Samsung AQ18TSBNCEE, AQ24TSBXEUR Changing direction of the drain hose, Drain hose installation

Page 33

Drain hose installation

1.If necessary, connect the 2-meter extension drain hose to the drain hose.

2.If you use the extension drain hose, insulate the inside of the extension drain hose with a shield.

3.Fit the drain hose into 1 of 2 drain hose holes, then fix the end of the drain hose tightly with a clamp.

• If you do not use the other drain hose hole, block it with a rubber stopper.

4. When extending the Drain Hose, hold the end of Drain Hose and Extended Hose,

 

rotate and insert the drain hose into Extended hose for 15~20 mm. Make sure the

Drain hose hole

two hoses are firmly connected, there is no water leakage.

 

5.Connect the Drain Hose after using Foam Insulation to wrap the Extended Hose. Then, Use vinyl tape to wrap the each side of connection by 20mm .

15~20 mm

20mm

20mm

or more

or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENGLISH

Drain hose

Ex

tensi

on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Extension

 

drain hose

Drain

hose

 

 

 

 

 

 

 

 

 

 

 

 

drain hose

6.Pass the drain hose under the refrigerant pipe, keeping the drain hose tight.

7.Pass the drain hose through the hole in the wall. Check if it slants downwards as seen in the picture.

8.Using natural drainage method, check the drainage is normal.

Vinyl Tape Foam Insulation

Shield

Drain hose

Extension drain hose

• The hose will be fixed permanently into position after finishing the installation and the gas leak test; refer to page

37~38 for further details.

• Make sure the installed direction of the drain hose is correct. Inadequate installation may cause condensate water leakage.

If the drain hose is routed inside the room, insulate the hose so that dripping condensation does not damage the furniture or floors.

DO NOT WALL UP THE DRAIN HOSE CONNECTION !

Drain hose connection must be easy accessible and serviceable.

Changing direction of the drain hose

Change the direction only when it is necessary.

1.

Detach the rubber cap with the plier.

 

2.

Detach the drain hose by pulling it and turning to the left.

3.

Insert the drain hose by fixing it with the screw into the groove of the drain

 

hose and the outlet of the drain pan.

 

4.

Attach the rubber cap with a screwdriver by turning it to the right until it

 

fixes to the end of the groove.

 

5.

Check for leakage on both side of the drain outlet.

 

Pour the water in direction of arrow.

Direction of the drained water

Screw hole

Screw

Drain hose

Drain pan outlet Rubber cap

Make sure the indoor unit is in upright position when you pour water to check for leakage.

Make sure that the water does not overflow onto the electrical part.

33

Image 33 Contents
Page Contents Important safety symbols and precautions Safety precautionsFollow directions Wall socketFor Using For Cleaning Operation ranges Checking before useChecking the name of the parts PowerMain parts  09/12/18/24T  Display  09/12/18/24TRemote controller buttons Checking the remote controllerBattery changing time Remote controller displayStoring the remote controller Inserting the batteriesBasic function Auto Auto Low Med HighLow Med High Using the Turbo function Adjusting the air flow directionPress the Air swing button on the remote controller Vertical air flowPress the button on the remote controller When the air conditioner is on and in cool/heat modeMode Press the Time Up or Time Down button to set the timeSetting the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode From the moment you have set the timer Using the Smart Saver functionIf the air conditioner is on If the air conditioner is off Turn off automaticallyUsing the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on Cleaning the indoor unit Cleaning the air conditionerCleaning the outdoor unit heat exchanger Opening the panelRemoving the Air filter Cleaning the air filterOpen the panel and put the Air filter out Dry the Air filter in a ventilated areaPeriodical checks Maintaining the air conditionerTroubleshooting Outdoor unit Heat exchanger during Heat mode in winter Flow movement changes. It is normalConnection Included Models Remark General informationInstalling the unit Choosing the installation locationPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitModel When the air outlet is towards the wall When installing more than 1 outdoor unit Figure Description Top view Side viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Optional accessories Fixing the installation plateTools required for installation General Tools Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberInstallation Smooth the cut edges Cut off the remaining foam insulationPass the pipe through the hole in the wall Cutting or extending the pipe Purging the indoor unitUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareCorrect Inclined Pipe 50 Pa. The joint must be accessible and serviceableCracked Outer DiameterChanging direction of the drain hose Drain hose installationTwo hoses are firmly connected, there is no water leakage Check for leakage on both side of the drain outletPurging the connected pipes Connect a drain hose to the drain plugEnsure that condensation draining is adequate Adding Refrigerant Gas service port as seen in the pictureIf you use a pipe longer than 5m If you use a pipe shorter than 5mPlease fill in with indelible ink  the factory refrigerant charge of the product1975 To check for gas leaks on the outdoor unit Performing the gas leak testsTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesThen place the indoor unit on the installation plate Fixing the indoor unit in placeFixing the outdoor unit in place Final Check and Trial Operation Apply heat to the contraction tube to contract it How to connect your extended power cablesAfter tube contraction work is completed, wrap it with Insulation tape to finishMemo Questions or COMMENTS? Air Conditioner
Related manuals
Manual 43 pages 7.84 Kb Manual 21 pages 37.46 Kb Manual 43 pages 50.34 Kb Manual 43 pages 54.35 Kb Manual 41 pages 57.34 Kb Manual 43 pages 47.11 Kb Manual 41 pages 21.89 Kb Manual 21 pages 33.89 Kb Manual 43 pages 20.03 Kb Manual 43 pages 57.8 Kb Manual 39 pages 24.04 Kb Manual 41 pages 16.8 Kb Manual 41 pages 21.55 Kb Manual 21 pages 17.82 Kb Manual 40 pages 16.42 Kb Manual 41 pages 7.22 Kb Manual 41 pages 49.92 Kb Manual 41 pages 32.45 Kb Manual 41 pages 26.36 Kb Manual 41 pages 36.71 Kb Manual 41 pages 46.99 Kb Manual 41 pages 14.18 Kb Manual 43 pages 51.4 Kb Manual 41 pages 63.42 Kb Manual 41 pages 47.02 Kb Manual 21 pages 20.86 Kb Manual 39 pages 33.67 Kb Manual 43 pages 50.37 Kb