Cold Shrink QS-III
Instructions
IEEE Std. 404 35 kV Class 250 kV BIL
Cable Range Requirements
Kit Number | Cable Insulation | Conductor |
| O.D. Range | Size Range |
|
|
|
| 1.07" to 1.70" | 1/0 AWG - 350 kcmil* |
| (27,2 mm to 43,2 mm) | (60 - 185 mm2) |
|
|
|
*Splices (including size transitions) can be made to smaller or larger conductors, provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements shown below.
Connector Dimensional Requirements
| Minimum | Maximum |
| inches (mm) | inches (mm) |
|
|
|
Outside Diameter | 0.51" (13,0 mm) | 1.70" (43,2 mm) |
|
|
|
Length |
|
|
Aluminum (Al/Cu) | 6.00" (152 mm) | |
|
|
|
Length |
|
|
Copper (Cu) | 6.50" (165 mm) | |
|
|
|
3M™ Cold Shrink
CAUTION
Working around energized