CAUTION: When flushing float type low water cut-off control, hot water and steam will flow out the blow down valve. Blow down valve is illus- trated below.

A.SPECIAL FLUSHING INSTRUCTIONS For new boiler installed in old system.

Installation of new boiler may break loose a heavy accumulation of sediment and scale from old piping and radiators. It is extremely important to blow down your McDonnell cut-off more frequently the first week.

First week — 3 times

Thereafter — at least once a week.

B.As boiler water circulates through the float chamber, dirt or other sediment may be deposited. This chamber is extra deep. But the only sure way to keep any accumulation from interfering with float action is to "blow down", or flush out, the control once a week. Do it while boiler is in operation. First note water level in gauge glass. Open blow-off valve at bottom of control; water will pour out, flush- ing away sediment. Drain until water is clear — about a pail —then close valve. If level in gauge glass has dropped, add water to boiler to restore level.

C.NOTE: Opening blow-off valve checks cut-off operation too. As float drops with falling water level, burner will stop. After burner is off and normal operating conditions restored, burner will resume firing.

D.Be sure that it is the low water cut-off and not the room thermostat, pressure cut-out, or other control that has shut off the burner.

PRESSURE CONTROL CHECK-OUT

A.Check burner to be certain it is ready for firing. DO NOT FIRE into an empty boiler.

B.Set thermostat high enough for boiler to make steam. Set the pres sure control down to its lowest setting. As the boiler starts to pro- duce steam, the steam pressure will start to build. The burner will shut off when the steam pressure exceeds the pressure setting (plus differential if control has this feature).

C.Adjust the pressure control to a higher setting. The higher setting should be above the steam pressure in the boiler. This should turn the burner back on.

D.Reset the pressure control as needed for the system. The pressure control should be checked at least twice a year.

REPLACEMENT OF STEAM BOILERS

Anytime an older steam boiler is removed from the heating system and replaced with a new boiler, there are certain conditions that have to be examined on the heating system.

A.Steam systems have a tendency to develop scale inside the wet return lines and the boiler. The older the system the greater the accumulation of scale that can exist inside the piping. Therefore, it is necessary when replacing a steam boiler to check the piping for blockage or restrictions. Clean or replace the piping as required. (See special flushing instructions on this page.)

B.Replace all buried wet return lines.

C.All equipment (air vents, radiation equipment, etc.) in the steam heating system should be checked for proper operation. All piping should be checked for proper pitch.

D.It is good engineering practice to repack or tighten the packing nuts on all valves in the heating system.

Image 10
Contents Intrepid Intrepid Minimum Clearance Chimney CONNECTOR-18Boiler Location Chimney RequirementsRequires AIR from OUT Intrepid Piping Installing Controls Accessories on Boiler UnitsCleaning Piping System Piping for Steam BoilersWiring the Boiler Installing the BurnerOIL Supply Piping Vent Piping and Draft Regulator Cleaning and Filling a NEW Water BoilerIII. Safety Check for Control System START-UPCOMBUSTION Test Instruments Must be UsedBlowing OFF a LOW Pressure Steam Boiler Cleaning and Filling a NEW Steam BoilerLOW Water CUT-OFF CHECK-OUT Replacement of Steam Boilers Pressure Control CHECK-OUTIntrepid Intrepid Wiring for Packaged Steam Boiler Steam Boiler Wiring for Riello Burner and McDONELL Intrepid Burner Data Beckett CF-375 Burners for Packaged Boilers only DelevanIntrepid Turbulator Settings Riello 40 Series Burner Data RielloIntrepid Intrepid II. Providing Protection for Freezing IV. General MaintenanceIII. OIL Burner Page Page SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

Oil-fired Boiler specifications

The Slant/Fin Oil-fired Boiler is renowned for its reliable performance and efficiency in residential and commercial heating applications. Designed to deliver optimal heating while minimizing fuel costs, this boiler is an excellent choice for those looking to maximize comfort in their living spaces.

One of the main features of the Slant/Fin Oil-fired Boiler is its robust construction, which ensures longevity and resilience against harsh conditions. Crafted from high-quality materials, the boiler boasts a cast iron heat exchanger that provides superior heat retention and distribution. This construction not only contributes to its durability but also enhances its overall energy efficiency.

A standout characteristic of the Slant/Fin Oil-fired Boiler is its advanced burner technology. The unit incorporates a high-efficiency oil burner that ensures complete combustion of the fuel. This upgrade leads to significant energy savings while producing low emissions, thereby making it an environmentally friendly heating solution. The burner is designed for quiet operation, which adds to the comfort of home environments.

The boiler is equipped with an innovative control system that allows users to easily monitor and adjust settings for optimal performance. This feature aids in maintaining a consistent temperature throughout the home, ensuring comfort during the coldest months. Additionally, the system offers diagnostic capabilities, making it easier to troubleshoot and maintain.

Another key characteristic of the Slant/Fin Oil-fired Boiler is its versatility in installation. The compact design allows for installation in a variety of spaces, including basements, utility rooms, and garages. This adaptability makes it a popular choice for homeowners looking to optimize their heating solutions without compromising on space.

Furthermore, Slant/Fin offers a variety of models within its oil-fired boiler range to cater to diverse heating needs. This range includes different output capacities to accommodate various home sizes. With a focus on user-friendly design, the boilers come with clear instructions and support for installation and maintenance.

In conclusion, the Slant/Fin Oil-fired Boiler stands out for its durability, efficiency, and advanced technologies. Its cast iron construction, high-efficiency oil burner, and innovative control systems combine to create a reliable heating solution. A perfect fit for both residential and commercial applications, this boiler ensures comfort and peace of mind, making it a preferred choice among homeowners seeking quality and performance in their heating systems.