Slant/Fin XL-2000 dimensions Burner DATA-CARLIN Burners for Packaged Boilers only, Delavan

Page 11

XL-2000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOZZLES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OIL PUMP

 

“A”

 

 

APPROXIMATE

 

 

SHUTTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATE

 

 

 

 

ANGLE

 

 

 

 

 

PRESSURE

 

APPROXIMATE

 

 

AIR BAND

 

 

NON-

 

BOILER

 

 

CARLIN BURNER

 

 

NO. 2 OIL

 

 

SIZE

 

AND

 

 

 

 

 

SETTING

 

HEAD SETTING

 

 

OPENING %

 

 

ADJUSTABLE

 

MODEL

 

 

MODEL (2) (3)

 

 

(GPH)

 

 

(GPH)

 

TYPE

 

MFR.

 

 

 

(PSIG)

 

NO.

 

 

(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XL-20

 

99-FRD

 

0.65

0.65

 

70° A

 

DELAVAN

100

 

0

 

50

 

 

Closed

 

 

 

71399-00F-XL-20

 

 

 

0.65

 

70° W

 

DELAVAN

100

 

0

 

50

 

 

Closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XL-30

 

99-FRD

 

1.00

1.00

 

70° A

 

DELAVAN

100

 

2

 

80

 

 

Closed

 

 

 

71399-00F-XL-30

 

1.15

1.00

 

70° A

 

DELAVAN

130

 

3

 

90

 

 

Closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XL-40

 

99-FRD

 

1.35

1.35

 

60° W

 

DELAVAN

100

 

4

 

50

 

 

Closed

 

 

 

71399-00F-XL-40

 

1.55

1.35

 

60° W

 

DELAVAN

130

 

4

 

65

 

 

Closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XL-50

 

99-FRD

 

1.80

1.75

 

60° B

 

DELAVAN

105

 

4

 

20

 

 

Open

 

 

 

71399-00F-XL-50

 

2.00

1.75

 

60° B

 

DELAVAN

130

 

5

 

40

 

 

Open

NOTES:

(1)Single slotted air band for XL-20 and XL-30, double slotted air band for XL-40 and XL-50.

(2)See “PRECAUTIONS BEFORE STARTING OIL BURNERS” and “START-UP” on page 7 and burner figures on this page.

(3)All burner models shown are single stage.

Image 11
Contents XL-2000 XL-2000 Ratings and DimensionsAIR Supply and Ventilation see Nfpa 31, latest edi- tion Chimney CONNECTOR-18Minimum Clearance DOORS. see Action NoneFrom OUTDOORS. see Requires AIR from OUTXL-2000 II. AIR Control Systems Installing Controls and Accessories on Boiler UnitsCirculating System Domestic HOT Water Installing the BurnerWiring the Boiler Precautions Before Starting OIL BurnerCare and Maintenance Cleaning and Filling a NEW Water BoilerIII. OIL Burner IV. General MaintenanceDo not USE Ethylene Glycol Because IT is Toxic XL-2000 Delavan Burner DATA-CARLIN Burners for Packaged Boilers onlyAFG Burner DATA-BECKETT Burners for Packaged Boilers onlyHago NO. †Burner Data Riello Turbulator SettingTurbulator Settings Riello 40 Series Setting the AIR Adjustment PlateSLANT/FIN CORPORATION, Greenvale, N.Y Phone 516