Stovax 7051Bl, 7053lG, 7008lG, 7008Bl Walls next to hearths, 150mm Minimum Thickness W PR7227

Page 16

SITE REQUIREMENTS

walls next to hearths

Solid, non-combustible material e.g. masonry or concrete

H

150mm

minimum

C

Thickness W

C

150mm

minimum

PR7227

Position of Appliance & Hearth in relation to walls

Requirement for the walls

 

 

 

 

Distance of hearth from wall

Distance of Appliance to wall

Min thickness of Wall

Min height of wall

'C'

 

'W'

'H'

 

 

 

 

0mm

0mm - 50mm

200mm

Height of appliance + 300mm

 

 

 

Or

 

 

 

 

 

 

1200mm from the hearth (take largest

0mm

51mm - 300mm

75mm

dimension)

 

 

 

 

0 - 150mm

150mm +

75mm

1200mm

 

 

 

 

150mm +

300mm +

No Minimum Requirement

 

 

 

 

Suitable clearance should be allowed around the stove to enable the correct fitting and maintenance of the stove. Any clearances should be confirmed by making a site survey and a physical check of wall thickness and dimensions.

16

Image 16
Contents Brunel 1A/2CB/3CB Installation Instructions PRE-INSTALLATIONInstallation Commissioning Maintenance & ServicingAppliance Commissioning Checklist Installation EngineerDealer appliance was purchased from Essential Information Must be completedUser Instructions General PointsSerial Number AIR ControlsUsing the Appliance for the First Time Use a protective gloved hand to operate. See DiagramRecommended Fuels Do not touch the paint during the first period of useLighting the fire Solid fuelWood PR7225aRunning The appliance Air Inlets Log Guard AR2147 Close the doorBurning Wood Burning Solid fuelBurning tips ASH Removal Over night burningOVER-FIRING Chimney fireGeneral Cleaning Cleaning GlassChimney Sweeping Care of stoveTroubleshooting tips Seasonal useRiddling mechanism jamming Glass crackingTECHNICAL SPECIFICATION Standard featuresBrunel Packing listBrunel Dimensions All dimensions in mm .4mm =PR7225 ModelSite Requirements Flue or ChimneyMax. Draught = 2.0mm Wg Min. Draught = 1.0mm Wg U.K Flue PlateHearth Dimensions Flue Outlet PositionsWalls next to hearths 150mm Minimum Thickness W PR7227Flue PRE-INSTALLATION ChecksAdditional Ventilation Ventilation Installation Instructions Installing the ApplianceTop flue pipe installation Legal requirementsRear flue pipe installation Removal of the LOG GuardDo not use a 90˚ elbow to make this connection Do not use appliance without the log guard in positionFitting & Removal of Baffle Brunel 1A onlyFitting and Removal Riddling Mechanism Multi-fuel onlyCommissioning CommissioningGive the copy of the Instructions to the customer Annual Service Fitting and Removal of the Firebricks Fitting and Removal of BaffleFitting a NEW Door Glass ALL Models Fitting a new door sealBasic Spare Parts List Brunel 1A Brunel 2CBBrunel 3CB Brunel 1APage Service Records Page