Johnson Controls PD 180 THRU 240 Refrigerant Mains, Take Adequate Precautions, Line Sizing

Page 10

430645-YIM-D-0610

Refrigerant Mains

Take Adequate Precautions

This Split-System (Air Condensing / Heat Pump / Air Handling) unit is one component of an entire system. As such it requires specific application considerations with regard to the rest of the system (air handling unit, duct design, condensing unit, refrigerant piping and control scheme).

Failure to properly apply this equipment with the rest of the system may result in premature failure and/or reduced performance / increased costs. Warranty coverage specifically excludes failures due to improper application and Unitary Products specifically disclaims any liability resulting from improper application.

Please refer to the equipment Technical Guide, Installation Manual and the piping applications bulletin 247077 or call the applications department for Unitary Products @ 1-877-UPG-SERV for guidance.

Line Sizing

When sizing refrigerant pipe for a split-system air conditioner, check the following:

1.Suction line pressure drop due to friction.

2.Liquid line pressure drop due to friction.

3.Suction line velocity for oil return.

4.Liquid line pressure drop due to vertical rise. For certain piping arrangements, different sizes of suction line pipe may have to be used. The velocity of the refrigerant vapor must always be great enough to carry the oil back to the compressor.

5.Evaporator Located Below Condenser - On a split system where the evaporator blower is located below the condenser, the suction line must be sized for both pressure drop and for oil return.

6.Condenser Located Below Evaporator - When the condenser is located below the evaporator blower, the liquid line must be designed for the pressure drop due to both friction loss and vertical rise. If the pressure drop due to vertical rise and friction exceeds 60 psi, some refrigerant will flash before it reaches the thermal expansion valve.

Flash gas:

1.Increases the liquid line pressure loss due to friction that in turn causes further flashing.

2.Reduces the capacity of the refrigerant control device which starves the evaporator.

3.Erodes the seat of the refrigerant control device.

4.Causes erratic control of the refrigerant entering the evaporator.

Many service problems can be avoided by taking adequate precautions to provide an internally clean and dry system and by using procedures and materials that conform to established standards.

Use hard drawn copper tubing where no appreciable amount of bending around pipes or other obstructions is necessary. If soft copper is used, care should be taken to avoid sharp bends that may cause a restriction. Pack fiberglass insulation and a sealing material such as permagum around refrigerant lines where they penetrate a wall to reduce vibrations and to retain some flexibility.

Support all tubing at minimum intervals with suitable hangers, brackets or clamps.

Braze all copper-to-copper joints with Silfos-5 or equivalent brazing material. Do not use soft solder. Insulate all suction lines with a minimum of 1/2" ARMAFLEX or equivalent that meets local codes. Liquid lines exposed to direct sunlight and/ or high temperatures must also be insulated. Never solder suction and liquid lines together. They can be taped together for convenience and support purposes, but they must be completely insulated from each other.

The liquid and suction service ports on the condenser section permit leak testing, evacuation, and partial charging of the field piping and the evaporator without disturbing refrigerant stored in the condenser during initial installation.

Before beginning installation of the main lines, be sure that the evaporator section has not developed a leak in transit. Check pressure at the Schrader valve located on the header of each coil. If pressure still exists in the system, it can be assumed to be leak free. If pressure DOES NOT exist the section will need to be repaired before evacuation and charging is performed.

A bi-flow solid core filter-drier MUST be field-installed in the liquid line of every system to prevent dirt and moisture from damaging the system. Properly sized filter-driers are shipped with each condensing section.

NOTE: Installing a filter-drier does not eliminate the need for the proper evacuation of a system before it is charged.

A field-installed moisture indicating sight-glass should be installed in the liquid line(s) between the filter-drier and the evaporator coil. The moisture indicating sight-glass can be used to check for excess moisture in the system.

Both condenser and evaporator sections have copper sealing disks brazed over the end of liquid and suction connections. The temperature required to make or break a brazed joint is high enough to cause oxidation of the copper unless an inert atmosphere is provided.

NOTE: Dry nitrogen should flow through the system at all times when heat is being applied and until the joint has cooled. The flow of nitrogen will prevent oxidation of the copper lines during installation.

10

Johnson Controls Unitary Products

Image 10
Contents 410A Nomenclature GeneralAgency Approvals Safety ConsiderationsRenewal Parts InspectionPhysical Data PC090 240 and PD180 240 Physical DataLimitations InstallationLocation Corner Weights & Center of Gravity Shipping OperatingRigging ClearancesMinimum Clearances Clearance Description Distance in Inches Phasing Power WiringControl Wiring CompressorsElectrical Data FLARefrigerant Mains Take Adequate PrecautionsLine Sizing Start Installation Thermostat Single Stage Cooling TWO Stage Heating NC120 240 Liquid Line Solenoid Wiring YIM-D-0610 Model Model Piping And Electrical Connections Start-UpCrankcase Heaters Sequence of Operation OperationCooling Sequence Of Operation Dual Stage Heat Pump PC120-240 Dual Stage Heat Pump 4 pipe PD180-240Heating Sequence of Operation Defrost Operation Fan Orientation, Control Box EndPD180 thru 240 Unit Control Board Flash Codes Unit Control BoardOption Byte Setup TroubleshootingUnit Control Board Option Setup Normal MaintenanceCooling Troubleshooting Guide If none of the above correct the error, replace the UCB Johnson Controls Unitary Products Cooling Charging Curves Cooling Charging Curves PC240 Typical Wiring Diagrams Typical PC090 Heat Pump Wiring DiagramTypical PC120 Heat Pump Wiring Diagram Typical PC180 240 Heat Pump Wiring Diagram Johnson Controls Unitary Products York Drive Norman, OK

PC090 THRU 240, PD 180 THRU 240 specifications

Johnson Controls has long been a leader in the HVAC and building efficiency industry, and the Johnson Controls PC090 THRU 240 and PD 180 THRU 240 series of commercial rooftop units exemplify their commitment to innovation and energy efficiency. These units are designed to provide optimal performance for a wide range of commercial applications, ensuring comfortable indoor climates while maintaining energy savings.

One of the standout features of the Johnson Controls PC and PD series is their advanced cooling and heating capabilities. Both series can operate efficiently across a varied range of capacities, typically from 90,000 to 240,000 BTU/h for the PC series and 180,000 to 240,000 BTU/h for the PD series. This versatility allows users to select the most appropriate unit size for their specific needs, optimizing performance without wasting energy.

The technology behind these rooftop units includes advanced inverter-driven compressors that enable variable-speed operation. This feature allows for precise temperature control, resulting in enhanced comfort and reduced energy usage. The units also integrate smart controls that enable easy monitoring and management, ensuring that the HVAC system can adapt to changes in occupancy or external weather conditions.

Another notable characteristic of the Johnson Controls rooftop units is their robust construction and reliability. Designed for outdoor use, these units can withstand harsh weather conditions while maintaining operational efficiency. They are equipped with corrosion-resistant materials and protective enclosures to prolong the life of the equipment.

The units are also engineered with eco-friendliness in mind, utilizing refrigerants with low global warming potential to minimize their environmental impact. Furthermore, their energy-efficient designs often qualify for various energy incentives, providing businesses an additional return on investment.

Ease of installation and maintenance is another hallmark of the PC and PD series. With a modular design, these units can be easily transported and installed. Maintenance tasks are simplified, allowing facility management teams to perform regular service checks efficiently and effectively.

Overall, the Johnson Controls PC090 THRU 240 and PD 180 THRU 240 series stand out in the commercial HVAC market due to their flexibility, advanced technology, and dedication to energy efficiency and environmental responsibility. These units not only meet modern energy codes but also contribute to a sustainable future with their innovative features and reliable performance.