SEQUENCE OF OPERATION FOR SENTRY BOILERS
EQUIPPED WITH CONTINUOUS BURNING PILOTS
FOR DIAGRAMS SHOWN ON PAGE 14.
LIGHTED PILOT HEATS THERMOCOUPLE AND KEEPS PILOTSTAT OPEN.
|
|
|
|
| THERMOSTAT CALLS FOR HEAT |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CIRCULATOR ENERGIZED |
| HIGH LIMIT CONTACTS CLOSED? |
|
| NO | |||||||
(IF COMBINATION AQUASTAT |
| LOW WATER |
|
|
|
| ||||||
|
|
|
|
| ||||||||
CONTROL USED) |
| CONTACTS CLOSED? |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| YES |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| VENT DAMPER RELAY ENERGIZED. |
|
|
| |||||
|
|
| VENT DAMPER MOTOR OPENS VENT DAMPER. |
|
|
| ||||||
|
|
|
|
| END SWITCH CLOSES. |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| MAIN VALVE OPERATOR OPENS. |
|
|
| |||||
|
|
| LIGHTED PILOT IGNITES MAIN BURNERS. |
|
|
| ||||||
|
|
| IF PILOT SHOULD BLOW OUT, THERMOCOUPLE |
|
|
| ||||||
|
|
|
| WILL SHUT OFF MAIN BURNER. |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| WHEN THERMOSTAT IS SATISFIED, OR WHEN HIGH LIMIT |
| |||||||||
|
| OR LOW WATER |
|
| ||||||||
|
|
|
|
| VALVE OPERATOR CLOSES. |
|
| |||||
|
|
| VENT DAMPER CLOSES. CIRCULATOR OFF. |
|
| |||||||
|
| SYSTEM GOES TO STANDBY WITH LIGHTED PILOT. |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
NO FURTHER
ACTION
SEQUENCE OF OPERATION FOR SENTRY BOILERS EQUIPPED WITH HONEYWELL INTERMITTENT
IGNITION SYSTEM (IID) FOR DIAGRAMS SHOWN ON PAGE 15.
|
|
|
|
| THERMOSTAT CALLS FOR HEAT |
|
|
|
| ||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CIRCULATOR ENERGIZED |
|
| HIGH LIMIT CONTACTS CLOSED? |
|
| NO | |||||
(IF COMBINATION AQUASTAT |
|
| LOW WATER |
|
|
|
| ||||
|
|
|
|
|
| ||||||
CONTROL USED) |
|
| CONTACTS CLOSED? |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| YES |
|
| |||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| VENT DAMPER RELAY ENERGIZED. |
|
| ||||
|
| VENT DAMPER MOTOR OPENS VENT DAMPER. |
|
| |||||||
|
|
|
|
| END SWITCH CLOSES. |
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| IGNITION CONTROL ENERGIZED |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
NO FURTHER
ACTION
SPARK GENERATOR MODULE POWERED.
S8600F OR S8600M: IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS. S8670E: IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR
L.P. PROPANE GAS (S8600M & S8670E)
IGNITION TRIAL CONTINUES FOR 90 SEC- ONDS. AFTER TRIAL FOR IGNITION, SYS- TEM SHUTS OFF. AFTER 5 MINUTES MOD- ULE
NO |
| NO |
THE PILOT FLAME ESTABLISHED ?
YES
SPARK GENERATOR OFF. MAIN VALVE OPERATOR OPENS. MODULE MONITORS PILOT FLAME.
NATURAL GAS (S8600F) IGNI-
TION SPARK CONTINUES.
PILOT VALVE REMAINS OPEN
UNTIL SYSTEM IS RESET.
WHEN THERMOSTAT IS SATISFIED OR WHEN HIGH LIMIT OR LOW WATER