3M 5797A-MT, 78-8126-0432-6-A manual Cold Shrink QS-III

Page 1

Cold Shrink QS-III

Three-Conductor Splice Kit for use on Armor and Non-Armor Cables

Instructions

IEEE Std. 404 35 kV Class 250 kV BIL

Cable Range Requirements

Kit Number

Cable Insulation

Conductor

 

O.D. Range

Size Range

 

 

 

5797A-MT

1.07" to 1.70"

1/0 AWG - 350 kcmil*

 

(27,2 mm to 43,2 mm)

(60 - 185 mm2)

 

 

 

*Splices (including size transitions) can be made to smaller or larger conductors, provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements shown below.

Connector Dimensional Requirements

 

Minimum

Maximum

 

inches (mm)

inches (mm)

 

 

 

Outside Diameter

0.51" (13,0 mm)

1.70" (43,2 mm)

 

 

 

Length

 

 

Aluminum (Al/Cu)

------

6.00" (152 mm)

 

 

 

Length

 

 

Copper (Cu)

------

6.50" (165 mm)

 

 

 

3MCold Shrink

QS-III Splicing Kit

5797A-MT

78-8126-0432-6-A

CAUTION

Working around energized high-voltage systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling high-voltage electrical equipment. De-energize and ground all electrical systems before installing product.

Image 1
Contents Cold Shrink QS-III Contents Prepare Cable Kit ContentsAluminum Cable end Place Components on CableMm measured from the Center of connectors Install Splice78-8126-0432-6-A Install Armor Continuity If Cable is Armored Install Splice Jacket Splice is complete Crimping Tool Die Sets number of crimps/end Electrical Products Division