Slant/Fin SX-210, S-150, SX-150 dimensions Sentry

Page 16

16

Sentry

PUMP OR VALVE ZONING OF WATER BOILERS

 

COMBINATION CONTROLS WITH T TV Z

TERMINALS*

Pump Zoning system using R845A Relay.

One R845A needed for each circulator.

NOTE: Pumps are powered from C1 . Total pump load must not exceed 7.4 amp rating of combination control pump switch.

Zone valve zoning system using Honeywell V8043F zone valves.

Pump zoning system using R8230C Relays.

*For zoning diagrams, combination controls without T TV Z terminals and non-combination control systems, consult Slant/Fin Zoning Tech. Bulletin.

NOTE: Pumps are powered from C1 . Total pump load must not exceed 7.4 amp rating of combination control pump switch.

Image 16
Contents Installation and Operating Instructions Liquefied Petroleum L.P Propane GAS-FIRED BoilersSentry Natural GAS-FIRED Boiler Location Boiler FoundationSafety Liquefied Petroleum L.P. Propane GAS-FIRED Boiler LocationChimney Requirements Draft HoodVent Damper Installation Installation Instructions Before YOU Start to InstallDamper Vane After Installation Thermostat Heat Anticipator AdjustmentsElectrical Controls and Wiring NOW, Proceed AS FollowsBoiler Room AIR Supply and Ventilation Water PipingCirculating Systems II. AIR Control SystemSafety Information For Your Safety Read Before LightingII. Initial Start InstructionsFor Your Safety Read Before Operating Operating InstructionsWater System Check Boiler rated input Cubic FeetAnnual Inspection and Cleaning Safety Check for Control SystemWater Level Check During Heating Season Providing Protection from FreezingPropane GAS S8600M & S8670E Wiring Diagram Continuous Pilot Wiring Diagram Intermittent Ignition IID Sentry Delayed Ignition Cause Remedy Burners will not Shut OFF Cause RemedyFlash Back Burning AT Orifices Cause Remedy Fumes and GAS Odors Cause RemedyIf Replacement Parts are Needed Appendix a Removal of Existing Boiler from Common Vent SystemSLANT/FIN CORPORATION, Greenvale, N.Y Phone 516