Johnson Controls PC090 THRU 240, PD 180 THRU 240 dimensions Cooling Charging Curves

Page 27

430645-YIM-D-0610

 

 

 

 

 

 

 

 

 

 

Cooling Charging Curves

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PC090

 

 

 

 

 

 

 

 

 

 

 

 

 

(psi)

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

130

140

150

160

170

 

 

 

Suction Pressure (psi)

Outdoor Air Entering Condenser (F)

180

1.Make sure that both condenser fans are running when charging.

2.This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been adjusted in the field, the charging chart may no longer apply.

Figure 11: PC090 Charging Chart

Cooling Charging Curves

PC120

Discharge Pressure (psi)

600

 

 

 

 

 

 

 

 

 

 

 

 

 

(F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

105°

 

Condenser

500

 

 

 

 

 

 

 

 

 

 

 

115°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering

400

 

 

 

 

 

 

 

 

 

 

 

85°

 

 

 

 

 

 

 

 

 

 

 

 

95°

 

 

300

 

 

 

 

 

 

 

 

 

 

 

75°

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

65°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

130

140

150

160

170

180

Suction Pressure (psi)

1.Make sure that both condenser fans are running when charging.

2.This chart is applicable to unit with the TXV’s left to the factory setting. If the TXV’s have been adjusted in the field, the charging chart may no longer apply.

Figure 12: PC120 Charging Chart

Johnson Controls Unitary Products

27

Image 27
Contents 410A General NomenclatureInspection Safety ConsiderationsRenewal Parts Agency ApprovalsPC090 240 and PD180 240 Physical Data Physical DataInstallation LimitationsLocation Shipping Operating Corner Weights & Center of GravityClearances RiggingMinimum Clearances Clearance Description Distance in Inches Compressors Power WiringControl Wiring PhasingFLA Electrical DataTake Adequate Precautions Refrigerant MainsLine Sizing Start Installation Thermostat Single Stage Cooling TWO Stage Heating NC120 240 Liquid Line Solenoid Wiring YIM-D-0610 Model Model Start-Up Piping And Electrical ConnectionsCrankcase Heaters Operation Sequence of OperationCooling Sequence Of Operation Dual Stage Heat Pump 4 pipe PD180-240 Dual Stage Heat Pump PC120-240Heating Sequence of Operation Fan Orientation, Control Box End Defrost OperationUnit Control Board PD180 thru 240 Unit Control Board Flash CodesNormal Maintenance TroubleshootingUnit Control Board Option Setup Option Byte SetupCooling Troubleshooting Guide If none of the above correct the error, replace the UCB Johnson Controls Unitary Products Cooling Charging Curves Cooling Charging Curves PC240 Typical PC090 Heat Pump Wiring Diagram Typical Wiring DiagramsTypical PC120 Heat Pump Wiring Diagram Typical PC180 240 Heat Pump Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK

PC090 THRU 240, PD 180 THRU 240 specifications

Johnson Controls has long been a leader in the HVAC and building efficiency industry, and the Johnson Controls PC090 THRU 240 and PD 180 THRU 240 series of commercial rooftop units exemplify their commitment to innovation and energy efficiency. These units are designed to provide optimal performance for a wide range of commercial applications, ensuring comfortable indoor climates while maintaining energy savings.

One of the standout features of the Johnson Controls PC and PD series is their advanced cooling and heating capabilities. Both series can operate efficiently across a varied range of capacities, typically from 90,000 to 240,000 BTU/h for the PC series and 180,000 to 240,000 BTU/h for the PD series. This versatility allows users to select the most appropriate unit size for their specific needs, optimizing performance without wasting energy.

The technology behind these rooftop units includes advanced inverter-driven compressors that enable variable-speed operation. This feature allows for precise temperature control, resulting in enhanced comfort and reduced energy usage. The units also integrate smart controls that enable easy monitoring and management, ensuring that the HVAC system can adapt to changes in occupancy or external weather conditions.

Another notable characteristic of the Johnson Controls rooftop units is their robust construction and reliability. Designed for outdoor use, these units can withstand harsh weather conditions while maintaining operational efficiency. They are equipped with corrosion-resistant materials and protective enclosures to prolong the life of the equipment.

The units are also engineered with eco-friendliness in mind, utilizing refrigerants with low global warming potential to minimize their environmental impact. Furthermore, their energy-efficient designs often qualify for various energy incentives, providing businesses an additional return on investment.

Ease of installation and maintenance is another hallmark of the PC and PD series. With a modular design, these units can be easily transported and installed. Maintenance tasks are simplified, allowing facility management teams to perform regular service checks efficiently and effectively.

Overall, the Johnson Controls PC090 THRU 240 and PD 180 THRU 240 series stand out in the commercial HVAC market due to their flexibility, advanced technology, and dedication to energy efficiency and environmental responsibility. These units not only meet modern energy codes but also contribute to a sustainable future with their innovative features and reliable performance.