Auxiliary controls on your Zoneline.
External Fan (Obtained locally)
When connected, an auxiliary or external fan can be controlled with the indoor fan motor on the Zoneline. Connections provide 24 V AC to energize a remote relay, turning on the external fan.
External Fan
Central Desk Control
When connected, the unit can be turned ON or OFF with a switch located at the Central Control Panel. A separate wire pair must be run from each separate controlling switch to each individual Zoneline.
Central Desk Control
Care and Cleaning
Troubleshooting Tips
Consumer Support
Remote Thermostat
When connected, the unit will be controlled by a remote thermostat.
NOTE: The number 4 dip switch must be in the enabled (UP) position to activate the remote thermostat. (See the installation instructions supplied with the remote thermostat.)
IMPORTANT:
The Zoneline thermostat connections provide 24 V AC only.
If using a digital/electronic wall thermostat, you must set it to the 24 V AC setting.
See the Installation Instructions for the wall thermostat.
Red - 24 V AC only
Green - Low Speed Fan
Green - High Speed Fan
Black - Solenoid
Yellow - Compressor
White - Heater
Common - Ground
CAUTION:
Damage to a wall thermostat or to the Zoneline electronics can result from improper connections. Special care must be used in connecting the wires. No line voltage connections should be made to any circuit. Isolate all wires in building from line voltage.