Voltage:
Voltage at motor must be not more than 10% above or below motor name- plate rated voltage or motor may overheat, causing overload tripping and re- duced component life. If voltage is less than 90% or more than 110% of rated voltage when motor is running at full load, consult power company.
Values given in tables below are for PUMP MOTOR ONLY. If addi-
tional spa accessories are installed on pump motor circuit (heater, blower, etc.), include their amperage draw when figuring wire and circuit breaker sizes.
TABLE I - RECOMMENDED CIRCUIT BREAKER SIZE AND WIRING DATA FOR 60 Hz MOTORS
|
|
|
| Branch |
| AWG (mm2) Wire Gauge Size |
| ||
|
|
| Full | Circuit |
| Dist in Ft. (M) - Service to Motor |
| ||
Model | Motor |
| Load | Breaker | Temp | ||||
No. | HP | Volts | Amps | Amp Rating | Deg. C. | ||||
|
|
|
|
|
|
|
|
| |
Single Speed Pumps: |
|
|
|
|
|
|
|
| |
1/2 | 115 | 7.0 | 15 | 14 | (2.0) | 12 (3.0) | 10 (5.5) | 75 | |
3/4 | 115 | 9.0 | 15 | 14 | (2.0) | 14 (2.0) | 10 (5.5) | 75 | |
1 | 115 | 12.0 | 15 | 14 | (2.0) | 10 (5.5) | 8 (8.4) | 75 | |
|
|
|
|
|
|
|
|
| |
115/230 | 16.4/8.2 | 25/15 | 10/14 (5.5/2.0) | 8/14 (8.4/2.0) | 6/12 (14/3.0) | 75 | |||
115/230 | 14.4/7.2 | 20/15 | 12/14 (3.02.0) | 8/14 (8.4/2.0) | 6/14 (14/2.0) | 75 | |||
|
|
|
|
|
|
|
|
| |
3/4 | 230 | 4.8 | 15 | 14 (2.0) | 14 (2.0) | 14 (2.0) | 75 | ||
1 | 230 | 6.1 | 15 | 14 (2.0) | 14 (2.0) | 14 (2.0) | 75 | ||
|
|
|
|
|
|
|
|
| |
Two Speed Pumps: |
|
|
|
|
|
|
|
| |
115 | 9.0/2.7 | 15 | 14 (2.0) | 12 (3.0) | 10 (5.5) | 75 | |||
115 | 9.0/2.7 | 15 | 14 (2.0) | 12 (3.0) | 10 (5.5) | 75 | |||
115 | 11.7/3.4 | 15 | 14 (2.0) | 10 (5.5) | 8 (8.4) | 75 | |||
115 | 12.0/3.3 | 15 | 14 (2.0) | 10 (5.5) | 8 (8.4) | 75 | |||
11¼2 - 1/6 115 | 16.6/3.6 | 25 | 10 (5.5) | 8 (8.4) | 6 (14) | 75 | |||
|
|
|
|
|
|
|
|
| |
230 | 4.7/1.4 | 15 | 14 (2.0) | 14 (2.0) | 14 (2.0) | 75 | |||
230 | 6.3/1.8 | 15 | 14 (2.0) | 14 (2.0) | 14 (2.0) | 75 | |||
11¼2 - 1/6 230 | 8.1/1.7 | 15 | 14 (2.0) | 14 (2.0) | 12 (3.0) | 75 | |||
|
|
|
|
|
|
|
|
| |
220 | 5.4/1.4 | 15 | 14 (2.0) | 14 (2.0) | 14 (2.0) | 75 | |||
220 | 6.3/1.8 | 15 | 14 (2.0) | 14 (2.0) | 14 (2.0) | 75 | |||
|
|
|
|
|
|
|
|
|
|
Remote Switching For 2-Speed Pumps
Ground (Green)
L2 | Common |
|
|
|
|
| |
B |
|
|
|
A | Lo | Lo |
|
|
|
| |
L1 | Hi | Hi |
|
|
| Circuit | |
| Timer Motor | Remote | |
| SPDT | Protector | |
| Supply | ||
|
|
|
Switch
Timer (optional)
Low Speed Only
Minimum switch and timer amp rating must equal Branch Fuse Rating given in "Recommended Circuit Breaker Size and Wiring Data" table.