Samsung APC3240C, UPC3240C installation manual Electrical Work

Page 27

ELECTRICAL WORK

The electrical work should be performed by a specialist qualified for the work.

Use the three phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit(separately purchased by the user).

Avoid octopus-type wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circuit.

Be sure to install circuit breaker (separately purchased by the user).

Be sure to connect the grounding wire.

Electric power spec

Power

 

Single phase 208-230V~, 60Hz

 

 

 

 

Sub switch

 

30A

 

 

 

 

Fuse

 

30A

 

 

 

 

Electric wire

Below 20m(65

85 ft)

3.5mm2

Below 50m(164 161 ft)

5.5mm2

 

Allowable voltage

 

187V~253V

Indoor and Outdoor Connection Wiring

When connecting the wiring harness between the indoor and outdoor unit, align the outdoor side and the indoor side with the terminal board No.

Connect the connection wire (1, 2, 3) and power cable (L1, L2) to terminals through the conduit hole

as shown in the diagram.

When the wiring harnesses of the indoor and outdoor unit are not properly connected, it may cause trouble. Be careful not to allow the indoor and outdoor wirings and power lines to get in contact with the service valve of the refrigerant system or to the pipe without an insulator.

 

INDOOR SIDE

 

 

 

 

Terminal board

OUTDOOR SIDE

Cover terminal

5

 

Terminal board

 

Earth

Earth

 

 

 

4

 

 

 

 

 

 

 

3

 

 

L1

L2

 

 

 

 

Earth

 

2

 

 

 

Cover

 

 

 

 

 

 

 

 

 

connector

1

 

 

 

 

Holder

 

 

Indoor/outdoor unit

 

 

Electric panel board

connection wire(1mm2)

Electric panel board

clamp

 

 

 

 

 

 

 

 

Terminal block

 

 

 

 

 

Electrical Wiring

1.Connect it to the terminal board L1 and L2 for power supply to the outdoor unit.

In so doing, peel off the end of the power cord by about 5mm( 163 "), and press the cord to the ring terminal for hooking.

2.Perform the power grounding using the screw for exclusive use with the outdoor unit.

ENGLISH

E-27

Image 27
Contents Climatiseur Monobloc DE Type Split Refroidissement APC3240C UPC3240C Split Type Packaged AIR Conditioner CoolSafety Precautions Contents Indoor Unit View of the UnitOutdoor Unit Remote Control Buttons and Display Getting Started Inserting the Remote Control Batteries Using the Control Panel on the Indoor UnitUsing the Remote Control Selecting the Automatic Operating Mode Cooling Your Room Removing Excess Humidity Changing the Room Temperature Quickly Selecting the Long Function Airing Your Room Adjusting the Air Flow Direction Horizontally Adjusting the Air Flow Direction VerticallyTo Cancel the On Timer Setting the On TimerTo Cancel the Off Timer Setting the Off TimerTo Cancel the Sleep Timer Setting the Sleep TimerTopic Recommendation Operating RecommendationsIf the air conditioner is used at... Then Temperature and Humidity RangesCleaning Your Air Conditioner AUTO, Cool Solving Common ProblemsModel Technical SpecificationsInstallation Manual Absolute Checkpoints Outdoor Unit Indoor UnitElectrical Work Installation Procedures Installation MethodEnglish Flare Processing Connection of Refrigerant PipingConnecting the pipe Drilling a Hole in the WallDrain Hose AIR Purge Refrigerant Charging Check Check and Test OperationTest Operation Electronics