Samsung AQ12TSBX, AQ24TSBXEUR manual Smooth the cut edges, Cut off the remaining foam insulation

Page 30

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies

 

 

according to the exit position of the pipe when facing the wall:

A

B

• Right(A)

 

 

• Left(B)

 

C

• Underside(C)

 

 

 

• Rear

 

 

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

• If you want to shorten or extend the pipes, refer to page 31~32.

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and purge the air, refer to page 34~36.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 37 for further details.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

30

Image 30 Contents
Page Contents Follow directions Safety precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning Checking before use Operation rangesMain parts  09/12/18/24T  PowerChecking the name of the parts Display  09/12/18/24TChecking the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasic function Auto Auto Low Med HighLow Med High Press the Air swing button on the remote controller Adjusting the air flow directionUsing the Turbo function Vertical air flowMode When the air conditioner is on and in cool/heat modePress the button on the remote controller Press the Time Up or Time Down button to set the timeSetting the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode If the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer Turn off automaticallyUsing the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on Cleaning the outdoor unit heat exchanger Cleaning the air conditionerCleaning the indoor unit Opening the panelOpen the panel and put the Air filter out Cleaning the air filterRemoving the Air filter Dry the Air filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Outdoor unit Heat exchanger during Heat mode in winter Flow movement changes. It is normalConnection General information Included Models RemarkPower supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitModel  Figure Description When installing more than 1 outdoor unitWhen the air outlet is towards the wall Top view Side viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberInstallation Smooth the cut edges Cut off the remaining foam insulationPass the pipe through the hole in the wall Unscrew the caps at the end of each pipe Purging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCracked Pipe 50 Pa. The joint must be accessible and serviceableCorrect Inclined Outer DiameterTwo hoses are firmly connected, there is no water leakage Drain hose installationChanging direction of the drain hose Check for leakage on both side of the drain outletPurging the connected pipes Connect a drain hose to the drain plugEnsure that condensation draining is adequate If you use a pipe longer than 5m Gas service port as seen in the pictureAdding Refrigerant If you use a pipe shorter than 5mPlease fill in with indelible ink  the factory refrigerant charge of the product1975 To check for gas leaks on the indoor unit Performing the gas leak testsTo check for gas leaks on the outdoor unit Leak test with nitrogen before opening valvesThen place the indoor unit on the installation plate Fixing the indoor unit in placeFixing the outdoor unit in place Final Check and Trial Operation After tube contraction work is completed, wrap it with How to connect your extended power cablesApply heat to the contraction tube to contract it Insulation tape to finishMemo Questions or COMMENTS? Air Conditioner
Related manuals
Manual 43 pages 7.84 Kb Manual 21 pages 37.46 Kb Manual 43 pages 50.34 Kb Manual 43 pages 54.35 Kb Manual 41 pages 57.34 Kb Manual 43 pages 47.11 Kb Manual 41 pages 21.89 Kb Manual 21 pages 33.89 Kb Manual 43 pages 20.03 Kb Manual 43 pages 57.8 Kb Manual 39 pages 24.04 Kb Manual 41 pages 16.8 Kb Manual 41 pages 21.55 Kb Manual 21 pages 17.82 Kb Manual 40 pages 16.42 Kb Manual 41 pages 7.22 Kb Manual 41 pages 49.92 Kb Manual 41 pages 32.45 Kb Manual 41 pages 26.36 Kb Manual 41 pages 36.71 Kb Manual 41 pages 46.99 Kb Manual 41 pages 14.18 Kb Manual 43 pages 51.4 Kb Manual 41 pages 63.42 Kb Manual 41 pages 47.02 Kb Manual 21 pages 20.86 Kb Manual 39 pages 33.67 Kb Manual 43 pages 50.37 Kb