & Settings DAY/TIME − Setting the Day and TimeThermostat Buttons Home ScreenHeat − Using the Heat Mode FANCool − Using the Cool Mode Enabling and Disabling Cool ModeCool Mode Disabled Turn Cool ON/OFFI036 FAN PM I036 FANSettings − Filter/Maintenance Reminders FAN − Controlling the Fan OperationSettings − Balance Point Service IndicatorThermostat Reset Removing/Installing ThermostatDefault Thermostat Settings Technical SpecificationsSmart Setback Recovery via DIP switch #6 Equipment Protection TimersOver−Temperature Protection Maintenance ReminderCooling Demands Thermostat Output TableHeating Demands 51M35 Merit Series 51M35 Merit Series Thermostat505049M 5/1/05 Heat − Using the Heat Mode Cool − Using the Cool Mode Enabling and Disabling Heat ModeHeat/Cool Mode Disabled Turn Heat ON/OFFHold − Using Temperature Hold Modes 1st press Removing and Installing Thermostat I0i451M35 Terminal Designations Thermostat Outputs Gas Heat, Auto FanGas Heat, Continuous Fan Electric Heat, Auto Fan51M34 Merit Series 51M34 Merit Series Thermostat505048M 5/1/05 51M34 Series 5/2 I036 FAN OFF I0i4 51M34 Terminal Designations Heat Demand Cool Demand No Demand 51M39 Merit Series 51M39 Merit Series ThermostatI026 530 Heat/Cool Mode Disabled Cooling DemandI030 Auto − Using the Autochangeover Mode Copy a Programmed Day to An other Day Displaying Outside Temperature Check Outside TemperatureFilter Maintenance Indicators Service Indicator FlashingDefault Program Settings Time & Temp Indoor Temperature Measurement Range Outdoor Temperature Measurement RangeAutochangeover Deadband Selection via DIP switch #7 51M39 Terminal DesignationsThermal-mechanical switch opens W1 and W2 at 93F+/−6F Page 51M42 Merit Series Thermostat 51M42 Merit Series−Day Programmable Thermostat 505069M 07/05 Large Heat Heating Demand FAN Auto MID Reminder Settings Display Using Fan on I026 Default Program Settings − Time & Temp With Electric Backup no outdoor sensorTechnical Specifications 51M42 Terminal Designations 51M38 Merit Series 51M38 Merit Series ThermostatY/TIME button 51M38 Series 5/2 Hold − Using Temperature Hold Modes Repeat steps a and B for as many days as you Settings Thermostat Output Table 51M38 Terminal Designations

51M37 specifications

Lennox International Inc, a prominent player in the heating, ventilation, and air conditioning (HVAC) market, has made significant strides in innovation and technology in recent years. Among its notable offerings is the Lennox 51M37, a well-engineered component designed to enhance HVAC efficiency and reliability.

The 51M37 is primarily known for its advanced motor technology, incorporating ECM (Electronically Commutated Motor) design, which significantly reduces energy consumption compared to traditional motor systems. This motor type is key to Lennox's commitment to sustainability, as it not only maintains optimal performance but also minimizes the carbon footprint associated with residential and commercial heating and cooling tasks.

A standout feature of the 51M37 is its intelligent control system, which allows for more precise management of airflow and temperature. This technology can adapt to specific environmental conditions and consumption patterns, optimizing performance and providing substantial cost savings on energy bills. The integration of smart technology aligns with modern demands for energy efficiency and control, making the 51M37 a vital component in achieving higher energy ratings for HVAC systems.

In terms of compatibility, the 51M37 is engineered to work seamlessly with a variety of Lennox heating and cooling units, ensuring versatility for both new installations and retrofits. This compatibility enhances system integration, resulting in improved overall performance.

The construction of the 51M37 emphasizes durability and reliability, featuring high-quality materials that withstand the challenges of constant operation. Its robust design is perfect for diverse environments, ensuring that it functions reliably in both residential settings and commercial applications.

Another characteristic worth noting is the user-friendly installation process, allowing HVAC technicians to install the 51M37 with relative ease. This not only reduces labor costs but also ensures that the system can commence operation quickly without extensive downtime.

Overall, Lennox International's 51M37 embodies innovation, efficiency, and reliability in HVAC technology. With its advanced ECM motor, intelligent controls, and durable construction, it stands as a prime example of how modern HVAC solutions can lead to enhanced performance and energy savings. As the industry continues to evolve, products like the 51M37 will play a critical role in shaping the future of heating and cooling, aligning with sustainability goals and meeting the needs of consumers.