Raypak 122-322 installation instructions Support of Vent Stack, Vent Terminal Location General

Page 26

Support of Vent Stack

The weight of the vent stack or chimney must not rest on the heater vent connection. Support must be provided in compliance with applicable codes. The vent should also be supported to maintain proper clearances from combustible materials.

Use insulated vent pipe spacers where the vent passes through combustible roofs and walls.

Vent Terminal Location

NOTICE:

General

During winter months check the vent cap and make sure no blockage occurs from build up of snow. Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition.

Give special attention to the location of the vent termination to avoid possibility of property damage or personal injury.

a)Gases may form a white vapor plume in winter. The plume could obstruct a window view if the termination is installed in close proximity to windows.

b)Prevailing winds could cause freezing of condensate and water/ice build-up on building, plants or roof.

c)The bottom of the vent terminal and the air intake shall be located at least 12 in. above grade.

d)Un-insulated single-wall metal vent pipe shall not be used outdoors on cold climates for venting gas utilization equip- ment.

e)Through-the-wall vents for Category II and IV appliances and non-categorized condensing appliances shall not termi- nate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment. Where local experience indicates that condensate is a problem with Category I and III appliances, this provision shall also apply.

f)Locate and guard vent termination to prevent accidental contact by people or pets.

g)DO NOT terminate vent in window well, stairwell, alcove, courtyard or other recessed area, unless previously approved by local authority.

h)DO NOT terminate above any door, window, or gravity air intake. Condensate can freeze, causing ice formations.

i)Locate or guard vent to prevent condensate from damaging exterior finishes. Use a 2’ x 2’ rust resistant sheet metal backing plate against brick or masonry surfaces.

j)DO NOT extend exposed vent pipe outside of building. Condensate could freeze and block vent pipe.

US Installations - Refer to latest edition of NFGC

Vent termination requirements are as follows:

a)Vent must terminate at least four (4) feet below, four (4) feet horizontally, or one (1) foot above any door, window or gravity air inlet to the building.

b)The vent must not be less than seven (7) feet above grade when located adjacent to public walkways.

c)Terminate vent at least three (3) feet above any forced air inlet located within ten (10) feet.

d)Vent must terminate at least four (4) feet horizontally, and in no case above or below unless four (4) feet horizontal distance is maintained, from electric meters, gas meters, regulators, and relief equipment.

e)Terminate vent at least six (6) feet away from adjacent walls.

f)DO NOT terminate vent closer than five (5) feet below roof overhang.

g)The vent terminal of a direct vent appliance with an input over 50,000 Btu per hour shall require a 12-inch vent terminal clearance.

h)Terminate vent at least one (1) foot above grade, including normal snow line.

i)Multiple direct vent installations require a four (4) foot clearance between vent caps.

26

Image 26
Contents Operating Installation Instructions Table of Contents Page Section a Before Installing the Heater Product ReceiptModel Identification Ratings and CertificationsHI Delta Component Location General Information Equipment Base Section B Heater InstallationInstallationcodes Models Heater Side 122-322Heater Model OutdoorinstallationsOutdoor Installation Minimum Clearances Heater Side 120-322Direct Combustion AIR Section C Combustion and Ventilation AIRCombustion and Ventilation AIR Indoor Units Page Section D Water Piping General LOW Temperature SystemTemperature & Pressure Gauge Reliefvalve PipingSection E Hydronic Heating Piping Page Section F Domestic HOT Water Piping Table F-1 Domestic Water Heater Flowrate RequirementsSingle Heater Domestic HOT Water with ONE Storage Tank Winterizingyou Heater Section G Pool HeatingAutomatic Chlorinators and Chemicalfeeders Pooland SPA Water ChemistryGAS Supply Pressure Section H GAS Supply ConnectionsGAS Supply Connection GAS Pressure Regulator Check Power Source Section I Electrical Power ConnectionsCheck the Power Source Surge ProtectionField Wiring Connection Making the Electrical ConnectionsElectrical Connections Domestic HOT Water ShockhazardSection J Venting Connections Definition ofAppliance CategoriesTable J-1 Support of Vent Stack Vent Terminal Location GeneralVenting Installation Tips Venting ConfigurationsSection J-1 Natural Draft Vertical Venting Category Natural Draft VerticalventNatural Draft Vertical Venting System Installation Natural Draft Vertical Vent TerminationPage Section J-2 HORIZONTALTHRU-WALLVENTING Category III TableHorizontal Thru-wall Direct Vent Termination Section J-3 Direct Vent HORIZONTALTHRU-WALLVENTING TableHorizontal Thru-wall Direct Vent Termination Direct Vent Verticalventing TableVertical Direct Vent System Installation Vertical Direct Vent TerminationSection J-5 Section K Controls Ignition Control Module Ignitionmodule High Limit Manual ResetManual Reset High Limit Flow Switch Operating ControlLOW Water CUT OFF Optional LOW Water CUT-OFFWire Diagram Models Section L General Safety Precautions TIME/TEMPERATURE Relationships in ScaldsSection M PRE-START-UP Preparation for START-UP Section N Initial START-UPTools Needed Turn Off Main Gas ValveSTART-UP Your Hi Delta is tunedSection O Post START-UP Check Section P Operation Toturn OffgastoapplianceSection Q Maintenance Suggested Minimum Maintenance ScheduleAppendix a InsidecombustionaircontaminationFig # Heat Exchanger Detail Page Page Page Corporate Headquarters
Related manuals
Manual 44 pages 22.92 Kb

122-322 specifications

Raypak 122-322 is a cutting-edge pool and spa heater designed for optimal performance and efficiency. Known for its robust construction and reliable heating capabilities, this heater has become a preferred choice among pool owners.

One of the standout features of the Raypak 122-322 is its advanced copper fin tube heat exchanger. This innovative technology enhances the heater's efficiency by maximizing heat transfer while minimizing energy consumption. By efficiently circulating the water through the heat exchanger, the Raypak 122-322 quickly raises the temperature, allowing for an enjoyable swimming experience regardless of the weather.

The heater is equipped with a digital control system that allows for precise temperature adjustments. This user-friendly interface makes it easy to set and maintain the desired water temperature, promoting user convenience. The digital controls also provide diagnostic features, which simplify troubleshooting and maintenance, ensuring the heater operates smoothly for years to come.

Safety is a crucial aspect of the Raypak 122-322. It comes with a series of safety features, including a flame rollout switch, high limit switch, and a pressure switch that ensures the unit operates safely under various conditions. This focus on safety provides peace of mind for users, knowing that their heating system is designed with protective measures in place.

The Raypak 122-322 is environmentally friendly, designed to use less energy compared to conventional heating systems. Its efficient performance not only reduces operational costs but also lessens the overall environmental impact, making it a responsible choice for conscious consumers.

With a compact design, the Raypak 122-322 can fit easily into various installation spaces, making it versatile for numerous residential or commercial settings. Additionally, the unit is built with durable materials resistant to corrosion and weather conditions, ensuring longevity and minimal maintenance requirements.

Overall, the Raypak 122-322 stands out in the market due to its advanced features, safety mechanisms, energy efficiency, and ease of use. It exemplifies a perfect blend of innovation and reliability, making it an exceptional option for anyone looking to enhance their pool or spa experience.