Desa BLUE FLAME VENT-FREE NATURAL GAS HEATER Ventilation AIR, Ventilation Air From Outdoors

Page 5

OWNER’S MANUAL

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op- tion 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventila- tion grills or ducts.

12"

Figure 2 - Ventilation Air from Inside Building

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

103113

5

Image 5
Contents BTU Manually Controlled Models Blue Flame VENT-FREE Natural GAS HeaterVanguard 6000 BTU Natural GAS Heater Safety InformationProduct Product FeaturesAIR for Combustion and Ventilation Local CodesUnusually Tight Construction Determining AIR Flow for Heater LocationConfined and Unconfined Space Determining if You Have a Confined or Unconfined SpaceVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Wall Installing toInstalling Bottom Mounting Screw Installing to WallAttaching to wall anchor method Placing Heater On Mounting ScrewsMinim um Connecting to GAS SupplyPressure Testing Heater GAS Connections Pressure Testing GAS Supply Piping SystemFor Your Safety Read Before Lighting Checking GAS ConnectionsLighting Instructions Manual Lighting ProcedureTo Turn OFF GAS To Appliance Shutting Off HeaterInspecting Burner Cleaning and MaintenanceObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Trouble ShootingGas leak. See Warning statement at top Replacement Parts SpecificationsTechnical Service Service PublicationsIllustrated Parts List Models VN600B and CFN600B Vanguard 6000 BTU Natural GAS Heater 103113 Limited Warranty VENT-FREE Residential GAS Heaters Warranty Information