Desa Tech CGN30TL, CGN20TL Fresh AIR, Determining FRESH-AIR Flow for Heater Location

Page 6

FRESH AIR

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

FOR

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

COMBUSTION

Space: Includes the room in which you will install heater plus any adjoining rooms

AND

with doorless passageways or ventilation grills between the rooms.

VENTILATION

1. Determine the volume of the space (length x width x height).

 

Continued

Length x Width x Height = _________________

cu. ft. (volume of space)

Example:

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =

 

 

 

2560 cu. ft. (volume of space)

 

 

 

If additional ventilation to adjoining room is supplied with grills or openings, add

 

the volume of these rooms to the total volume of the space.

 

2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the

 

space can support.

 

 

 

 

 

___________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can

 

support)

 

 

 

 

 

 

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum

 

Btu/Hr the space can support)

 

 

 

 

 

3. Add the Btu/Hr of all fuel burning appliances in the space.

 

 

Vent-free heater

 

_________________ Btu/Hr

 

 

Gas water heater*

 

_________________ Btu/Hr

 

 

Gas furnace

 

_________________ Btu/Hr

 

 

Vented gas heater

 

_________________ Btu/Hr

 

 

Gas fireplace logs

 

_________________ Btu/Hr

 

 

Other gas appliances*

+ _________________ Btu/Hr

 

 

Total

= _________________ Btu/Hr

 

Example:

Gas water heater

 

40,000

 

Btu/Hr

 

 

Vent-free heater

+

20,000

 

Btu/Hr

 

 

Total

=

60,000

 

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_______________

Btu/Hr (maximum the space can support)

_______________

Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200

Btu/Hr (maximum the space can support)

60,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

6

103873

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety InformationIf you smell gas Product Identification Local Codes Unpacking Product FeaturesSafety Device Piezo Ignition SystemFresh AIR For VentilationProviding Adequate Ventilation Fresh AIR Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Fresh AIR for Combustion and Ventilation Ventilation AIRVentilation Air From Inside Building Ventilation Air From Outdoors Ventilation Air from OutdoorsCheck GAS Type Installing to WallInstallation Items Locating HeaterThermostat Sensing Bulb Locating Thermostat Sensing BulbAttaching Thermostat Sensing Bulb Bracket Greater clearances from floor and joining wall Marking Screw LocationsMaintain minimum clearances shown in . If you can, provide Attaching Mounting Bracket To WallInstalling Bottom Mounting Screws Placing Heater On Mounting BracketConnecting to GAS Supply Supply ConnectingTo GAS Checking GASPressure Testing Heater GAS Connections CheckingFor Your Safety Read Before Lighting Operating HeaterOperating Heater Shutting Off Heater Shutting Off Burner Only pilot stays litInspecting Burner Pilot Flame PatternBurner Flame Pattern Correct Burner Flame PatternTrouble Shooting ODS/PILOT and BurnerCabinet Cleaning and Mainte TroubleIng and Maintenance TROUBLE- ShootingDo not try to light any appliance If you smell gasShut off gas supply BuildingTechnical Service Service Hints Service Publications20,000 Btu/Hr Models Parts Under Warranty Parts CentralsCGN20T CGN20TL CGN30T CGN30TL Parts List Description QTYAccessories Valve GA5010103873 Warranty Information Keep this Warranty