Slant/Fin Oil-fired Boiler dimensions Installing the Burner, OIL Supply Piping, Wiring the Boiler

Page 7

INTREPID

7

C.HOT WATER RADIATION VENTING - Manual air vents should be installed at the top of all "drops"(where piping goes downward).

Air must be vented or purged from all zone lines to permit proper system heating.

D.PUMP LOCATION-Locating low-head pump(s) on return to boil- er is only acceptable in residences of one or two stories. (See figure 6) The pump location shown in figure 7 is required in large, multi-story building installations, especially when high-head pumps are used and is also recommended for all applications.

E.A conventional compression tank may be connected to the 3/4" tapping as shown in figure 7.

IMPORTANT: Hot water heating systems containing high water volume, such as would occur with cast-iron radiation, require special care with air elimination. The circulator pump should be located on the boiler supply pipe and the expansion tank and air scoop should be located near the pump suction. (See Figure 6, Alternate Pump Location.)

PIPING TANKLESS HEATER (if used)

I. Heater capacities are listed on Page 2.

II.Pipe the built-in tankless heater using the inlet and outlet tappings indicated on the heater (figure 8).

A.Tempering valve (illustrated, but not furnished) is suggested to provide more volume of temperate water to kitchen and bath.

B.High temperature water, for dishwasher and laundry, may be piped direct.

C.A flow control valve should be used to control the rate of flow of water through the coil, otherwise the heating capacity of the coil will be exceeded. To insure sufficient hot water, the flow rate through the coil should be limited to a maximum shown for inter- mittent draw in the ratings table on page 2.

INSTALLING THE BURNER

See Burner Data, pages 14-18, and Burner Manual supplied with burn- er. If burner is not mounted as received, mount to boiler, placing flange over mounting studs. Use gasket between flange and boiler. Distance between flange and nose of burner must be as shown on pages 14-18. Check to see that nozzle and settings are as given in burner data tables, pages 14-18.

OIL SUPPLY PIPING

Install the oil tank or tanks and piping from tank to burner. Follow local codes and practices, NFPA No. 31, INSTALLATION OF OIL BURNING EQUIPMENT and the instruction sheet attached to the oil burner pump.

A one-pipe system should be used for gravity-fed fuel systems and for lift systems, where the total lift is less than 8 feet. Where the total lift is greater than 8 feet, a two-pipe system must be used. In some instances, local codes may require a two-pipe system for below grade fuel oil tanks. Be sure to set-up the fuel oil pump for the piping system used; follow the instructions attached to the pump. Be sure to include a good quality, low pressure drop fuel oil filter in the supply line from the tank. This is necessary, especially at low fuel oil flow rates (small nozzle sizes), to prevent nozzle plugging. See Slant/Fin publication on one-pipe and two-pipe fuel oil systems.

WIRING THE BOILER

A.The wiring diagrams for the burner and boiler may be found on pages 11-13.

B.24 volt control wiring should be approved Safety Circuit wire, protected as needed.

C.Power supply wiring to the burner must be 14 gauge or heavier, as required, and should have a properly fused disconnect switch. 120 volt wiring to pumps and safety controls must also be 14 gauge or heavier. Wire must be enclosed in approved conduit.

D.All wiring must be installed in compliance with the National Electric Code, or any local or insurance codes having jurisdiction.

Image 7
Contents Intrepid Intrepid Chimney Requirements Chimney CONNECTOR-18Boiler Location Minimum ClearanceRequires AIR from OUT Intrepid Piping for Steam Boilers Installing Controls Accessories on Boiler UnitsCleaning Piping System PipingWiring the Boiler Installing the BurnerOIL Supply Piping START-UPCOMBUSTION Test Instruments Must be Used Cleaning and Filling a NEW Water BoilerIII. Safety Check for Control System Vent Piping and Draft RegulatorBlowing OFF a LOW Pressure Steam Boiler Cleaning and Filling a NEW Steam BoilerLOW Water CUT-OFF CHECK-OUT Pressure Control CHECK-OUT Replacement of Steam BoilersIntrepid Intrepid Wiring for Packaged Steam Boiler Steam Boiler Wiring for Riello Burner and McDONELL Intrepid Delevan Burner Data Beckett CF-375 Burners for Packaged Boilers onlyIntrepid Burner Data Riello Turbulator Settings Riello 40 SeriesIntrepid Intrepid II. Providing Protection for Freezing IV. General MaintenanceIII. OIL Burner Page Page SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

Oil-fired Boiler specifications

The Slant/Fin Oil-fired Boiler is renowned for its reliable performance and efficiency in residential and commercial heating applications. Designed to deliver optimal heating while minimizing fuel costs, this boiler is an excellent choice for those looking to maximize comfort in their living spaces.

One of the main features of the Slant/Fin Oil-fired Boiler is its robust construction, which ensures longevity and resilience against harsh conditions. Crafted from high-quality materials, the boiler boasts a cast iron heat exchanger that provides superior heat retention and distribution. This construction not only contributes to its durability but also enhances its overall energy efficiency.

A standout characteristic of the Slant/Fin Oil-fired Boiler is its advanced burner technology. The unit incorporates a high-efficiency oil burner that ensures complete combustion of the fuel. This upgrade leads to significant energy savings while producing low emissions, thereby making it an environmentally friendly heating solution. The burner is designed for quiet operation, which adds to the comfort of home environments.

The boiler is equipped with an innovative control system that allows users to easily monitor and adjust settings for optimal performance. This feature aids in maintaining a consistent temperature throughout the home, ensuring comfort during the coldest months. Additionally, the system offers diagnostic capabilities, making it easier to troubleshoot and maintain.

Another key characteristic of the Slant/Fin Oil-fired Boiler is its versatility in installation. The compact design allows for installation in a variety of spaces, including basements, utility rooms, and garages. This adaptability makes it a popular choice for homeowners looking to optimize their heating solutions without compromising on space.

Furthermore, Slant/Fin offers a variety of models within its oil-fired boiler range to cater to diverse heating needs. This range includes different output capacities to accommodate various home sizes. With a focus on user-friendly design, the boilers come with clear instructions and support for installation and maintenance.

In conclusion, the Slant/Fin Oil-fired Boiler stands out for its durability, efficiency, and advanced technologies. Its cast iron construction, high-efficiency oil burner, and innovative control systems combine to create a reliable heating solution. A perfect fit for both residential and commercial applications, this boiler ensures comfort and peace of mind, making it a preferred choice among homeowners seeking quality and performance in their heating systems.