Final Check and Trial Operation

To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly.

Check the followings:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (follow the steps below)

ENGLISH

1.Press the Power button and check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

2.Press the Mode button to select Cool or Heat mode.

In Cool mode, use Temp + or - button and set the temperature at 16°C.

In Heat mode, use Temp + or - button and set the temperature at 30°C.

• Approximately 3~5 minutes later, outdoor unit will start to operate and the Cool or Warm air will blow out.

• After 12 minutes of stationary condition check the indoor unit air treatment:

Cooling mode (indoor unit check) Inlet air temp. - Outlet air temp : From 10°K to 12°K ( indicative delta T)

Heating mode (indoor unit check) Outlet air temp. - Inlet air temp : From 11°K to 14°K (indicative delta T)

In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space.

3.Press the Air swing button and check the following:

The airflow blades work properly.

4.Press the Power button to stop the operation.

• When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe

place.

Pump down procedure (when removing the product)

1.Turn on the air conditioner and select Cool mode to run the compressor for 3 minutes.

2. Release the valve caps on High and Low pressure side.

3. Use L wrench to close the valve on the high pressure side.

4. Approximately 2 minutes after, close the valve on the low pressure side.

5. Stop operation of the air conditioner.

6. Disconnect the pipes.

39

Vivaldi MAX EUR_AQV09&12U@@ IB&IM_33988A_EN-5.indd 39

2014/12/11 18:24:30

Image 39 Contents
Vivaldi MAX EURAQV09&12U@@ IB&IM33988AEN-5.indd 2014/12/11 Contents Wall socket Safety precautionsImportant safety symbols and precautions Follow directionsFor Using For Cleaning Operation ranges Checking before useDisplay Power buttonChecking the name of the parts Main partsRemote controller buttons Checking the remote controllerInserting the batteries Remote controller displayBattery changing time Storing the remote controllerBasic function Press Button to adjust the temperatureVertical air flow Adjusting the air flow directionUsing the Turbo function Press the Air swing button on the remote controllerPress the Time Up or Time Down button to set the time When the air conditioner is on and in cool/heat modePress the button on the remote controller ModeAdditional options available in On timer mode Setting the On/Off timerPress the On Timer/Off Timer button Cancel Press the Cancel buttonTurn off automatically Using the Smart Saver functionFrom the moment you have set the timer If the air conditioner is on If the air conditioner is offYou can reduce the noise generated from an indoor unit Using the Quiet functionUsing the Auto Clean function When the air conditioner is turned onOpening the panel Cleaning the air conditionerCleaning the indoor unit Cleaning the outdoor unit heat exchangerDry the Air filter in a ventilated area Cleaning the air filterRemoving the Air filter Open the panel and put the Air filter outPeriodical checks Maintaining the air conditionerTroubleshooting Outdoor unit Heat exchanger during Heat mode in winter Flow movement changes. It is normalConnection General information  a place where the air filter can be replaced easily Choosing the installation locationInstalling the unit Power supply line, fuse or circuit breakerWhere sulfide gas exists Outdoor UnitModel Top view Side view When installing more than 1 outdoor unitWhen the air outlet is towards the wall  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Tools for test operations Fixing the installation plateOptional accessories Tools required for installation General ToolsIf you fix the indoor unit on a gypsum board Connecting the cableFix the indoor unit If you fix the indoor unit on a wall If you fix the indoor unit on a window frameExtend the assembly cable if necessary Cut off the remaining foam insulation Smooth the cut edgesPut a flare nut slightly into the pipe and modify the flare Purging the indoor unitCutting or extending the pipe Unscrew the caps at the end of each pipeOuter Diameter Pipe 50 Pa. The joint must be accessible and serviceableCorrect Inclined CrackedDrain hose installation Purging the connected pipes Connect a drain hose to the drain plugEnsure that condensation draining is adequate Adding Refrigerant Please fill in with indelible ink  the factory refrigerant charge of the product2088 Leak test with nitrogen before opening valves Performing the gas leak testsTo check for gas leaks on the outdoor unit To check for gas leaks on the indoor unitFixing the outdoor unit in place Outdoor unit installed on the wall by rackThen place the indoor unit on the installation plate Fixing the indoor unit in placeFinal Check and Trial Operation Insulation tape to finish How to connect your extended power cablesApply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withEnglish Questions or COMMENTS? Air Conditioner
Related manuals
Manual 41 pages 47.02 Kb Manual 21 pages 20.86 Kb Manual 39 pages 33.67 Kb Manual 43 pages 50.37 Kb Manual 41 pages 12.62 Mb Manual 43 pages 23.26 Kb Manual 41 pages 10.61 Kb Manual 41 pages 45.51 Kb Manual 23 pages 13.22 Kb Manual 41 pages 16.8 Kb Manual 41 pages 63.42 Kb Manual 21 pages 17.82 Kb Manual 43 pages 57.8 Kb