Slant/Fin Oil-fired Boiler dimensions Requires AIR from OUT

Page 4

4

INTREPID

Any oil-fired boiler must have a steady draft* and an ample supply of combustion air at all times during firing. If air supply or chimney draft* is unreliable, CO2 and overfire draft* will change unpredictably.

DO NOT vent this boiler to the same chimney flue used by a fireplace or coal or wood burning furnace or boiler. The draft* produced by solid fueled devices varies tremendously between high fire and low fire:

In modern, weather stripped, energy-saving buildings or older buildings which have been modified similarly, natural infiltration may not supply enough air for combustion, particularly if other fuel burning appliances, exhaust fans or draft inducers are competing for the same air supply. Fireplaces, other solid fuel burning appliances and exhaust fans con- sume great quantities of air; if air supply is not ample, such an appliance will create a downdraft in the oil-fired boiler flue. This can create a haz- ardous condition. Flue gases can be sucked out of the chimney through

the vent regulator into the living space. DO NOT operate this boiler and a solid fuel burning appliance at the same time, unless the solid fuel burner is provided with its own outside air supply.

See Table 2, “Provisions for Combustion and Ventilation Air Supply” for determining need and method of providing air for combustion and ventilation.

If fly screen must be used over air supply openings, areas calculated should be doubled; the screen should be inspected and cleaned fre- quently to maintain free air flow.

Protect air openings against closure by snow, debris, etc. Openings such as doors or windows, if used, must be locked open.

* Draft is negative or suction pressure

TABLE 2: Provisions for Combustion and Ventilation Air Supply. See NFPA 31, latest edition for more detailed information.

 

 

 

 

 

 

 

 

 

 

Boiler Location

Air Supply

 

 

Action Required

 

 

2.1

Unconfined space

Is there sufficient air for combus-

 

 

NONE

 

 

 

 

tion by natural infiltration (see

 

 

 

 

 

 

 

NOTE (1), “Test...” below)?

 

 

 

 

 

 

 

 

 

 

 

 

 

2.2

Unconfined space

If there is NOT sufficient air for

 

 

Provide air from outdoors directly through a permanent outside

 

 

 

 

combustion by natural infiltration

 

 

wall opening or openings with a free open area of not less than

 

 

 

 

due to tight construction or other

 

 

1 sq. in. per 4000 Btu/hr of TOTAL input of ALL fuel burning

 

 

 

 

conditions, then it REQUIRES AIR

 

 

appliances in the building. See Note (1) and (3).

 

 

 

 

FROM OUTDOORS. SEE

 

 

 

 

 

 

 

“ACTION REQUIRED” column at

 

 

 

 

 

 

 

right. See Notes (1) and (2) below.

 

 

 

 

 

 

 

 

 

 

 

 

 

2.3

Confined space

If there is sufficient air for combus-

 

 

 

 

 

 

 

tion from within building but it

 

 

The confined space shall be provided with two permanent air

 

 

 

 

comes from outside of the

 

 

openings, one near the top of the enclosure and one near the

 

 

 

 

confined space. SEE “ACTION

 

 

bottom. EACH opening shall have a free air opening of not less

 

 

 

 

REQUIRED” column at right.

 

 

than 1 sq. in. per 1000 Btu/hr. of TOTAL input of ALL fuel burning

 

 

 

 

See Note (1) below.

 

 

appliances within the enclosure. The two openings shall freely

 

 

 

 

 

 

 

communicate with the interior areas of the building which in turn

 

 

 

 

 

 

 

would have to have adequate infiltration of air from outdoors.

 

 

 

 

 

 

 

See Notes (1, 3) and Figure 3a.

 

 

 

 

 

 

 

 

 

 

2.4

Confined space

If there is NOT sufficient air for

 

 

(a) Air from the outdoors shall be provided to the confined space

 

 

 

 

combustion due to tight construc-

 

 

by two permanent openings, one in or near the top of the

 

 

 

 

tion or other conditions it

 

 

enclosure space and one in or near the bottom. The open-

 

 

 

 

REQUIRES AIR FROM OUT-

 

 

ings shall communicate directly, or by means of ducts, with

 

 

 

 

DOORS. SEE “ACTION

 

 

outdoors or to such spaces (crawl or attic) that freely com-

 

 

 

 

REQUIRED” column at right.

 

 

municate with outdoors (See figures 3b, 3c

 

 

 

 

See NOTE (2) below.

 

 

and 3d).

 

 

 

 

 

 

 

(b) Where directly communicating with outdoors or by means of

 

 

 

 

 

 

 

vertical ducts, each opening shall have a free area of not

 

 

 

 

 

 

 

less than 1 sq. in. per 4,000 Btu/hr. (35 sq. in. per gal. per hr.)

 

 

 

 

 

 

 

of TOTAL input rating of ALL appliances in the enclosure. If

 

 

 

 

 

 

 

horizontal ducts are used, each opening shall have a free

 

 

 

 

 

 

 

 

 

 

 

 

area of not less than 1 sq. in. per 2,000 Btu/hr. (70 sq. in. per

 

 

 

 

 

 

 

gal. per hr.) of TOTAL input of ALL appliances in the confined

 

 

 

 

 

 

 

space. See Figures 3b, 3c and 3d.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)Test for sufficient air for combustion by infiltration by running this boiler for 30 minutes under all of the following conditions and at the same time: a) all doors, win- dows and other like openings must be closed, b) all fuel burning appliances should be FIRING, c) all exhaust fans and clothes dryers turned ON. At the above conditions the CO2, smoke and draft readings must be normal. (CO2 between 11% and 13%, smoke between ZERO and a TRACE, draft between .02” W.C. and

.04” W.C. negative pressure.)

(2)Aside from tight construction, some of the conditions that steal air for combustion from a boiler are other fuel burning appliances, exhaust fans and clothes dryers.

(3)Generally, louvers made of wood have a free open area of 20% and those made of metal have a 60% to 70% free open area. Screens also reduce the open area of the louvers.

Image 4
Contents Intrepid Intrepid Chimney CONNECTOR-18 Boiler LocationMinimum Clearance Chimney RequirementsRequires AIR from OUT Intrepid Installing Controls Accessories on Boiler Units Cleaning Piping SystemPiping Piping for Steam BoilersWiring the Boiler Installing the BurnerOIL Supply Piping Cleaning and Filling a NEW Water Boiler III. Safety Check for Control SystemVent Piping and Draft Regulator START-UPCOMBUSTION Test Instruments Must be UsedBlowing OFF a LOW Pressure Steam Boiler Cleaning and Filling a NEW Steam BoilerLOW Water CUT-OFF CHECK-OUT Replacement of Steam Boilers Pressure Control CHECK-OUTIntrepid Intrepid Wiring for Packaged Steam Boiler Steam Boiler Wiring for Riello Burner and McDONELL Intrepid Burner Data Beckett CF-375 Burners for Packaged Boilers only DelevanIntrepid Turbulator Settings Riello 40 Series Burner Data RielloIntrepid Intrepid II. Providing Protection for Freezing IV. General MaintenanceIII. OIL Burner Page Page SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

Oil-fired Boiler specifications

The Slant/Fin Oil-fired Boiler is renowned for its reliable performance and efficiency in residential and commercial heating applications. Designed to deliver optimal heating while minimizing fuel costs, this boiler is an excellent choice for those looking to maximize comfort in their living spaces.

One of the main features of the Slant/Fin Oil-fired Boiler is its robust construction, which ensures longevity and resilience against harsh conditions. Crafted from high-quality materials, the boiler boasts a cast iron heat exchanger that provides superior heat retention and distribution. This construction not only contributes to its durability but also enhances its overall energy efficiency.

A standout characteristic of the Slant/Fin Oil-fired Boiler is its advanced burner technology. The unit incorporates a high-efficiency oil burner that ensures complete combustion of the fuel. This upgrade leads to significant energy savings while producing low emissions, thereby making it an environmentally friendly heating solution. The burner is designed for quiet operation, which adds to the comfort of home environments.

The boiler is equipped with an innovative control system that allows users to easily monitor and adjust settings for optimal performance. This feature aids in maintaining a consistent temperature throughout the home, ensuring comfort during the coldest months. Additionally, the system offers diagnostic capabilities, making it easier to troubleshoot and maintain.

Another key characteristic of the Slant/Fin Oil-fired Boiler is its versatility in installation. The compact design allows for installation in a variety of spaces, including basements, utility rooms, and garages. This adaptability makes it a popular choice for homeowners looking to optimize their heating solutions without compromising on space.

Furthermore, Slant/Fin offers a variety of models within its oil-fired boiler range to cater to diverse heating needs. This range includes different output capacities to accommodate various home sizes. With a focus on user-friendly design, the boilers come with clear instructions and support for installation and maintenance.

In conclusion, the Slant/Fin Oil-fired Boiler stands out for its durability, efficiency, and advanced technologies. Its cast iron construction, high-efficiency oil burner, and innovative control systems combine to create a reliable heating solution. A perfect fit for both residential and commercial applications, this boiler ensures comfort and peace of mind, making it a preferred choice among homeowners seeking quality and performance in their heating systems.