Slant/Fin SX-210, S-150, SX-150 dimensions Propane GAS S8600M & S8670E

Page 13

Sentry

13

SEQUENCE OF OPERATION FOR SENTRY BOILERS

EQUIPPED WITH CONTINUOUS BURNING PILOTS

FOR DIAGRAMS SHOWN ON PAGE 14.

LIGHTED PILOT HEATS THERMOCOUPLE AND KEEPS PILOTSTAT OPEN.

 

 

 

 

 

THERMOSTAT CALLS FOR HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCULATOR ENERGIZED

 

HIGH LIMIT CONTACTS CLOSED?

 

 

NO

(IF COMBINATION AQUASTAT

 

LOW WATER CUT-OFF (WHEN USED)

 

 

 

 

 

 

 

 

 

CONTROL USED)

 

CONTACTS CLOSED?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT DAMPER RELAY ENERGIZED.

 

 

 

 

 

 

VENT DAMPER MOTOR OPENS VENT DAMPER.

 

 

 

 

 

 

 

 

END SWITCH CLOSES.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAIN VALVE OPERATOR OPENS.

 

 

 

 

 

 

LIGHTED PILOT IGNITES MAIN BURNERS.

 

 

 

 

 

 

IF PILOT SHOULD BLOW OUT, THERMOCOUPLE

 

 

 

 

 

 

 

WILL SHUT OFF MAIN BURNER.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHEN THERMOSTAT IS SATISFIED, OR WHEN HIGH LIMIT

 

 

 

OR LOW WATER CUT-OFF CONTACTS ARE OPEN, MAIN

 

 

 

 

 

 

 

VALVE OPERATOR CLOSES.

 

 

 

 

 

VENT DAMPER CLOSES. CIRCULATOR OFF.

 

 

 

 

SYSTEM GOES TO STANDBY WITH LIGHTED PILOT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO FURTHER

ACTION

SEQUENCE OF OPERATION FOR SENTRY BOILERS EQUIPPED WITH HONEYWELL INTERMITTENT

IGNITION SYSTEM (IID) FOR DIAGRAMS SHOWN ON PAGE 15.

 

 

 

 

 

THERMOSTAT CALLS FOR HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCULATOR ENERGIZED

 

 

HIGH LIMIT CONTACTS CLOSED?

 

 

NO

(IF COMBINATION AQUASTAT

 

 

LOW WATER CUT-OFF (WHEN USED)

 

 

 

 

 

 

 

 

 

 

CONTROL USED)

 

 

CONTACTS CLOSED?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT DAMPER RELAY ENERGIZED.

 

 

 

 

VENT DAMPER MOTOR OPENS VENT DAMPER.

 

 

 

 

 

 

 

END SWITCH CLOSES.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IGNITION CONTROL ENERGIZED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO FURTHER

ACTION

SPARK GENERATOR MODULE POWERED.

S8600F OR S8600M: IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS. S8670E: IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR 30-70 SECONDS.

L.P. PROPANE GAS (S8600M & S8670E)

IGNITION TRIAL CONTINUES FOR 90 SEC- ONDS. AFTER TRIAL FOR IGNITION, SYS- TEM SHUTS OFF. AFTER 5 MINUTES MOD- ULE RE-INSTATES TRIAL FOR IGNITION. IF PILOT FLAME NOT ESTABLISHED, IGNI- TION TRIAL, SYSTEM SHUT-OFF AND 5 MINUTES WAIT SEQUENCE REPEATS CONTINUOUSLY.

NO

 

NO

THE PILOT FLAME ESTABLISHED ?

YES

SPARK GENERATOR OFF. MAIN VALVE OPERATOR OPENS. MODULE MONITORS PILOT FLAME.

NATURAL GAS (S8600F) IGNI-

TION SPARK CONTINUES.

PILOT VALVE REMAINS OPEN

UNTIL SYSTEM IS RESET.

WHEN THERMOSTAT IS SATISFIED OR WHEN HIGH LIMIT OR LOW WATER CUT-OFF CONTACTS ARE OPEN, VALVE OPERA- TORS CLOSE. PILOT & MAIN BURNERS OFF. VENT DAMPER CLOSES. CIRCULATOR OFF. SYSTEM GOES TO STANDBY.

Image 13
Contents Liquefied Petroleum L.P Propane GAS-FIRED Boilers Installation and Operating InstructionsSentry Boiler Foundation Natural GAS-FIRED Boiler LocationLiquefied Petroleum L.P. Propane GAS-FIRED Boiler Location SafetyChimney Requirements Draft HoodInstallation Instructions Before YOU Start to Install Vent Damper InstallationDamper Vane Thermostat Heat Anticipator Adjustments After InstallationElectrical Controls and Wiring NOW, Proceed AS FollowsWater Piping Boiler Room AIR Supply and VentilationCirculating Systems II. AIR Control SystemFor Your Safety Read Before Lighting Safety InformationII. Initial Start InstructionsOperating Instructions For Your Safety Read Before OperatingBoiler rated input Cubic Feet Water System CheckSafety Check for Control System Annual Inspection and CleaningWater Level Check During Heating Season Providing Protection from FreezingPropane GAS S8600M & S8670E Wiring Diagram Continuous Pilot Wiring Diagram Intermittent Ignition IID Sentry Burners will not Shut OFF Cause Remedy Delayed Ignition Cause RemedyFlash Back Burning AT Orifices Cause Remedy Fumes and GAS Odors Cause RemedyIf Replacement Parts are Needed Removal of Existing Boiler from Common Vent System Appendix aSLANT/FIN CORPORATION, Greenvale, N.Y Phone 516