Heatiator IDV4833IT owner manual Construct the Appliance Chase, Clearances

Page 18

B. Construct the Appliance Chase

A chase is a vertical box-like structure built to enclose the gas appliance and/or its vent system. In cooler climates the vent should enclosed inside the chase.

NOTICE: Treatment of ceiling firestops and wall shield firestops and construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of local building codes. Therefore, you MUST check local building codes to determine the requirements to these steps.

Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The chase should not break the outside building envelope in any manner.

Walls, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltration barriers should be installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infiltration may be an issue, the inside surfaces may be sheetrocked and taped for maximum air tightness.

To further prevent drafts, the wall shield and ceiling firestops should be caulked with caulk with a minimum of 300ºF con- tinuous exposure rating to seal gaps. Gas line holes and other openings should be caulked with caulk with a mini- mum of 300ºF continuous exposure rating or stuffed with unfaced insulation. If the appliance is being installed on a cement slab, a layer of plywood may be placed underneath to prevent conducting cold up into the room.

C. Clearances

NOTICE: Install appliance on hard metal or wood surfaces extending full width and depth. DO NOT install directly on carpeting, vinyl, tile or any combustible material other than wood.

WARNING! Risk of Fire! Maintain specified air space clearances to appliance and vent pipe:

Insulation and other materials must be secured to prevent accidental contact.

The chase must be properly blocked to prevent blown insulation or other combustibles from entering and making contact with fi replace or chimney.

Failure to maintain airspace may cause overheating and a fire.

1-1/2 in.(38 mm)

D

 

1-1/2 in.

(38 mm)

1/2 in. (13 mm)

Drywall

Combustible flooring may be installed next to the front of the appliance.

0 in.

B

C

A

30in. (762 mm) to ceiling

Object

36 in.

 

0 in. TO LEVEL OF STANDOFFS

 

 

A

B

C

D

 

 

Rough

Rough

Rough

Rough

 

 

Opening

Opening

Opening

Opening

Model #

(Width)

(Height)

(Depth)

(vent pipe)

IDV4833I

in.

47-1/2

45-1/2

30-1/2

10

mm

1207

1156

775

254

 

IDV6247I

in.

61-1/2

50

30-1/2

10

mm

1562

1270

775

254

 

Combustible

(914 mm)

 

 

Adjust framing dimensions for interior sheathing (such as sheetrock)

 

Note: Wiring for and the installation of the heat zone must be done

O in.

before framed enclosure is completed.

Figure 5.2 Clearances to Combustibles

18

Heatilator • ICON DV-IDV Series • 4042-575 • Rev. S • 5/11

Image 18
Contents Installation and Operation IDV6247IH, IDV6247ILHCongratulations Homeowner Reference InformationTable of Contents Troubleshooting Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Gas Fireplace Safety Operating InstructionsYour Fireplace Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Decorative Doors and Fronts H. Lighting Instructions IPI Final inspection byInitial Break-in Procedure Flame Adjustment ControlFrequently Asked Questions After Fireplace is LitMaintenance and Service Maintenance Tasks-HomeownerMaintenance Tasks-Qualified Service Technician Getting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Framing and Clearances Select Appliance LocationConstruct the Appliance Chase ClearancesMantel and Wall Projections MantelsMantel Legs or Wall Projections Termination Locations Vent Termination Minimum ClearancesMinimum Clearances for Termination Vent Table Key Vent Information and DiagramsApproved Pipe Use of ElbowsVent Diagrams Top Vent Horizontal TerminationTwo 45 Elbows replacing One 90 Elbow Two ElbowsInstalled Vertically Three ElbowsInstall Flue Restrictor Top Vent Vertical TerminationNo Elbow 12 ft 3.66 m min 60 ft 18.29 m max Wall Penetration Framing Vent Clearances and FramingPipe Clearances to Combustibles Combustible Wall PenetrationInstall the Ceiling Firestop Ceiling firestop Must be used between floors and at- ticsInstall Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation Appliance Preparation Secure and Level the ApplianceAssemble Vent Sections Install Vent PipeAttach Pipe to the Firebox Assembly Assemble Pipe SectionsAssemble Slip Sections Secure the Vent SectionsInstall Metal Roof Flashing Disassemble Vent SectionsAssemble and Install Storm Collar 13 Assembling the Storm CollarInstall Vertical Termination Cap Heat Shield Requirements for Horizontal TerminationInstall Horizontal Termination Cap InteriorField Constructed Shrouds ShroudsHHT Shrouds Open Top Shroud may be used with DVP-TV, DVP-TVHW, SLP-TVHWMailbox Style Shroud Dimensions Min. Base Dims Gas Pressure Gas InformationFuel Conversion Gas ConnectionIntellifire Ignition System Wiring Wiring RequirementsOptional Accessories Requirements Electrical Service and RepairJunction Box Installation Remove Two Screws From BracketFinishing Facing MaterialNon-combustible Finishing Material ModelAppliance Setup Install the Logs Base logs are pre-installed Place three top logsPlace Lava Rock and Rockwool Glass Panel Assembly Removing/Replacing Glass AssemblyEyelet Rod Support Open Refractory Package Figure Installing External RefractoriesInstall Side Refractories Bottom Front Hearth RefractoryAir Shutter Setting 24 Air Shutter AdjustmentTroubleshooting Intellifire Ignition SystemVerify that wire harness is firmly connected to the module Appliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP45DVP-TRAPFL DVP-TVHW DVP-TRAP DVP-HRC-SS Contact Information Do not Discard this Manual

IDV4833IT specifications

The Heatiator IDV4833IT is an innovative and efficient heating solution, ideal for homeowners seeking both aesthetics and functionality. This contemporary gas fireplace blends seamlessly with modern interior designs while offering powerful heating capabilities.

One of the standout features of the IDV4833IT is its impressive heating capacity, capable of efficiently warming spaces of up to 1,600 square feet. This makes it an excellent choice for larger rooms or open-concept living areas, ensuring consistent warmth during colder months. The fireplace is powered by natural gas or propane, providing flexibility depending on local availability and preference.

A defining characteristic of the Heatiator IDV4833IT is its advanced technology. The unit is equipped with a programmable thermostat, allowing users to set and maintain their desired temperature efficiently. This feature not only enhances comfort but also optimizes fuel consumption, making it an eco-friendly option. The fireplace also includes an easy-to-use remote control system, enabling users to adjust settings from across the room without any hassle.

The design of the IDV4833IT stands out with its sleek, linear appearance and large viewing area, framed by a minimalist façade. The expansive glass panel provides a captivating view of the flames, adding a touch of elegance to any living space. The adjustable flame height allows homeowners to customize the ambiance, creating a cozy atmosphere for gatherings or a tranquil setting for relaxation.

Additionally, the Heatiator IDV4833IT is designed with safety in mind. It features a built-in safety shut-off system that automatically turns off the gas supply in case of malfunction. The unit also includes a protective barrier to prevent accidental contact with the hot glass surface, ensuring peace of mind for families with children or pets.

In summary, the Heatiator IDV4833IT combines aesthetic appeal with advanced heating technology. Its substantial heating capacity, programmable thermostat, and user-friendly design make it an ideal choice for those seeking a reliable and stylish heating solution. Emphasizing safety and efficiency, this fireplace stands as a testament to modern home heating solutions and an investment in comfort for years to come.