Desa CLD3018N, CLD3924NT Checking GAS Connections, Pressure Testing gas Supply Piping system

Page 12

CGS2718N, CGS3124N, CLD3018N,

CLD3924NT, and CCL3930NT(A)

UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing gas Supply Piping system

Test Pressures In Excess Of 1/2 PSIG

1.

Disconnect heater and its individual

 

manual shutoff valve from gas supply

 

piping system. Pressures in excess of

 

1/2 psig will damage heater regulator.

2.

Cap off open end of gas pipe where

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 14).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 15). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Manual

 

 

Shutoff Valve

 

 

 

ON

 

 

Open

 

 

POSITION

OFF

POSITIONClosed

Figure 14 - Manual Shutoff Valve

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Fig- ure 14).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 15). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 16 and 17 [manually-controlled models] or pages 17 and 18 [thermo- statically-controlled models]). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 17 [manually-con- trolled models] or page 18 [thermostati- cally-controlled models]).

 

manual shutoff valve was connected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or opening

 

main gas valve located on or near gas

 

meter.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and manual shutoff

 

valve to gas supply. Check reconnected

 

fittings for leaks.

Manual

 

Shutoff

Control Valve Location

Valve

 

Gas Meter

 

Figure 15 - Checking Gas Joints

12

104385

Image 12
Contents What to do if YOU Smell GAS Winchester Oak Model ShownPatent Pending Safety Information Unvented Natural GAS LOG HeaterProduct Features Product IdentificationLocal Codes UnpackingAIR for Combustion and Ventilation Providing Adequate VentilationUnusually Tight Construction Confined Space and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From InsideBuilding Ventilation Air From OutdoorsInstallation Check GAS TypeMinimum Wall and Ceiling Clearances see Figure If Using Mantel If Not Using MantelMinimum Noncombustible Material Clearances Mantel Clearances Floor ClearancesDetermining Minimum Mantel Clearance Installing Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyInstallation Items Needed Chimney Minimum Permanent Height ft Flue Opening sq. insConnecting to GAS Supply Attaching Flexible Gas Hose to Heater Gas RegulatorPressure Testing gas Supply Piping system Pressure Testing Heater Gas ConnectionsChecking GAS Connections Test Pressures In Excess Of 1/2 PsigInstalling Logs on Models CGS2718N and CGS3124N Installing Back LogInstalling Logs on Models CLD3018N and CLD3924NT Damage or personal injuryInstalling Logs on Model CCL3930NTA Front Log #1 Grate Fingers Grate BaseFor Your Safety Read Before Lighting Operating HeaterLighting Instructions Manual Lighting Procedure Variable Control OperationTo Turn OFF GAS To Appliance Shutting Off HeaterInspecting Burners Thermostat Control OperationPilot Flame Pattern Burner Primary AIR HolesCleaning and Maintenance Cleaning Burner Injector Holder and Pilot AIR Inlet HoleMain Burner ODS/PILOT and BurnerTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Top Gas leak. See Warning statement atOptional POSI- Tioning of THER- Mostat Sensing Bulb For Masonry and Factory- built Metal FireplaceSpecifications Technical ServiceService Hints Replacement PartsAccessories Parts CentralManual Shutoff Fireplace HoodIllustrated Parts Breakdown Parts List CGS2718N CGS3124NUnvented Natural GAS LOG Heater CLD3018N CLD3924NT KEY CLD3924NT Part Number Description QTY CCL3930NTA CCL3930NT CCL3930NTA CCL3930NT CCL3930NTAWarranty Information