APPENDIX A

Removal of Existing Boiler from Common Vent System

"At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation."

(a)Seal any unused openings in the common venting system.

(b)Visually inspect the venting system for proper size and hor- izontal pitch and determine there is no blockage or restric- tion, leakage, corrosion and other deficiencies which could cause an unsafe condition.

(c)Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryer and any appliance not connected to the common vent- ing system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. DO NOT operate a summer exhaust fan. Close fire- place dampers.

(d)Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.

(e)Test for spillage at the draft hood relief opening after 5 min- utes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.

(f)After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous conditions of use.

(g)Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1- latest edition.

Image 19
Contents Liquefied Petroleum L.P Propane GAS-FIRED Boilers Installation and Operating InstructionsSentry Boiler Foundation Natural GAS-FIRED Boiler LocationDraft Hood SafetyLiquefied Petroleum L.P. Propane GAS-FIRED Boiler Location Chimney RequirementsInstallation Instructions Before YOU Start to Install Vent Damper InstallationDamper Vane NOW, Proceed AS Follows After InstallationThermostat Heat Anticipator Adjustments Electrical Controls and WiringII. AIR Control System Boiler Room AIR Supply and VentilationWater Piping Circulating SystemsInstructions Safety InformationFor Your Safety Read Before Lighting II. Initial StartOperating Instructions For Your Safety Read Before OperatingBoiler rated input Cubic Feet Water System CheckProviding Protection from Freezing Annual Inspection and CleaningSafety Check for Control System Water Level Check During Heating SeasonPropane GAS S8600M & S8670E Wiring Diagram Continuous Pilot Wiring Diagram Intermittent Ignition IID Sentry Fumes and GAS Odors Cause Remedy Delayed Ignition Cause RemedyBurners will not Shut OFF Cause Remedy Flash Back Burning AT Orifices Cause RemedyIf Replacement Parts are Needed Removal of Existing Boiler from Common Vent System Appendix aSLANT/FIN CORPORATION, Greenvale, N.Y Phone 516