Heatiator IDV4833IT owner manual Install Horizontal Termination Cap, Interior

Page 37

I. Install Horizontal Termination Cap

WARNING! Risk of Fire! The telescoping flue section of the termination cap MUST be used when connecting vent.

1-1/2 (38 mm) minimum overlap of flue telescoping section is required.

Failure to maintain overlap may cause overheating and fire.

Vent termination must not be recessed in the wall. Siding may be brought to the edge of the cap base.

Flash and seal as appropriate for siding material at outside edges of cap.

When installing a horizontal termination cap, follow the cap location guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149installation codes and refer to Section 6 of this manual.

CAUTION! Risk of Burns! Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap.

NOTICE: For certain exposures which require superior resistance to wind-driven rain penetration, a flashing kit and HRC caps are available. When penetrating a brick wall, a brick extension kit is available for framing the brick.

Note: When using termination caps with factory-supplied heat shield attached, no additional wall shield firestop is required on the exterior side of a combustible wall.

Heat Shield or

Heat Shield

Extended

1-1/2 in. (38 mm) min.

Wall Shield Heat Shield

overlap

Firestop

 

Slip Section

 

can be extended

 

Inner Vent

SHEATHING

Outer Vent

INTERIOR

EXTERIOR

Vent depth from back of appliance to

 

outside surface of exterior wall

 

(see chart below)

 

Figure 10.16 Venting through the wall

 

Cap Specification Chart (depth without using additional pipe sections)

 

DVP-TRAPK1

DVP-TRAP1

DVP-TRAPK2

DVP-TRAP2

 

Top Vent Depth

Rear Vent Depth

Top Vent Depth

Rear Vent Depth

 

3-1/2 to 5-3/8 in.

NA

5-7/8 to 9-7/8 in.

NA

IDV Series

 

 

 

 

 

 

 

 

 

 

DVP-HPC1

DVP-HPC1

DVP-HPC2

DVP-HPC2

 

Top Vent Depth

Rear Vent Depth

Top Vent Depth

Rear Vent Depth

 

3-1/2 to 5-5/8 in.

NA

5-5/8 to 9-3/4 in.

NA

DVP-TRAP1 can adjust 1-7/8 in. (4-3/16 to 6-1/16)

DVP-TRAP2 can adjust 4 in. (6-9/16 to 10-9/16)

DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8)

DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2)

Heatilator • ICON DV-IDV Series • 4042-575 • Rev. S • 5/11

37

Image 37
Contents IDV6247IH, IDV6247ILH Installation and OperationHomeowner Reference Information CongratulationsTable of Contents Troubleshooting Limited Lifetime Warranty Limited Lifetime WarrantyWarranty Conditions Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Operating Instructions Gas Fireplace SafetyYour Fireplace Remote Controls, Wall Controls and Wall Switches Fixed Glass AssemblyClear Space Decorative Doors and FrontsFinal inspection by  H. Lighting Instructions IPIFrequently Asked Questions Flame Adjustment ControlInitial Break-in Procedure After Fireplace is LitMaintenance Tasks-Homeowner Maintenance and ServiceMaintenance Tasks-Qualified Service Technician Typical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Select Appliance Location Framing and ClearancesClearances Construct the Appliance ChaseMantels Mantel and Wall ProjectionsMantel Legs or Wall Projections Vent Termination Minimum Clearances Termination LocationsMinimum Clearances for Termination Approved Pipe Vent Information and DiagramsVent Table Key Use of ElbowsTop Vent Horizontal Termination Vent DiagramsTwo Elbows Two 45 Elbows replacing One 90 ElbowThree Elbows Installed VerticallyTop Vent Vertical Termination Install Flue RestrictorNo Elbow 12 ft 3.66 m min 60 ft 18.29 m max Pipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Combustible Wall PenetrationCeiling firestop Must be used between floors and at- tics Install the Ceiling FirestopFlat Ceiling Installation Install Attic Insulation ShieldVaulted Ceiling Installation Secure and Level the Appliance Appliance PreparationAttach Pipe to the Firebox Assembly Install Vent PipeAssemble Vent Sections Assemble Pipe SectionsSecure the Vent Sections Assemble Slip SectionsDisassemble Vent Sections Install Metal Roof Flashing13 Assembling the Storm Collar Assemble and Install Storm CollarHeat Shield Requirements for Horizontal Termination Install Vertical Termination CapInterior Install Horizontal Termination CapHHT Shrouds ShroudsField Constructed Shrouds Open Top Shroud may be used with DVP-TV, DVP-TVHW, SLP-TVHWMailbox Style Shroud Dimensions Min. Base Dims Fuel Conversion Gas InformationGas Pressure Gas ConnectionOptional Accessories Requirements Wiring RequirementsIntellifire Ignition System Wiring Electrical Service and RepairRemove Two Screws From Bracket Junction Box InstallationFacing Material FinishingModel Non-combustible Finishing MaterialAppliance Setup Base logs are pre-installed Place three top logs Install the LogsPlace Lava Rock and Rockwool Removing/Replacing Glass Assembly Glass Panel AssemblyEyelet Rod Support Install Side Refractories Installing External RefractoriesOpen Refractory Package Figure Bottom Front Hearth Refractory24 Air Shutter Adjustment Air Shutter SettingIntellifire Ignition System TroubleshootingVerify that wire harness is firmly connected to the module Reference Materials Appliance Dimension DiagramDVP45 Vent Components DiagramsDVP-TRAPFL DVP-TVHW DVP-TRAP DVP-HRC-SS Do not Discard this Manual Contact Information

IDV4833IT specifications

The Heatiator IDV4833IT is an innovative and efficient heating solution, ideal for homeowners seeking both aesthetics and functionality. This contemporary gas fireplace blends seamlessly with modern interior designs while offering powerful heating capabilities.

One of the standout features of the IDV4833IT is its impressive heating capacity, capable of efficiently warming spaces of up to 1,600 square feet. This makes it an excellent choice for larger rooms or open-concept living areas, ensuring consistent warmth during colder months. The fireplace is powered by natural gas or propane, providing flexibility depending on local availability and preference.

A defining characteristic of the Heatiator IDV4833IT is its advanced technology. The unit is equipped with a programmable thermostat, allowing users to set and maintain their desired temperature efficiently. This feature not only enhances comfort but also optimizes fuel consumption, making it an eco-friendly option. The fireplace also includes an easy-to-use remote control system, enabling users to adjust settings from across the room without any hassle.

The design of the IDV4833IT stands out with its sleek, linear appearance and large viewing area, framed by a minimalist façade. The expansive glass panel provides a captivating view of the flames, adding a touch of elegance to any living space. The adjustable flame height allows homeowners to customize the ambiance, creating a cozy atmosphere for gatherings or a tranquil setting for relaxation.

Additionally, the Heatiator IDV4833IT is designed with safety in mind. It features a built-in safety shut-off system that automatically turns off the gas supply in case of malfunction. The unit also includes a protective barrier to prevent accidental contact with the hot glass surface, ensuring peace of mind for families with children or pets.

In summary, the Heatiator IDV4833IT combines aesthetic appeal with advanced heating technology. Its substantial heating capacity, programmable thermostat, and user-friendly design make it an ideal choice for those seeking a reliable and stylish heating solution. Emphasizing safety and efficiency, this fireplace stands as a testament to modern home heating solutions and an investment in comfort for years to come.