3M 5797A-MT, 78-8126-0432-6-A manual Kit Contents, Prepare Cable

Page 3

1.0Kit Contents:

1.1Kit Contents are as follows:

3

Cold Shrink 5467A QS-III Silicone Splice Bodies

6

Tubes, P55/R Red Compound

3

Metallic Shield Sleeves

6

Constant Force Spring Shield Connectors (1.31" I.D.)

2

Constant Force Spring Shield Connectors (1.54" I.D.)

1

Armor to Armor Continuity Braid

2

Cold Shrink Jacket Tubes

1

3MCC-2 Cable Preparation Kit

1

Roll, Scotch33+ Vinyl Electrical Tape (3/4" x 66')

5

Rolls, ScotchSuper 88 Vinyl Electrical Tape (1 1/2" x 44')

4

Rolls, Scotch-Seal2229 Mastic Tape (3 3/4" x 10')

1

Roll, Scotch24 Electrical Shielding Tape (1" x 15')

1

Roll, Scotch2228 Rubber Mastic Tape (2" x 10')

6

Rolls, ArmorcastStructural Material (4" x 15')

6

Cold Shrink Adapter Tubes (3 white core and 3 red core)

1

Instruction Sheet

6

Copper Foil Tape (1/2" x 10")

12

Gloves

2.0Prepare Cable

2.1Prepare the cable according to your company's

standard procedures. Allow cable ends to overlap as much as 10" (254 mm).

Remove 33" (838 mm) of cable jacket, plus half of the overlap from Cable X.

Remove 25" (635 mm) of cable jacket, plus half of the overlap from Cable Y.

Keep a 22" (559 mm) piece of cable jacket removed from Cable X and a 14" (356 mm) piece of jacket from Cable Y for use later in these instructions.

2.2If cable is armored, remove cable armor leaving

1 1/2" (37 mm) armor exposed beyond jacket end.

Remove cable binder , if present, at the end of the jacket or armor and discard.

Fold cable fillers and ground wire(s) back over cable jacket end. Do not cut off.

Temporarily hold the fillers and ground wire(s) back by banding them to the cable jacket using Scotch33+ vinyl tape.

Cable X

33" (838 mm)

Cable Y

25" (635 mm)

11/2"

(37 mm)

remove

binderfold fillers back

DO NOT CUT OFF

78-8126-0432-6-A

3

Image 3
Contents Cold Shrink QS-III Contents Prepare Cable Kit ContentsAluminum Cable end Place Components on CableMm measured from the Center of connectors Install Splice78-8126-0432-6-A Install Armor Continuity If Cable is Armored Install Splice Jacket Splice is complete Crimping Tool Die Sets number of crimps/end Electrical Products Division